ZBM 2 BATTERY - Cellnexx Energy

Transcription

ZBM 2 BATTERY - Cellnexx Energy
ZBM 2 : Zinc Bromide Module
ZBM 2 BATTERY
Store and shift renewable energy, manage peak grid load,
support off-grid power systems and Uninterrupted Power
Supply (UPS) with the Redflow ZBM.
High energy density at 10kWh
Warranted life of 10 years, 30MWH energy
throughput at 100% daily discharge
Suitable for parallel or series configurations
Power Rating 3kW (5kW peak)
10kWh
48V
ZBM 2
Why Zinc-Bromide Flow Battery Technology
COMPETITIVE CAPEX
100% of the capacity is usable over lifetime, with no
capacity fading therefore no over sizing required
COMPACT AND HIGH ENERGY DENSITY
0.34m2 (3.7ft2) with expected electrode stack
throughput 40,000kWh
BEST IN CLASS LCOS
Warranted life of 10 years or 30MWH energy throughput based on
100% daily discharge - 3000 cycles at 100% depth of discharge
GREATER SAFETY
Fire retardant electrolyte, no thermal runaway due to
separated tank and stack
UNLIMITED SHELF LIFE
Sustains regular outages without battery damage and
can be suspended, stored or hibernated from 0% to 100%
state of charge
No fire suppression system necessary or safety abuse
testing required
RECYCLE OR REPURPOSE
For all Redflow battery components and electrolyte
CONSTANT POWER
Charge 100% of the capacity with constant power, due to a flat
voltage curve and simple one stage charge profile
NO ACTIVE COOLING REQUIRED
Lifetime, safety and performance are not affected by temperature
INTUITIVE WEB BASED MANAGEMENT SYSTEM
24/7 remote self-monitoring with real-time data capture accessed
via the web, through the MODBUS communications system
ZBM MANUFACTURED BY FLEX for REDFLOW
Building blocks to advanced energy storage features
100% depth of discharge is perfect for
intermittent energy sources with no battery
damage from regular power outages.
TELECOMMUNICATION
APPLICATIONS
Redflow batteries are suited to storing
long-duration and renewable energy during
times of high generation and discharging it
during peak periods.
RENEWABLES
INTEGRATION
ON AND OFF GRID
REMOTE POWER
Enables grid peak shifting and shaving for
utilities and consumers.
MICRO GRID AND
SMART GRID
Our flow batteries reduce the cost of
generating energy by storing and shifting
renewables for anytime use.
TRANSMISSION AND
DISTRIBUTION DEFERRAL
ZBM 2 : Zinc Bromide Module
TYPICAL CHARGE AND DISCHARGE CURVE
Battery Voltage vs Battery Current
Battery Voltage vs Battery Current
40
20
0
-20
2
30
30
20
20
00
-60
4
6
8
20
20
10
12
14
16
18
20
-20
-20
-80
-40
-40
TIME (HR)
10
10
00
40
40
-40
40
40
10
0
20
50
50
30
60
60
40
60
60
50
VOLTAGE (V)
(V)
VOLTAGE
VOLTAGE (V)
60
70
70
60
80
80
80
CURRENT (A)
70
BATTERY CURRENT
00
22
-60
-60
BATTERY VOLTAGE
44
CURRENT (A)
(A)
CURRENT
80
80
80
0
Discharge Curves
66
88
Discharge - Capacity Curves
10
10
12
12
TIME
TIME (HR)
(HR)
BATTERY
BATTERYCURRENT
CURRENT
14
14
16
16
18
18
20
20
-80
-80
Energy - Capacity Curves
BATTERY
BATTERYVOLTAGE
VOLTAGE
Technical Specifications:
VOLTAGE: 48 Volt DC nominal batteries (typical operating range 40-60V)
SAFETY DATA SHEET: DG Class 8 for electrolyte
CAPACITY: Maximum 10kWh energy output per daily cycle. No reserved
battery capacity requirement - full 10kWh cycle depth available
DIMENSIONS: 845L x 823H x 400W (mm); 33L x 32H x 16W (in)
POWER RATING: 3kW (5kW peak)
+ 3kW continuous: current up to 75A (40V disconnection point)1
+ 5kW duration depending on the State of Charge (SOC):
current up to 125A (40V disconnection point)1, 2
WEIGHT: 240kg (530 lb) with electrolyte; 90kg (198 lb) without electrolyte
REGULATORY COMPLIANCE MARK:
ELECTROLYTE VOLUME: 100L (26Gal)
WARRANTY:
Warranted electrode stack lifetime 30,000kWh energy throughput or
10 years (whichever comes first). Expected electrode stack throughput
40,000kWh. No cycle depth limitations - battery performance and
lifetime is not sensitive to cycle depth
NET ENERGY EFFICIENCY: 80% DC-DC Max
OPERATING ELECTROLYTE TEMPERATURE RANGE:
15°C to 50°C (50°F to 122°F), ZBM2 can typically operate at ambient
temperatures outside this range for extended periods
COMMUNICATION: MODBUS RS485
10kWh
48V
1 Values reported for ZBM2 at 100% state of health (SOH) and room temperature
2 Redflow internal testing shows a 5kW supply for approximately 45 minutes before
disconnection, for a ZBM2 starting at 100% state of charge (SOC)
UK Head Office:
Brambles | Scotter Common | Gainsborough | Lincolnshire | DN21 3JF
For more information:
visit: www.cellnexx.co.uk or email: [email protected] or call: (+44) 1724 304 001
Copyright © 2016 Cellnexx Energy Limited. All rights reserved
TELECOMMUNICATION
APPLICATIONS
RENEWABLES
INTEGRATION
ON AND OFF GRID
REMOTE POWER
MICRO GRID AND
SMART GRID
TRANSMISSION AND
DISTRIBUTION DEFERRAL