KAPPA Rev Low GWP Brochure

Transcription

KAPPA Rev Low GWP Brochure
Kappa Rev LGW
245÷1229 kW
Air cooled & freecooling modular screw chiller
General
Bullet points
High energy efficiency chillers and freecooling chiller
with screw compressors and shell&tube exchanger.
►► High seasonal efficiency
►► Eurovent A Class Unit
►► Low refrigerant charge
►► Microchannel condensing coil
►► Multilogic and Multifree function
►► Integrated web server
►► Wide operating limits
Configurations
HE: High efficiency unit
LN: Low noise unit
SLN: Super Low noise unit
DS: Unit with desuperheaters
DC: Heat exchange condenser
HAT: unit for high temperature of external air
Pump and integrated buffer tank available as option
►► Integrated hydraulic modules also with a buffer
tank.
►► Three types of pumps: standard, oversize and for
high percentages of glycol (e.g. up to 50%).
F-gases
Fluorinated gases (‘F-gases’) are man-made gases used in a range of industrial applications. Because they do not damage the
atmospheric ozone layer, they are often
used as substitutes for ozone-depleting
substances. However, F-gases can stay in
the atmosphere for centuries and contribute to a global greenhouse effect, with
a global warming effect up to 8000 times
greater than carbon dioxide (CO2), and
their emissions are rising strongly.
The three groups of F-gases are hydrofluorocarbons (HFCs), perfluorocarbons
(PFCs) and sulphur hexafluoride (SF6).
HFCs are by far the most relevant F-gases
from a climate perspective.
F-gases account for 2% of the EU’s overall greenhouse gas emissions, but F-gas
emissions have risen by 60% since 1990
in contrast to all other greenhouse gases,
which have been reduced.
F-gas emissions
to be cut by two-thirds by 2030
The European Union is therefore taking regulatory action to control F-gases as part
of its policy to combat climate change.
A new Regulation, which replaces the first
and applies from 1 January 2015, strengthens the existing measures and introduces a number of far-reaching changes. By
2030 it will cut the EU’s F-gas emissions
by two-thirds compared with 2014 levels.
This represents a fair and cost-efficient
contribution by the F-gas sector to the EU’s
objective of cutting its overall greenhouse
gas emissions by 80-95% of 1990 levels
by 2050.
The expected cumulative emission savings are 1.5 Gigatonnes of CO2-equivalent
by 2030 and 5 Gigatonnes by 2050. The
latter number is more than the CO2 produced by a billion return flights from Paris
to New York.
DANGEROUS
MILDLY
NON
CURRENT
FLAMMABLE FLAMMABLE REFRIGERANT
Alternative refrigerant going
forward for commercial
HVAC application
R134a
GWP=2088
R134a & R1234ze
R32 & R1234ze
blended
blended
GWP 600
GWP 600
R1234ze
R32
GWP <1
R1234yf
GWP 675
GWP <1
R290
R717
GWP 3
GWP 0
HIGH FLAMMABLE
F-gas emissions
to be cut by two-thirds
R410A
GWP=1430
(Propane)
2030
(Ammonia)
HIGH FLAMMABLE
AND TOXIC
HFOs
ODP=0
GWP<1
R1234yf
R1234ze
2006
R744
(Carbon dioxide)
GWP 1
HIGH WORKING
PRESSURE
GWP
Global-warming potential (GWP) is a relative measure
of how much heat a greenhouse gas traps in the atmosphere.
It compares the amount of heat trapped by a certain
mass of the gas in question to the amount of heat trapped by a similar mass of carbon dioxide.
A GWP is calculated over a specific time interval, commonly 20, 100 or 500 years. GWP is expressed as a
multiplying factor of carbon dioxide value that is standardized equal to GWP=1.
In the past, refrigerants artificial category HCFC (HydroChloro-Fluoro-Carbides) were used but, later were banded because they were one of main causes of Ozone
layer depletion (high ODP value).
Currently mainly used refrigerants as HCFC subsitutes,
belong to HFC category (Hydro-Fluoro-Carbides) with
ODP=0, but with still strong greenhouse effect (HIgh
GWP).
Natural refrigerants (R744, R717) and hydrocarbons HC
(R290) represent an alternative to HFCs but with several
implications and limitations.
New chemical refrigerants belonging to HFO category (Hydro-Fluoro-Olefin) like R1234ze/R1234yf
offer a good alternative to HFC, offering:
• Adaptation to exhisting Chillers Design
• Higher Efficiency
• Longer life of components
• Suitable for all climate zones
HFCs
ODP=0
GWP 1400÷3500
R410A
R407C
R404A
R134a
mid 1990
HCFCs
high ODP & GWP
R123
R22
CFCs
very high ODP
& GWP
R12
1990
WIDE CAPACITY RANGE
STD | 244÷1.226 kW on 25 sizes
2,3,o 4
compressors
/HE - high efficiency | 263÷1.042 kW on 18 sizes
/SLN - super low noise | 253÷1.004 kW on 18 sizes
200
400
600
chiller only
800
1000
1.200
freecooling available
CONTROL FUNCTION (HFO OPTIMIZED)
Unit management by integrated web server page
(alarms, set points, antisticking function...)
User friendly interface based on visual icons
MULTILOGIC FUNCTION
Up to 32 units (1 Master e 31 Slave) connected to the same hydronic circuit
Management of units with different logics and priority levels
ETHERN
ET
USB
MULTIFREE FUNCTION
Maximise the efficiency using the freecooling from stand-by unit in n+1 configuration.
MICROCHANNEL
ALUMINIUM COIL
Kappa Rev LGW units use this new generation of condensing coil on chiller section as standard.
This means:
•Extended life cycle
•10% overall chiller weight reduction
•less air side pressure drop
30% less refrigerant
LEAK
DETECTION
The unit is equipped of a leak
detector located in the compressor compartement, with
the pump down function that
encloses the refrigerant in the
condensing coil.
R1234ze has been classified on
safety group 2 for PED (european standard).
Unit size
Cooling capacity (A35; W7)
Total absorbed power
EER
Efficiency class
Water flow (A35; W7)
Pressure drop (A35; W7)
Unit size
Cooling capacity (A35; W7)
Total absorbed power
EER
Efficiency class
Water flow (A35; W7)
Pressure drop (A35; W7)
33.2
245
82
3,01
B
42,1
22
35.2
271
82
3,22
A
46,5
26
Kappa Rev STD
37.2
40.2
43.2
296
326
365
82
82
82
3,05
2,91
2,87
B
B
C
51,0
56,0
62,8
31
38
20
51.2
384
82
2,92
B
66,1
28
54.2
429
82
2,93
B
73,8
34
58.2
487
82
2,87
C
83,8
25
67.2
548
82
2,97
B
94,2
30
73.2
586
82
3,05
B
100,7
34
80.2
626
82
3,12
A
107,6
23
85.2
668
82
3,01
B
114,9
26
90.2
708
82
2,90
C
121,7
30
95.2
757
82
2,92
B
130,2
35
115.2
887
82
2,91
B
152,6
18
120.2
957
82
2,94
B
164,5
21
130.2
1027
82
3,00
B
176,6
23
140.3
1146
82
2,89
C
197,1
28
150.3
1192
82
2,89
C
205,0
24
160.3
1229
82
2,88
C
211,3
25
kW
kW
m3/h
kPa
kW
kW
m3/h
kPa
100.2 105.2
791
832
82
82
2,90
2,89
C
C
136,0 143,1
38
34
Kappa Rev HE
m3/h
kPa
kW
kW
m3/h
kPa
37.2
311
95
3,28
A
53,4
17
40.2
354
108
3,30
A
61,0
25
43.2
395
119
3,31
A
68,0
29
51.2
415
126
3,30
A
71,4
19
54.2
460
140
3,29
A
79,1
23
58.2
540
164
3,29
A
92,9
18
67.2
587
179
3,29
A
101,0
20
73.2
618
188
3,29
A
106,2
22
80.2
652
198
3,30
A
112,2
25
85.2
710
215
3,31
A
122,2
30
90.2
764
231
3,30
A
131,5
35
95.2
821
248
3,31
A
141,2
34
100.2
871
262
3,32
A
149,8
37
105.2
915
278
3,29
A
157,4
18
115.2
970
295
3,29
A
166,8
20
120.2
1044
317
3,29
A
179,5
23
MODULAR
FREECOOLING
AVAILABLE
Kappa Rev LGW allow all combinations
with 3 freecooling levels. Every chiller
version can be couple with the different
freecooling sections.
Chiller
Extra
kW
35.2
294
90
3,28
A
50,6
15
Custom
Unit size
Cooling capacity (A35; W7)
Total absorbed power
EER
Efficiency class
Water flow (A35; W7)
Pressure drop (A35; W7)
kW
33.2
264
80
3,31
A
45,4
26
Basic
Unit size
Cooling capacity (A35; W7)
Total absorbed power
EER
Efficiency class
Water flow (A35; W7)
Pressure drop (A35; W7)
fc
fc
fc
TFT: total freecooling temperature
t
f
t.
*
eer
*
up to
3
.
3
4C
up to
TFT: total freecooling temperature
* External air temperature 30°C; Inlet outle water temperature 10-15°C; Glycol 30%
Blue Box applied product range
find outthe complete product range on our web site and catalogues
Zeta Echos > 40÷140 kW
Beta Echos > 40÷301 kW
High efficiency air cooled chillers and heat pumps.
Tetris series > 84÷913 kW
High efficiency air cooled modular chillers and heat pumps.
Tetris W series > 32÷615 kW
High efficiency water cooled chillers and heat pumps with integrated hydronic module. .
Omega V Echos series > 143÷1569 kW
High efficiency water cooled chillers.
Omicron S Evo > 31÷226 kW
Air cooled multifunctional units for indipendet production of domestic hot
water, heating and cooling.
Omicron V Evo > 230÷773 kW
Air cooled multifunctional units for indipendet production of domestic hot
water, heating and cooling.
Blue Box Group S.r.l.
Via Valletta, 5 - 30010 Cantarana di Cona, (VE) Italy
www.bluebox.it - [email protected]
Phone +39 0426 921111 - Fax +39 0426 302222