Installation & Maintenance Instructions
WARNING !
Isolate electrical supply before commencing fitting.
Cover Removal
Remove the four M5 hex head screws which secure the cover to the base.
Lift cover clear.
Switchbox Mounting To Actuator
Ensure actuator and switchbox are both in the same mode i.e. fully OPEN or fully CLOSED
position.
Using the four M5 socket head cap screws and four nyltite washers provided, mount the
switchbox to the actuator by placing the screws and the washers into the four holes in the base of
the switchbox and securing to the actuator top or mounting plat.
If open indication is required on the top of the switchbox, use the open indication label
supplied with the mounting kit.
If the actuator is transversely mounted to the pipe axis, use both labels supplied with mounting kit.
Use open
to superimpose over closed marking on the side of the actuator.
Use closed
on the flat part of the switchbox.
Note: for Units fitted to actuators transversely mounted across the pipeline cams may need to be
reset. (see setting procedure).
Wiring
Remove conduit transit plug to gain access to wiring terminals. Wire in accordance with the
appropriate diagram on page 19 or see underside of switchbox cover. Customers wiring 2.5 mm2
maximum conductor size.
Limit Switch Setting
Note: Limit switches are factory set to 0° and 90° ± 2 degrees.
• Remove cover assembly by removing 4-off cover screws.
• Operate to the fully OPEN position, slacken central M3 cheese head screw two turns.
• Adjust top cam by turning adjusting screw marked “OPEN” using a small flat blade screwdriver.
Clockwise movement turns the cam away from the switch. Anticlockwise movement turns the
cam into the switch.
• Operate to fully closed position.
• Adjust bottom cam by turning adjusting screw marked “CLOSE” using the screwdriver.
Clockwise movement turns the cam into the switch. Anticlockwise movement turns the cam
away from the switch.
• After setting the cams, retighten the central clamping screw firmly and check that the switch
setting is as required.
Simple Check List
1. When fitting the Low Profile switchbox to model 002 pneumatic actuators, ensure the required
mounting plate is fitted and secure.
2. Switchbox conduit adaptors must be of correct size to effectively seal the unit. Use of a thread
sealant is recommended.
3. Ensure switchbox is securely fitted to the actuator.
4. Ensure cover screws are secure.
5. Ensure the fit between the actuator output shaft and switchbox shaft is correct i.e. no backlash.
Note: Top switch open.
Bottom switch closed.
www.tycoflowcontrol-eu.com
Tyco reserves the right to change the contents without notice
EUKGH-0120-EN-0711
Keystone Figure 792 Position Monitor
Installation & Maintenance Instructions
5
3
1
2
4
14
11
6
12
8
7
13
19
20
9
10
18
17
23
16
15
22
24
Materials of construction
Item
Description
Qty
Material
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
22.
23.
24.
Indicator
Indicator Drive
Dome
Cover
Gasket (dome)
Gasket (cover)
Cam & Shaft Assembly (shaft 11 x 16)
Terminal, Switch & Wire assy.
Terminal Stool
Base
M3 x 30 pan head screw
Internal Lock Washer M3
M3 x 6 pan head screw
M5 x 12 hex head screw
External Circlip
Retaining Washer
Plug (yellow)
Plug PG 13.5 (hex head)
M5 x 16 socket head cap screw
Nyltite washer
Adaptor (F79U/E 003)
Adaptor (F79U/E 006-012)
Adaptor (F79U/E 024-090)
1
1
1
1
1
1
1
1
1
1
2
2
1
8
1
1
1
1
4
4
1 A/R
1 A/R
1 A/R
A.B.S.(acrylanitrile butadene styrene)
Acetal
Ektar (DN004 Copolyester)
Aluminium
Neoprene
Neoprene
Acetal
Acetal
Aluminium
Stainless Steel
Stainless Steel
Stainless Steel
Stainless Steel
Spring Steel
Stainless Steel
Plastic
Steel
Steel
Nylon
Plastic
Plastic
Plastic
Tyco reserves the right to change the contents without notice
Keystone Figure 792 Position Monitor
Installation & Maintenance Instructions
Proximity switch details
Technical Data
Type
: Pepperl & Fuchs NJ2-V3-N
or as specified
Sensing distance : 2mm maximum (metal
face). NB. Separate
amplifier required.
Nominal Voltage : 8V DC (Ri approx. 1kOhm)
Repetition
: ≤ 0.01mm
Hysteresis
: ≤ 0.05mm Type 3%
Output
: Sensor absent - 3mA or
above
Sensor present - 1mA or
below
Switching rate -1kHz
maximum
Ratings for V9 microswitches (Single Pole Double Throw SPDT)
Voltage
Resistive load
(Volts)
Tungsten lamp load (amps)
(Amps)
NC
Inductive load
NO
(Amps)
AC
125
250
10
10
2
1.5
1
1
10
10
15
10
3
1
0.5
0.25
3
3
0.8
0.6
0.5
0.25
1.5
1.5
0.8
0.6
0.5
0.25
15
10
2.5
0.5
0.07
0.03
DC
Up to 15
30
50
75
125
250
Wiring Diagrams
(Shown in mid travel)
Blue (-)
5
Output
to lamp
Earth
6
G/Y
6
NC
5
G/Y
Brown (+)
Btm sw.
(Close)
4
4
Blue
3
Red (+)
Brown
Btm sw.
(Close)
2
Black (-)
Top sw.
(Open)
3
Red
NC
Output
to lamp
1
Top sw.
(Open)
Mains
supply
2
Black
1
Yellow
(Shown in mid travel)
Earth
Note! terminal 3 and 4 can also
be used for light indication
Option 1
Low profile switchbox with two V9 microswitches
Option 2
Low profile switchbox with two inductive proximity
sensors
Dimensions (Switchbox rating to IP 65)
142.0
93.5
41.3
87.5
4- holes 5.85 dia
Plan view with cover removed
4.0
Tyco reserves the right to change the contents without notice
4.0
11
79.0
108.0
¿16