MINISTRY OF HEALTH
MALAYSIA
GENERAL REQUIREMENTS FOR
INSTALLATION AND MAINTENANCE
OF A Centralized THREE PHASE
UNINTERRUPTIBLE POWER SUPPLY (UPS)
IN HEALTHCARE FACILITIES
JUNE 2015
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTs FOR
INSTALLATION AND MAINTENANCE
OF A Centralized THREE PHASE
UNINTERRUPTIBLE POWER SUPPLY (UPS)
IN HEALTHCARE FACILITIES
All Right Reserved
No part of this publication may be reproduced, store
in a retrieval system, or transmitted in any form or
by any means, electronic, mechanical, photocopy,
recording, or otherwise without prior notice,
permission of the Ministry of Health Malaysia
MOH/ESD/2015-01
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
CONTENTS
INTRODUCTION
5
DEFINITION
7
LOCATION
9
UPS INSTALLATION
GENERAL REQUIREMENTS
11
MAINTENANCE OF THE UPS
16
REFERENCES
19
ACKNOWLEDGEMENTS
21
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
INTRODUCTION
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
5
6
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
1.0 INTRODUCTION
This guideline on installation and maintenance of a
centralized three phase Uninterruptible Power Supply (UPS)
was generated in response to the recent fire incidents that
occurred in UPS rooms throughout healthcare facilities under
the Ministry of Health (MOH). Most of the incidents happened
due to poor ventilation design and lack of maintenance
activities. This guideline will serve as a reference for all
designers,
implementers/installers,
and
maintenance
personnel, to ensure that UPS systems are installed
appropriately and are well maintained. This guideline is also
intended to serve as a resource for any future upgrading
projects related to UPS systems.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
DEFINITION
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
7
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
8
2.0 DEFINITION 1
An Uninterruptible Power Supply (UPS) is necessary for
providing a no-break three-phase supply to specific
equipment during blackouts, covering the period from the loss
of normal supply to the start-up and subsequent electrical
power generation of the emergency generator. Without a
UPS, even very short power breaks may cause disruption in
hospital operations.
Any UPS in Healthcare Facilities shall include the following
components:
a)
b)
c)
d)
e)
f)
g)
Rectifier
Charger
Inverter
Control and instrumentation
Switch gears
Battery bank
Electronic and/or manual bypass switch
maintenance bypass switch (internal and external)
and
This excludes ICT and other equipment that have a built-in
UPS.
Note:
1. Refer to Healthcare Technical Memorandum 2011
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
LOCATION
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
9
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
10
3.0 LOCATION
In healthcare facilities, a UPS shall be installed to provide
uninterruptible power supply to all uninterruptible power/
lighting points and life supporting/monitoring equipment in
specific critical and emergency areas/departments at the
following locations1:
a)
b)
c)
d)
e)
f)
g)
h)
i)
Operation Theatre Suites
Invasive Cardio Laboratory (ICL)
Intensive Care Unit (ICU)
Special Care Nurseries (SCN)
Neonatal Intensive Care Unit (NICU)
Coronary Care Unit (CCU)
High Dependency Ward (HDW)
Emergency and Trauma (red zone)
Fluoroscopy Room
Note:
1. Refer to Healthcare Technical Memorandum 2011
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
UPS INSTALLATION
GENERAL
REQUIREMENTS
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
11
12
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
4.0 UPS INSTALLATION GENERAL REQUIREMENTS
4.1 The UPS shall be of sufficient capacity to handle the
present load and have a minimum of 20% spare
capacity for future extensions.
4.2 All UPS installations in new buildings shall avoid ANY
water/liquid/gases pathways, sources and outlets2 in the
ceiling above the battery bank and control system of the
UPS. It is an additional requirement that ceiling facilities
be waterproofed in existing UPS rooms.
4.3 All UPS installations in new buildings shall be designed
in two (2) connected compartments separated by a
two (2) hours fire rated brick wall partition and door or
something equivalent to a two (2) hours fire rated wall
and door. One compartment will contain the battery
bank and the other will house the control system. The
compartments must be well air-conditioned by an
independent 24-hour cooling system.
4.4 The battery capacity shall be at least one (1) hour1 full
load capacity with an electronic and/or manual bypass
switch and maintenance bypass switch (internal and
external). The UPS should be connected to the essential
services supply. The full load discharge capacity has to
be specified along with the battery calculation.
Note:
1. Refer to Healthcare Technical Memorandum 2011
2. This includes waste water pipes, chilled water pipes, hot water pipes, sanitary pipes, rain water down
pipes, etc.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
13
4.5 Batteries for the UPS system shall comply with the latest
standards set by the International Electrotechnical
Commission (IEC) and the Institute of Electrical and
Electronics Engineers (IEEE).
4.6 All cells in the same bank shall be of the same size and
type.
4.7 Batteries or chargers should not be located in areas of
vibration and restricted only to maintenance personnel1.
4.8 Any new UPS system installation must have a minimum
one (1) year warranty.
4.9 Any new UPS installation must be provided with
a minimum of eight (8) years spare parts availability.
A guarantee letter must be issued by the manufacturer
before installation.
4.10 The minimum design lifespan of batteries is ten (10)
years.
4.11 All battery bank compartments should display a clear
legible label or signage indicating the type of battery
electrolyte used. Explosion signage must be provided
due to the possibility of gas explosion arising from the
mishandling of acid and alkaline battery electrolytes.
Note:
1. Refer to Healthcare Technical Memorandum 2011
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
14
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
4.12 The required specifications for the UPS are as follows:
a) Output efficiency ≥ 95%
b) Power factor ≥ 0.85
4.13 The required environmental conditions for the UPS are
as follows:
a) Operating Temperature : 0°C to 40°C
b) Relative Humidity ≤ 95%
c) Room Temperature ≤ 25°C
4.14 The UPS room shall be installed with a suitable
Automatic Fire Protection System in both compartments.
A smoke detector, heat detector, and clean agent
suppression system type substances shall be used in
the above system. Other latest fire protection systems
will be approved on a case by case basis.
4.15 Upon completion of the UPS installation, all relevant
technical documents shall be properly handed over to
the respective healthcare facilities. Technical documents
shall include but not be limited to the following:
a) A Manufacturer’s Operation and Maintenance Manual
complete with Manufacturer’s Maintenance Checklists
b) Warranty / Guarantee Certificate
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
15
c) As-Built Drawings - hardcopy and softcopy
d) A Testing & Commissioning Report, including a
factory acceptance test and safety test
4.16 The implementer or installer shall provide technical
training to the respective end user and technical
personnel upon completion of the installation.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
16
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
MAINTENANCE
OF THE UPS
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
17
5.0 MAINTENANCE OF THE UPS
5.1 The implementer or installer shall perform Planned
Preventive Maintenance (PPM) and rectify any failures
or defects during the warranty/defect liability period.
5.2 All maintenance activity
competent personnel.
shall
be
performed
by
5.3 Routine Inspection (RI) shall be performed daily. RI
activity shall consist of:
a) Recording room temperature
b) Recording operating temperature
c) Recording any warning alarm
d) Visual inspection
e) Checking battery condition
f ) Checking the functionality of support systems in the
UPS room (e.g., ventilation, fire protection system,
etc.)
g) Housekeeping of UPS room
5.4 PPM shall be performed based on the manufacturer’s
recommendation or according to the MOH’s Hospital
Engineering Plan Preventive Maintenance (HEPPM).
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
18
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
5.5 The PPM’s activity details (semi-annually and annually)
shall be referred to HEPPM checklists.
5.6 Immediate action shall be taken if any abnormal
condition is detected (especially in the UPS battery) to
prevent any mishaps from happening. All RI and PPM
activities shall be recorded. A log book/log sheet must
be made available and updated at all times.
5.7 All spare parts shall be new and genuine, sourced from
equipment manufacturers or Original Equipment
Manufacturers (OEM) equivalents approved by the
government.
5.8 All workmanship shall be in accordance to approved
codes and good engineering practices.
5.9 Replacement of the batteries shall be carried out if:
a) Efficiency drops to a minimum level of 10% ±5
b) Battery fails or is in poor condition
c) Battery exceeds life span based on requirements set
by manufacturer
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
REFERENCES
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
19
20
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
6.0 REFERENCES
6.1 Health Technical Memorandum 2011 - Emergency
Electrical Services.
6.2 MS IEC 62040 - Uninterruptible Power Supply Unit
(UPS).
6.3 MOH HEPPM Guideline - Task No: E31316 / E31315.
6.4 JKR Specification - Contract Document National Cancer
Institute (NCI)/IT room specification.
6.5 IEEE 450 (Battery - Lead Acid)
6.6 IEEE 1106 (Battery - Nickel Cadmium)
6.7 Industry Operation and Maintenance Manual:
a) Schneider Electric Sdn. Bhd.
b) Emerson Sdn. Bhd.
c) Socomec UPS (M) Sdn. Bhd.
d) Power Solution Sdn. Bhd.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
21
ACKNOWLEDGEMENTS
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
22
ACKNOWLEDGEMENTS
The working group on General Requirements For
Installation And Maintenance Of A Centralized Three
Phase Uninterruptible Power Supply (UPS) In Healthcare
Facilities consists of the following representatives:
No.
Name
Designation/Department
ENGINEERING SERVICES DIVISION, MINISTRY OF HEALTH
1
Hj Md. Jalal b. Bongkik
Director
2
Hj Tauran Zaidi b. Ahmad
Zaidi
Deputy Director
Hospital Operations Section
3
Khairul Azmy b. Kamaluddin
Deputy Director
Clinic Operations Section
4
Hj Yahaya b. Saad
Deputy Director
Project Implementation Section
5
Mohd Azizi b. Ibrahim
Senior Principle Assistant
Director
6
Azrul Aminurrashid b. Roslan Principle Assistant Director
Hospital Operations Section
7
Mohd Affendi b. Amran
Principle Assistant Director
Project Implementation Section
8
Ir. Noor Muhammad b. Abd
Rahman
Senior Assistant Director
Hospital Operations Section
9
Ir. Mohd Hisam b. Sa’at
Senior Assistant Director
Hospital Operations Section
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
No.
Name
23
Designation/Department
10 Shairam b. Salleh
Senior Assistant Director
Hospital Operations Section
11 Sharminie bt. Zainul Abidin
Senior Assistant Director
Clinic Operations Section
12 Rijal Mahadi b. Rahindra
Senior Assistant Director
Project Implementation Section
13 Chwa Chee Woon
Senior Assistant Director
Project Implementation Section
14 Dazihayu bt. Hamdan
Assistant Director
Hospital Operations Section
15 Nur Khalida Salmi bt. Mohd
Nawar
Assistant Director
Hospital Operations Section
16 Yom Zuraima bt. Mohd
Zaizizi
Assistant Director
Hospital Operations Section
17 Nur Adilah bt. Razali
Assistant Director
Hospital Operations Section
18 Muhammad Taheri b. Abdul
Rashid
Assistant Director
Hospital Operations Section
19 Syazwani bt. Yahaya
Assistant Director
Hospital Operations Section
20 Norsuriana Fatiha bt. Hussin
Assistant Director
Selangor State Health
21 Izyan Nadirah bt. Sabri
Assistant Director
Kuala Lumpur Hospital
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
24
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
No.
Name
Designation/Department
PUBLIC WORKS DEPARTMENT
1
Muhammad Shukri b. Khasim Senior Principle Assistant
Director
2
Rafizan b. Mohamad Rasul
Senior Assistant Director
Health Works Branch
CONCESSION COMPANY
1
Jufri b. Abdul Jalil
Faber Medi-Serve Sdn. Bhd.
2
Ir. Abd Razak b. Mohamad
Faber Medi-Serve Sdn. Bhd.
3
Khairul Nizam b. Mohd Yusof Radicare Sdn. Bhd.
4
Mohd Zainuri b. Remali
Radicare Sdn. Bhd.
5
Zairi b. Othman
Medivest Sdn. Bhd.
6
Mohd Saifful Izzuan b. Ishak
Medivest Sdn. Bhd.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES
No.
Name
25
Designation/Department
MANUFACTURER/SUPPLIER
1
Brandon Ng
Schneider Electric Sdn. Bhd.
2
Andy Chang Liang Hong
Emerson Network Power
Sdn. Bhd.
3
Eric Cheah
Emerson Network Power
Sdn. Bhd.
4
Fong Keng Loong
Power Solution Sdn. Bhd.
5
Mohd Hasyidan b. Mohamed Power Solution Sdn. Bhd.
6
Jeffry@Tan Hin Guey
Power Solution Sdn. Bhd.
7
Ken Lee
Socomec UPS (M) Sdn. Bhd.
8
Alex Ang Eng Hua
FPS-ENP Sdn. Bhd.
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
26
GENERAL REQUIREMENTS FOR INSTALLATION AND MAINTENANCE
OF A CENTRALIZED THREE PHASE UNINTERRUPTIBLE POWER SUPPLY (UPS) IN HEALTHCARE FACILITIES