BOA-Systronic 2 MB
Transcription
BOA-Systronic 2 MB
KSB Know-how, Volume 2 B OA- Sy s t ro n i c Contents Intelligent pump and valve management saves energy . . . . . . . . . . . . . 2 1 Heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 System concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4 Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5 Volume flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 6 Circulator pump heads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 7 Hydraulic balancing of branch circuits . . . . . . . . . . . . . . . . . . 12 8 Differential pressure control elements . . . . . . . . . . . . . . . . . . . 14 9 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 10 Practical testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 10.1 Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 10.2 Circulator selection for BOA-Systronic . . . . . . . . . . . . . . . . . . 19 10.3 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 10.4 External temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 10.5 Volume flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10.6 Differential pressures of the pumps . . . . . . . . . . . . . . . . . . . . . 22 10.7 Electrical pump power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 11 Payback period for BOA-Systronic . . . . . . . . . . . . . . . . . . . . . 24 11.1 Control valve investment and energy savings . . . . . . . . . . . . . . 24 11.2 Investment costs for heating circuit with Riotec pump . . . . . . 25 11.3 Investment costs for heating circuit with Rio-Eco pump . . . . . 26 11.4 Total savings comparison Riotec/Rio-Eco . . . . . . . . . . . . . . . . 26 12 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 13 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 List of figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 List of tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 1 060206_knowhow05_e_IS 1 06.02.2006, 12:49:41 Uhr Intelligent pump and valve management saves energy The new BOA - Systronic system solution improves the supply temperature control of heating circuits. It opens up a previously unused potential for saving electrical energy used by the circulator pump. 2 060206_knowhow05_e_IS 2 06.02.2006, 12:49:42 Uhr 1 Heating circuit 1 Heating circuit • Mixing or injection-type systems produce a constant volume flow rate through the Every heating circuit consists of consumer installations1. As a several control components result, part-load conditions – such as the circulator pump and which account for more than the control valve, which are 95% of the operating period – connected by pipes. The circu- result in the circulator pump lator pump conveys the heating handling predominantly cold water from the heat generator return water most of the time. (boiler) to the consumer instal- • In a mixing or injection-type lations, and the control valve system, the discharge head of adjusts the volume flow rate the variable-speed circulator pumped through the consumer pump remains constant, irre- installations. Conventional spective of the actual load heating set-ups can be charac- conditions, i.e. irrespective of terized as follows: external temperature. Only external heat gains will result THE CONTROL COMPO- in energy savings, depending NENTS IN CONVENTION- on the set pump characteristic AL HEATING SYSTEMS ARE curve (∆p = constant or ∆p = NOT COORDINATED variable). • If several heating circuits of • The circulator pump and a mixing or injection-type the control valve fitted in con- system branch off a main feed ventional, mixing or injec- circuit, they must be balanced tion-type systems operate in- manually. dependently, without coordination between the two components. There is no system knowledge about the hydraulic conditions in the heating circuit, so that some of the hydraulic energy supplied by the circulator pump may actually be destroyed by valves and differential pressure control elements elsewhere in the heating circuit. 1 Constant volume fl ow rate through consumer installations: results from the hydraulic confi guration of the main feed circuit (e.g. 3-way mixing valve). Whether the system is operating under nominal load or part-load conditions, the circulator pump will always deliver the nominal volume fl ow rate calculated for the design point. Only when external heat is acting on the consumer installations will the level of this volume fl ow rate be adjusted by the control function of the thermostats. 3 060206_knowhow05_e_IS 3 06.02.2006, 12:49:42 Uhr 2 System concept 2 System concept An analysis of this situation re- The supply temperature is in- main feed manifold is now sulted in the BOA-Systronic creased by the higher-level con- automatically performed via the system concept, which has the troller. This results in hydraulic circulator pump, which reduces clearly defined benefit of reduc- savings regarding both volume commissioning costs for the ing the running costs of the flow rate ∆Q and discharge heating circuit. When the heat- heating circuit. head ∆H, whose product is pro- ing circuit of a conventional portional to the corresponding mixing or injection-type system electrical power savings for the is commissioned, the tempera- SAVINGS POTENTIAL BY SYSTEM CONCEPT circulator pump2 . ture difference between supply and return (temperature differ- BOA-Systronic coordinates the A positive side effect is that ential) is set for the design point operation of circulator pump static hydraulic balancing at the using the balancing valve, usu- and control valve. Depending on the control signal issued by the higher-level heating controller the two BOA-CVE SuperCompact control valves adjust the resulting volume flow rate pumped through the consumer installations. At the same time, the appropriate discharge head Higher-level heating controller setpoint is transmitted to the variable-speed drive of the circulator pump. BOA-Systronic transforms the conventional, constant-flow mixing or injection-type system into a variable-flow system, and adjusts the discharge head of the circulator pump to the reduced volume flow rates via the system control curve. The radiator diagram illustrates the physical fact that – at identical heat output – the volume flow rates provided to the consumer installations can be reduced if the supply temperature is increased at the same time. 2 Fig. 01 Hydraulics schematics of BOA-Systronic t2 Electrical power input of circulator pump: P = constant · ∫ Q(t) · H(t)dt. electr. t1 The constant describes the efficiency of circulator pump and frequency inverter as well as water density and acceleration due to gravity. 4 060206_knowhow05_e_IS 4 06.02.2006, 12:49:43 Uhr 2 System concept ally by throttling this valve. ic balancing of branch circuits, The pressure drop across the they can even be replaced by valve may amount to several more cost-effective balancing tenths of bar. With BOA-Sys- valves. Variable volume flow tronic, this step is dispensed rate control by BOA-Systronic with. has no influence on the hydraul- As BOA-Systronic produces ic balancing of the branch cir- only the discharge head actually cuits, which is performed for required to overcome system the design point. resistance, flow noises are prevented, even with external heat input, and expensive differential pressure control elements are not required for balancing the heating circuits. For hydraulKNOWLEDGE ABOUT PIPING CHARACTERISTIC OF HEATING CIRCUIT Fig. 02 Comparison of systems Conclusion The savings realised by BOA - Systronic result from knowledge about the hydraulic conditions in the heating circuit. They are completely independent from differential pressure control of the circulator pump. With BOA - Systronic , differential pressure control of the circulator pump is effected as before. 5 060206_knowhow05_e_IS 5 06.02.2006, 12:49:44 Uhr 3 Components 3 Components The transformation into a sys- ing on the actual load (external and thus the hydraulic resist- tem with variable volume flow temperature). ance of the heating circuit. The presupposes that the partial The control unit is mounted on measuring valve remains fully volume flows are hydraulically the main control valve at the open both during commission- decoupled and that information factory. The BOA-Control ing and over the entire operat- about the flow rates required in IMS 4 valve is used here to ing range and – due to its very the heating circuit is available. measure the volume flow rate at low ζ-coefficient – acts just like For this reason, BOA-Systronic the main feed manifold during a piece of pipe. The measuring comprises three valves. The two commissioning. This measuring computer is not included in the BOA-CVE SuperCompact con- signal is used to determine the system scope of supply. trol valves are used for adjust- discharge head of the circulator ing volume flow through the pump for the design point as consumer installations depend- well as the system control curve Fig. 03 BOA-Systronic components 3 4 5 BOA- CVE SuperCompact: Automated shut-off and control valve for HVAC applications with smart electric actuator. The valve is produced in nominal sizes from DN20 to DN150 and nominal pressure class PN6/10/16. Thanks to its compact design, it is the smallest and lightest valve of this pressure class manufactured in series production today, enabling the space-saving design of air-conditioning and heating centrals. Due to its low weight, the valve is easy to install and handle. The self-calibration feature of the actuator is another benefi t, which does away with the adjustment of limit switches. BOA- Control IMS: The valve measures volume fl ow rates independently from valve travel positions and minimum differential pressures. Unlike on conventional valve models, the measurement accuracy is constant across the entire valve travel. The measuring signal is read and processed by a measuring computer. Valves of this kind are often insulated, and any identifi cation on their bodies may be diffi cult to read. After start-up, the computer display therefore fi rst shows the nominal diameter of the connected valve. The operator can then choose via two keys whether the current fl ow rate is to be indicated [in m 3 /h] or the temperature of the fl uid handled [in C°]. Volume fl ow rates can be checked within a matter of seconds in this way. BOA- Control IMS, which has a linear characteristic, can also be used as shut-off valve. Thanks to a travel stop with a protective cap, the valve can be set exactly to its original position once the shut-off process has been completed. ζ-coeffi cient: describes the resistance a valve offers to the fl uid passing through it. The ζ-coeffi cient depends on the valve type and design. 6 060206_knowhow05_e_IS 6 06.02.2006, 12:49:46 Uhr 4 Control 4 Control BOA-Systronic is a control sys- supply temperature measured, tem which is installed down- the higher-level controller gen- stream of the heating system’s erates the control error signal, control unit. It does not replace which is the input of the (PI or the higher-level controller. PID) control algorithm. This control algorithm generates a HIGHER-LEVEL CONTROL- signal, which – in conventional LER IS RETAINED mixing / injection-type systems – is then transmitted to the control Supply temperature control valve. remains the task of the higher- This output control signal from level controller. Input signals the higher-level controller is the for this controller are, among input for BOA-Systronic, i.e. it others, the external tempera- is transmitted to the Systrobox ture measured and the supply control unit. With the help of temperature measured in the the system control curves deter- heating circuit. With the help of mined during commissioning, the heating curve stored in the Systrobox translates the control higher-level control unit, the signal into two separate control setpoint for the supply tempera- signals for the two BOA-CVE ture of the heating circuit is SuperCompact control valves generated on the basis of the and into a discharge head set- external temperature measured. point for the circulator pump. Based on this setpoint and the 7 060206_knowhow05_e_IS 7 06.02.2006, 12:49:51 Uhr 5 Volume flow rates 5 Volume flow rates type systems. As a result, pre- water, whereas the control valve dominantly cold return water in the mixing line adjusts the is pumped through the heating volume of cold return water to Thermal output of the heating circuit under part-load be mixed in. The additional op- circuit is calculated for the conditions. timizing effect of external heat design point as the product of The volume flow rate through load compensation by the ther- volume flow rate Q and temper- the heating circuit is only re- mostatic valves remains un- ature differential ∆T. duced by the regulating func- affected. tion of the thermostatic valves The radiator diagram illustrates (external heat load compensa- that volume flow rate can be re- tion). duced while thermal output at Pth = 1.163 · Q · ∆T Conventional systems the consumer installations stays BOA-Systronic the same, if the supply tempera- figuration, conventional mixing The innovative control concept ture is increased accordingly. of BOA-Systronic regulates Two methods can be used, provide the consumer installa- thermal output by variation of which can be realized by mak- tions only with a constant vol- the temperature differential and ing use of a standard function ume flow rate, irrespective of the volume flow rate, consider- offered by the heating control- the heating controller’s signal. ably reducing the water volume ler. The volume flow in the supply to be pumped through the heat- line is coupled with the volume ing circuit. This is possible flow of the cold return water because the two BOA-CVE Parallel shift of heating curve pumped through the mixing SuperCompact control valves The controller’s heating curve is line (Fig. 04). decouple the volume of heating shifted parallel by a fixed water coming from the supply amount towards higher supply line from the volume of cold re- temperatures. The controller turn water pumped through the adds the fixed amount ∆T to the So thermal output of the heating mixing line. supply temperature setpoint circuit can only be regulated via The main control valve installed (parallel shift of the heating the temperature differential in in the supply or return line regu- curve). Due to the increased conventional mixing / injection- lates the volume of heating temperature differential, the or injection-type systems 6 can Qtotal =Q1supply+Q2mixing Q 1 supply Q total (hot) Volume flow rate Q [%] Owing to their hydraulic con- Q total 100 Q 2 mixing 80 60 40 20 Q 1 supply 0 Q 2 mixing (cold) 0 20 40 60 80 100 Controller signal [%] Fig. 04 Volume flow rates of 3-way valve 6 3-way configuration: In a 3-way mixing valve, the fl uids to be mixed enter the valve via two input ports and the sum of their fl ow exits through a single output port. The ratio between the fl ow rates through both inlet ports is determined by the stem position. The sum of the throttling cross-sections on both inlet ports is constant over the entire valve travel. The valve therefore provides a constant volume fl ow at its outlet port, independent of stem position. 8 060206_knowhow05_e_IS 8 06.02.2006, 12:49:51 Uhr 5 Volume flow rates nominal volume flow rate is In principle, this new design design point of the circulator reduced by 25% in all cases, point can also be achieved with pump remain unchanged. In resulting in a new design point a conventional hydraulic con- this case, the investment costs for the circulator pump (Fig. 05) figuration. However, BOA- for the circulator pump and the Systronic offers a number of other valves cannot be reduced. INCREASED SUPPLY TEM- benefits. PERATURE BY PARALLEL • The consultant can size the SHIFT OR SLOPE MODIFI- consumer installations of the CATION OF HEATING heating circuit as usual CURVE • The consultant can use the benefits offered by BOA- Thanks to the new design Systronic without changing point, investment costs for the his planning circulator pump and the valves • The consultant saves in the heating circuit can be planning work and thus time reduced considerably. and costs • Normally, a circulator rating can be selected Slope modification of heating curve Benefit: Substantially reduced The controller’ s heating curve investment costs for the circu- is shifted towards higher supply lator pump temperatures only if the system pump with a lower output • The nominal diameter of is running under part-load conditions. Depending on the value be chosen one nominal diam- of the control signal, the control- eter smaller. ler internally adds an amount Benefit: Reduced investment ∆T to the supply temperature costs for piping, shut-off setpoint (slope modification of valves and strainers, including heating curve). The nominal insulation. volume flow rate and thus the Q 1 supply (hot) Q total + Q 2 mixing (cold) Volume flow rate Q [%] the heating circuit can usually 100 80 Q total 60 40 20 Q 2 mixing Q 1 supply 0 0 20 40 60 80 100 Controller signal [%] Fig. 05 Reduced volume flow rates of BOA-Systronic 9 060206_knowhow05_e_IS 9 06.02.2006, 12:49:55 Uhr 6 Circulator pump heads 6 Circulator pump heads Control IMS valve measures the cuit, the pressure losses in the volume flow rate in the heating consumer installations, balanc- circuit and thus determines the ing valves, differential pressure Owing to the hydraulic config- required nominal discharge head control elements, strainers as uration of conventional mixing of the circulator at the design well as thermostatic and shut- or injection-type systems, the point. The values obtained are off valves. circulator pump head cannot be then used to determine the The volume flow rate and dis- matched to the system control system constant of the heating charge head are shown in nor- curve. The circulator pump can circuit. As a result, the hydraul- malized representation here. only react to reduced volume ic resistance of the heating The circulator pump of a mix- flow rates resulting from the circuit is known, and the control ing or injection-type system can control function of the thermo- unit knows the circulator head only respond to reduced volume static valves at the consumer in- required for the individual load flow rates (external heat gain) stallations. Depending on the conditions. with a constant discharge head, pump curve selected, the dis- thus saving a certain amount of charge head either remains The H/Q diagram on page 11 constant (∆p = constant) or is shows an example of the possi- reduced accordingly (∆p = ble discharge heads of a differ- NEW DESIGN POINT FOR variable). ential pressure controlled THE PUMP energy. pump. The diagram shows the BOA-SYSTRONIC CON- H/Q data of a pump controlled With BOA-Systronic, parallel TROLS THE PUMP AS A independently of throughflow shift of the heating curve results FUNCTION OF THE SYSTEM (∆p = constant) and offers a in the new nominal volume CURVE OF THE HEATING comparison between a conven- flow rate CIRCUIT tional system and a system equipped with BOA-Systronic. Q new = 0.75 · Q old BOA-Systronic, by means of the two control valves, adjusts the The design point is represented and, by application of the affin- volume flow rate as a function by the intersection of the system ity law, yields the associated of external temperature and curve of the heating circuit with discharge head of the circulator measures the system curve of the characteristic curve of the pump: the heating circuit during com- circulator pump. (see equation below) missioning. As a result, the circulator’s discharge head can be matched to the volume flow ( H new = H old · Q new Q old 2 ) ( = 100%· 75% 100% 2 ) ·H old = 0.56 · H old rate to be pumped. This is done by means of the system control The system curve describes the The valve authority of the main curve (Fig. 6). The system resistance the volume flow has control valve must then be add- control curve is automatically to overcome, and corresponds ed to this value. It describes the determined by measuring the to the discharge head required pressure drop at the control volume flow rate during of the circulator pump. It de- valve, in relation to the differ- commissioning; it is limited by pends on the length and nom- ential pressure to be produced the minimum discharge head of inal diameter of the supply and by the pump (overall pressure the circulator pump. The BOA- return lines in the heating cir- drop in the system). With BOA- 10 060206_knowhow05_e_IS 10 06.02.2006, 12:49:56 Uhr 6 Circulator pump heads Systronic, valve authority is the BOA-Systronic controlled pump curve set, the discharge constant over the entire operat- circulator pump moves along head either remains constant ing range. This correlation is the system control curve. As (∆p=constant) or decreases with reflected in the system control external temperature rises, the decreasing volume flow rate curve and explains why the sys- operating point moves towards (∆p=variable). All the familiar tem control curve runs parallel lower volume flow rates and features of the variable-speed to the system curve, at a slightly lower discharge heads. pump and the thermostatic higher level (Fig. 6) valves are retained. ALL FEATURES OF THE In our example, a new design VARIABLE SPEED PUMP point is established for the cir- ARE RETAINED culator pump: the nominal volume flow rate is reduced by The diagram also illustrates the 25%, and the nominal dis- effect the control function of charge head of the circulator the thermostatic valves has on pump is reduced accordingly. various operating points (exter- As a result, a circulator pump nal heat load). Under the influ- with a lower performance rat- ence of external heat load, the ing can be selected. operating point also moves along the characteristic curve of Depending on the external tem- the differential pressure con- perature, the operating point of trolled pump. Depending on the P el 1 Discharge head H [%] P el2 = constant Q1 H1 constant Q2 H2 = Q1 H1 Q2 H2 180 Chara o f f ixedc t e r i s t i c c u r v e speed p ump 160 Operating point, conventional with external heat load P el 11 = 84% Design point, conventional without external heat load Pel 1 = 100% 140 120 External heat effect Characteristic curve of variable speed pump ∆p = constant 100 Design point BOA-Systronic with external heat load P el 21 = 35% 80 External heat effect Characteristic curve of variable speed pump ∆p = constant 60 Operating point BOA-Systronic part-load, with external heat load P el 31 = 11% 40 External heat effect Characteristic curve of variable speed pump 20 System control curve Syst urv em c BO A st -Sy e ron Design point BOA-Systronic without external heat load P el 2 = 45% ic Operating point BOA-Systronic part-load, without external heat load P el 3 = 16% 0 0 10 20 30 40 50 60 70 80 90 100 110 120 Volume flow rate Q [%] Fig. 06 Circulator pump heads (example) 11 060206_knowhow05_e_IS 11 06.02.2006, 12:49:57 Uhr 7 Hydraulic balancing of branch circuits 7 Hydraulic balancing of branch circuits BOA-Systronic operates the heating circuit with variable volume flow rates. The question therefore arises whether the branch circuits are hydraulically balanced for these variable operating points. The branch circuits are hydraulically balanced for the design point (nominal load). This ensures adequate heat supply to the consumer installations in the individual branch circuits. In the following, the nominal load case is indexed N, whereas the Fig. 07 Heating circuit with branch circuits part-load case is indexed T. At the design point (nominal mains unchanged. The pressure The following is to show that load), the differential pressure drop at the valve then only de- variable volume flow control by at the balancing valve of the pends on the volume flow rate BOA-Systronic has no influence branch circuit drops as follows: (Q). on branch circuit balancing. Differential pressure at The volume flow rates in branch by means of balancing valves nominal load: QN 1 1 ∆ pN = · ρ · ζ · w 2 = · ρ · ζ · 2 2 A BV1, BV2 and BV3. What is Equation 1 circuits 1, 2 and 3 are adjusted 2 ( ) of interest is the ratio of the pressure drops at the balancing where ρ is the water density, ζ is The opening cross-section (A) valves at nominal load the valve’s zeta coefficient, w is and the zeta coefficient (ζ) of the flow velocity of the water, A the valve remain unchanged. (e.g. ∆ pN2 ∆ pN1 ) and part load (e.g. ∆ pT2 ∆ pT1 is the flow cross-section at the throttling point, and Q N is the ). volume flow rate at design point. 1 1 2 ·ρ·ζ· = constant = c 2 A () Equation 2 Hydraulic balancing of the Differential pressure at the bal- branch circuit is performed for ancing valve therefore only the design point (nominal load). depends on a factor (c) which After that, the throttling pos- describes the valve and the vol- ition of the balancing valve re- ume flow rate (Q): 12 060206_knowhow05_e_IS 12 06.02.2006, 12:49:57 Uhr 7 Hydraulic balancing of branch circuits Differential pressure at nominal load: ∆ pN = c · Q 2 N Differential pressure BV1 Equation 3 Equation 6 ∆ pT1 = F2 ·∆ p N1 Under part-load conditions, the differential pressure at the bal- Differential pressure BV2 ancing valve (BV) is reduced as ∆ pT2 = F2 ·∆ p N2 follows: Equation 7 Differential pressure at parl load: ∆ pT = c ·(F·Q N ) 2 Equation 4 where factor F describes the Differential pressure BV3 ∆ pT3 = F2 ·∆ p N3 Equation 8 part-load level (0-100)%. Inserting equation 3 in equation Therefore, the ratios of these 4 yields differential pressures are as follows: ∆ pT = F2 ·∆ p N Equation 5 resulting in the following differ- ∆ pT2 ∆ pT1 = ∆ pN2 ∆ pN1 Equation 9 ential pressures at nominal and part-load for branch circuits 1, 2 and 3: Conclusion The same law governing differential pressures in the branch circuits can be established for part load conditions as for nominal load conditions. It is therefore ensured that the branch circuits are actually supplied with the necessary volume flow rate for the thermal output required. 13 060206_knowhow05_e_IS 13 06.02.2006, 12:49:59 Uhr 8 Differential pressure control elements 8 Differential pressure control elements circulator pump is immediately higher excess discharge head at reduced by the differential pres- the thermostatic valve (∆p 2 ), as sure control valve in many cases! does the fixed speed pump By way of example, the H/Q (∆p1). If external heat is acting on a diagram in fig. 08 compares the room – sunlight, for instance – influence of external heat gain the thermostatic valves will re- on the operating behaviour of a duce the volume flows passing fixed speed circulator pump, a through the radiators in this differential pressure controlled room. If volume flow rates are circulator pump of a mixing or reduced, the circulator pump of injection-type system, and a a conventional heating system differential pressure controlled will either be operated with a pump controlled by BOA-Sys- constant or variable discharge tronic. The diagram shows that head, depending on the set the BOA-Systronic controlled pump curve. The reduced vol- pump generates only little ex- ume flow rate will result in a cess differential pressure, which reduced pressure drop in the drops at the thermostatic valve. piping. The excess differential pressure produced by the circu- NO DIFFERENTIAL lator pump can only drop at the PRESSURE CONTROL thermostatic valve, which caus- ELEMENTS REQUIRED es considerable flow noise or whistling. Differential pressure This differential pressure results control elements are often used from the hydraulic resistance of to prevent this. Their function the heating circuit and the dis- limits the increase in differen- charge head of the circulator tial pressure across the thermo- pump controlled by BOA- static valve, thus preventing Systronic. The differential flow noise. In conventional sys- pressure controlled pump of a tems, therefore, part of the dis- mixing or injection-type system, charge head provided by the by contrast, produces a much Conclusion BOA -Systronic provides the circulator pump with the discharge head required for the actual load conditions. No excess discharge heads are produced under part load conditions, nor flow noises at the consumers. Expensive differential pressure control elements for balancing the heating circuits can be dispensed with. For hydraulic balancing of branch circuits, they can even be replaced by lower priced balancing valves. 14 060206_knowhow05_e_IS 14 06.02.2006, 12:49:59 Uhr 9 Commissioning 9 Commissioning this procedure has been com- termines the circulator’s discharge pleted, the system knows the head required for the design circulator’s discharge head for If parallel shift of the heating point. To do so, the circulator the design point and the system curve is planned, BOA-Systronic pump is started up with its constant of the heating circuit, will always reduce the volume minimum discharge head. A and thus its system curve. flow rate for the design point by corresponding volume flow rate Therefore, the correlation be- 25 %, based on the volume flow is produced in the heating cir- tween discharge head and vol- rate the system designer has cal- cuit, which is measured by the ume flow rate for the heating culated for a conventional mixing BOA-Control IMS valve at the circuit is known. or injection-type system. main feed manifold. The BOA-Systronic has to be config- BOATRONIC M- 420 measur- BOA-SYSTRONIC AUTO- ured prior to commissioning. ing computer converts this MATICALLY DETERMINES This is done by entering the value measured value into an analog THE OPTIMUM PUMP HEAD of the volume flow rate deter- (4-20)mA current signal and mined for a conventional mixing transmits it to the Systrobox With the data stored for the or injection-type system into the control unit, where it is com- volume flow rate at part load commissioning software, together pared against the value for the conditions, BOA-Systronic then with the nominal system diam- (new) nominal volume flow generates the system control eter of BOA-Systronic (param- rate. The circulator’s discharge curve as well as the two valve eterization). The nominal diam- head is increased step by step, control curves. eter of the BOA-Control IMS until the difference between set- measurement valve corresponds point and measured value falls to this nominal system diameter. below a certain limit. When Discharge head H [%] BOA-Systronic automatically de- 180 Operating point, conventional, variable speed pump with external heat load Operating point, conventional, fixed speed pump with external heat load 160 H1 140 External heat effect Design point, conventional without external heat load 120 100 H2 ∆p1 80 ∆p2 60 Operating point BOA-Systronic variable speed pump with external heat load External heat effect 40 External heat effect Operating point BOA-Systronic variable speed pump without external heat load H3 ∆p 3 BO y A-S str oni Sy s tem cu rve c Hydraulic resistance of heating circuit 20 0 0 10 20 30 40 Q part-load 60 70 Q NS 80 90 QN 110 120 Volume flow rate Q [%] Fig. 08 Excess circulator pump heads (example) Q Q N N Sys Q T Design point of heating circuit with 3-way valve ∆p1 Differential pressure at thermostatic valve (fi xed speed pump) Design point of heating circuit with BOA-Systronic ∆p2 Differential pressure at thermostatic valve Part load condition (example) 060206_knowhow05_e_IS 15 (variable speed pump ∆p=const.) ∆p3 Differential pressure at thermostatic valve (BOA-Systronic) 15 06.02.2006, 12:49:59 Uhr 10 Practical testing 10 Practical testing 10.1 Plant BOA-Systronic has been in use in the office building of DeTeImmobilien in Heidelberg, Germany, since 2001. The heating water is produced in a twoboiler system with a thermal output of approx. 2 MW. Each boiler is equipped with a 2-stage burner. The main feed manifold is connected directly Fig. 09 Two-boiler system to the boilers (without hydraulic separator) and feeds 4 heat- sections, any disturbances in CONTROLLER TRANSMITS ing circuits plus several other room temperature (external CONTROL SIGNAL TO BOA- hot water circuits. Four heating heat gain) are re-adjusted by SYSTRONIC controllers control supply tem- means of the radiators’ thermo- perature in the four building static valves. Both circulator The main control valve is sections. The controllers are pumps are differential pressure supplied in nominal system fitted in a separate control controlled (∆p = constant). diameter DN50 (Fig. 15). Fitted cabinet in the plant room. Table 01 demonstrates the with an EA-C40 actuator, it is benefits of BOA-Systronic by installed in the supply line of the FOUR HEATING CIRCUITS comparing the performance heating circuit. The designation HEAT THE BUILDING data of the two heating circuits. EA-C40 means that this actuator has an actuation force of BOA-Systronic supplies heat to the West wing of the building. The East wing is equipped with a conventional mixing system. Both building sections require the same heat output. The “Stat. Heizung West” heating controller transmits its control signal (for the control valve) to the control unit of BOA-Systronic, where it is converted into the load-dependent discharge head setpoint for the circulator pump and two separate control signals for the two control valves. In both building Fig. 10 Return manifold 16 060206_knowhow05_e_IS 16 06.02.2006, 12:50:00 Uhr 10 Practical testing 4,000 N. The photo shows the al-position feedback (2-10)VDC. terminal box for cable connec- When combined with BOA-Sys- tion and the black handwheel tronic, it is configured with a for emergency operation in the linear valve characteristic and event of a power failure. The fed by an analog (2-10) VDC smart actuator makes it pos- voltage signal. sible to select either a linear or an equal-percentage valve EA-C40 FOR NOMINAL characteristic. Configuration is SYSTEM DIAMETERS FROM performed exclusively by means DN 65 of the parameterization software. The mixing valve is always selected two nominal diameters smaller than the nominal system diameter and replaces the swing check valve in the mixing Fig. 11 Control cabinet Parameter line (Fig. 16). East wing (3-way configuration) West wing (BOA-Systronic) Unit 300.00 300.00 kW Temperature differential 20.00 27.00 K Volume flow rate (max.) 13.00 9.75 m³/h 8.00 4.50 m Circulator pump Riotec 65 -100 Riotec 50 -100 Differential pressure control ∆ p = constant ∆ p = constant DN65 DN50 No +3.5 Thermal output Discharge head (max.) Nom. diameter of main heating circuit Parallel shift of heating curve K Table 01: Performance data of main feed circuits 2 ACTUATOR TYPES FOR DIFFERENT NOMINAL SYSTEM DIAMETERS The actuator can either be supplied with 24 VAC/DC or 230 VAC/DC. As standard, it is capable of processing 230/24 VAC 3-point control signals as well as analog (0/4-20) mA current or (0/2-10) VDC voltage Fig. 12 Heating controllers for Fig. 13 Main feed manifold, signals and features active actu- West and East wings West and East wings 17 060206_knowhow05_e_IS 17 06.02.2006, 12:50:09 Uhr 10 Practical testing In the event of a power failure, dressed by an analog voltage the valve can be actuated by signal (2-10) VDC. means of an Allen key. The Systrobox is the “heart” of EA-B12 FOR NOMINAL BOA-Systronic. The control SYSTEM DIAMETERS UP TO unit stores the two valve control DN50 curves for the main control valve and the mixing valve, as For applications other than well as the system control curve BOA-Systronic, this actuator for the pump. also offers the option of setting a linear or equal-percentage SYSTROBOX IS THE valve curve. “HEART” OF BOA- A five-core cable supplies the SYSTRONIC. IT RECEIVES actuator with supply and con- AND TRANSMITS ALL trol voltage. As the terminals SIGNALS. Fig. 14 Main feed circuit with are located inside the actuator, BOA-Systronic the cover must be removed prior The control unit is powered by to installation. Operating on a 24 VAC. It contains the inter- It adjusts the volume flow rate 24 VAC/DC voltage supply, face for powering the BOA- in the mixing line in accordance the actuator requires an ana- TRONIC measuring computer with the valve control curve log (0/2-10)V control signal and for receiving and process- stored in the Systrobox. In this and provides (2-10)VDC active ing its measuring signal. As in- case, it is of nominal size DN32 actual-position feedback. When terface with the (higher-level) and therefore equipped with ac- combined with BOA-Systronic, controller, it receives the con- tuator type EA-B12, which has it is configured with a linear troller’s control signal and an actuating force of 1,200 N. valve characteristic and ad- transmits the three control sig- Fig. 15 Main control valve Fig. 16 Mixing valve BOA-Systronic BOA-Systronic 18 060206_knowhow05_e_IS 18 06.02.2006, 12:50:14 Uhr 10 Practical testing nals simultaneously to the pump and the control valves. 10.2 Circulator selection for BOA -Systronic The control valves receive a k heating circuit = 8 = 0.0473 132 Equation 11 separate analog (2-10)VDC The following analysis shows control signal each, whereas the that the Riotec 50-100 circula- The example is based on a tem- integrated FTT10 transceiver tor pump selected, which is perature differential of ∆T = sends the currently required controlled by BOA-Systronic, is 20K, and the heating curve of discharge head as digital signal oversized. The system curve of the higher-level controller was to the pump via LON bus. A the heating circuit is calculated shifted by 3.5K (parallel shift), second pair of integrated LON as the quotient of the pump resulting in a new design point: terminals serves to transmit the head (H) and the square of the the nominal volume flow rate is LON output variables of BOA- volume flow rate (Q): reduced by 25%. Systronic as well as any other nodes of the LON bus to a higher-level building management system. (Equation 12: see below) k heating circuit = H Q2 For selecting the circulator Equation 10 pump operated with BOA-Systronic, the required discharge Systrobox comes pre-assembled The volume flow rate for the de- head is calculated for the design to the main control valve as sign point of the conventionally point, including equations 2 standard. However, it can also equipped main feed circuit is and 3. 3 be mounted on the mixing Qnom = 13m /h. At this volume (Equation 13: see below) valve, as in the present case, or flow rate, the Riotec 65-100 in the control cabinet. pump can provide a maximum This new design point [Q/H] = head of approx. H=8m (see [9.75m 3 /h / 4.5m] can be han- pump catalogue). For this max- dled by a Riotec 50-60 pump. imum case, the following sys- For the present example, invest- tem constant is calculated for ment costs for the circulator the heating circuit: pump are reduced as follows: Q N, Systronic = 0.75 · Q N,conv = 0.75 · 13m 3 /h = 9.75m 3 /h Equation 12 H N,Systronic = k heating circuit · Q2 N,Systronic = 0.0473 · 9.75m 2 = 4.5m Equation 13 Pump Fig. 17 Control unit of BOASystronic (Systrobox Catalogue price 2005 [€] Riotec 65 – 100 1,825.11 Riotec 50 – 60 1,223.20 Difference [€] 602.91 Table 02: Reduced investment costs for circulator pump 19 060206_knowhow05_e_IS 19 06.02.2006, 12:50:23 Uhr 10 Practical testing 10.3 Measurements To verify the function of the BOA-Systronic system, the following quantities were measured, among others. (Table 03) Measurements were taken on Heating circuit East (3-way mixing configuration) Heating circuit West (BOA-Systronic) External temperature External temperature Volume flow rate at main feed manifold Volume flow rate at main feed manifold Differential pump pressure Differential pump pressure Electrical power input Electrical power input Tab. 03: Measured quantities 545 days in the period from 2000 to 2002. The measured measuring period 2000 to temperature of the heating values were recorded at two- 2002. The diagram shows an system is [(-12°C) – (+16°C)] = minute intervals, resulting in average external temperature of 28°C. The temperature differ- 711 values per day (24 hours), approx. 10°C in the period ence between the design point from which the day mean monitored. Depending on the and the average temperature is values were calculated for each location, the heating circuits are [(-12°C) – (+10°C)] = 22°C. measured quantity. selected for an external temper- The ratio between both values ature of approx. –12°C to –15°C. is 22/28 = 0.79. This means Regulations stipulate that the that in the monitored period building must be heated until both heating circuits on average the external temperature only require about 21% of the reaches approx. 16°C. The tem- thermal output they were se- The external temperatures perature difference between the lected for. This theory should measured were plotted for the design point and the switch-off be confirmed by a comparison 10.4 External temperature External temperature [°C] External temperature – Heidelberg test installation – Average temp. 10°C (approx) 35 30 25 20 15 10 5 0 -5 22. Oct 02 22. Sep 02 23. Aug 02 24. Jul 02 24. Jun 02 25. May 02 25. Apr 02 26. Mar 02 24. Feb 02 25. Jan 02 26. Dec 01 26. Nov 01 27. Oct 01 27. Sep 01 28. Aug 01 29. Jul 01 29. Jun 01 30. May 01 30. Apr 01 31. Mar 01 1. Mar 01 30. Jan 01 31. Dec 00 1. Dec 00 1. Nov 00 -10 Years External temperature Fig. 18 External temperatures measured at the test installation in 2000 – 2002 20 060206_knowhow05_e_IS 20 06.02.2006, 12:50:25 Uhr 10 Practical testing of the volume flow rates meas- required volume flow rate Qnom heating circuit by BOA-Systronic ured, the differential pump for the design point is calculat- during the utilization period is pressures and the pump power ed as follows: considerably smaller than the vol- consumption of both systems. Pth Qnom = 10.5 Volume flow rates 1.163 · ∆ T Equation 14 = 300 1.163 · 20 m 3 /h = 13m 3 /h. The conventional, mixing-type This value is confirmed by the ume flow rate the conventional, system must provide a thermal measurements (Fig. 19). Irrespect- mixing-type system provides to its output Pth = 300 kW at the de- ive of its degree of opening, the heating circuit. Fig. 19 shows that sign point. Based on a tempera- three-way control valve of the the measured nominal volume ture differential ∆T = 20K, the conventional, mixing-type system flow rates supplied by the conven- always supplies the nominal vol- tional, mixing-type system do not ume flow rate to the heating circuit quite reach the theoretical, calcu- (constant-flow system). BOA- lated values. This is due to the Systronic, by contrast, adjusts the control function of the thermostat- resulting volume flow rate in the ic valves under the influence of main feed circuit depending on the external heat input to the heating opening degree of the two control circuit. The equation valves and thus depending on the ing controller. As expected, the t2 water volume flow = ∫ Q(t) dt t1 volume flow rate supplied to the is used to calculate the amounts control signal issued by the heat- Volme flow rate [m3/h] Volume flow rates – Heidelberg test installation – Savings by BOA-Systronic approx. 65% 16 14 12 10 8 5 4 2 22. Oct 02 22. Sep 02 23. Aug 02 24. Jul 02 24. Jun 02 25. May 02 25. Apr 02 26. Mar 02 24. Feb 02 25. Jan 02 26. Dec 01 26. Nov 01 27. Oct 01 27. Sep 01 28. Aug 01 29. Jul 01 29. Jun 01 30. May 01 30. Apr 01 31. Mar 01 1. Mar 01 30. Jan 01 31. Dec 00 1. Dec 00 1. Nov 00 0 Years 3-way configuration BOA-Systronic Fig. 19 Volume flow rates measured at the main feed manifold in 2000 – 2002 21 060206_knowhow05_e_IS 21 06.02.2006, 12:50:25 Uhr 10 Practical testing of water (volume flow rates) At identical thermal output, pumped through the two heat- BOA-Systronic was shown to ing circuits, respectively. The pump only 40 % of the water mean values of the volume flow volume through the heating cir- rates measured in the two heat- cuit, compared to the conven- ing circuits are calculated. tionally equipped heating circuit. Measured Quantity Volume flow rate (Q) Heating circuit 3-way configuration 3 [m /h] Mean value Q Systronic /Q 3 - way configuration BOA-Systronic 3 Unit Ratio [m /h] 11.2 3.2 0.29 Table 4: Analysis of volume flow rates in 2000-2002 10.6 Differential pressures of the pumps With BOA-Systronic, the pump is operated on average at only about 66% of the nominal discharge head at design point. Measured Quantity Differential pressure (H) Heating circuit 3-way configuration Unit [m] Mean value 4.4 Ratio H Systronic /H 3 - way configuration BOA-Systronic [m] 2.9 0.66 Table 5: Analysis of differential pump pressures in 2000 -2002 Pump differential pressures [mbar] Pump differential pressures – Heidelberg test installation – Savings by BOA-Systronic approx. 37% 800 700 600 500 400 300 200 100 22. Oct 02 22. Sep 02 23. Aug 02 24. Jul 02 24. Jun 02 25. May 02 25. Apr 02 26. Mar 02 24. Feb 02 25. Jan 02 26. Dec 01 26. Nov 01 27. Oct 01 27. Sep 01 28. Aug 01 29. Jul 01 29. Jun 01 30. May 01 30. Apr 01 31. Mar 01 1. Mar 01 30. Jan 01 31. Dec 00 1. Dec 00 22 1. Nov 00 0 Years 3-way configuration BOA-Systronic Fig. 20 Differential pressures of the circulators measured in 2000 – 2002 22 060206_knowhow05_e_IS 22 06.02.2006, 12:50:26 Uhr 10 Practical testing 10.7 Pump input power The pump input power, and heads, the pump draws much thus its power consumption, is less power from the electricity proportional to the product of grid. BOA-Systronic was shown the discharge head and volume to save approx. 70% in flow rate. As BOA-Systronic electrical energy. operates the pump at reduced volume flow rates and discharge Measured quantity Pump input power (P) Heating circuit 3-way configuration Unit PSystronic /P3 - way configuration BOA-Systronic [W] Mean value Ratio [W] 561 184 0.33 Table 6: Savings in pump power consumption Pump input power [W] Pump input power – Heidelberg test installation – Savings by BOA-Systronic approx. 70% 900 800 700 600 500 400 300 200 100 22. Oct 02 22. Sep 02 23. Aug 02 24. Jul 02 24. Jun 02 25. May 02 25. Apr 02 26. Mar 02 24. Feb 02 25. Jan 02 26. Dec 01 26. Nov 01 27. Oct 01 27. Sep 01 28. Aug 01 29. Jul 01 29. Jun 01 30. May 01 30. Apr 01 31. Mar 01 1. Mar 01 30. Jan 01 31. Dec 00 1. Dec 00 1. Nov 00 0 Years 3-way configuration BOA-Systronic Fig. 21 Pump power input in 2000 – 2002 Conclusion In our example, both heating circuits on average require only 21% of the thermal output at design point. By comparison, BOA - Systronic consumes only about 30 % of the electricity required by the conventional set- up ( here : 3 - way mixing system) . 23 060206_knowhow05_e_IS 23 06.02.2006, 12:50:27 Uhr 11 Payback period for BOA - Systronic 11 Payback period for BOA -Systronic 11.1 Control valve investment and energy savings valves and the pump as well configuration, the differences as automatic hydraulic bal- depending on the nominal sys- ancing at the main feed mani- tem diameter of the main feed fold. circuit (table 07). Items (1) to (5) can also be In the present example, a main planned and achieved in a con- feed circuit with a thermal out- ventional system by increasing put of 300 kW was equipped the temperature differential at with BOA-Systronic of nominal With BOA-Systronic, the nom- design point. Items (6) and (7), system diameter DN50, where- inal diameter of the heating cir- however, can only be realized as a nominal diameter of DN65 cuit components can be smaller with BOA-Systronic. was selected for the convention- than usual. This is due to the al set-up of identical thermal combined effect of increased To compare the prices of the temperature differential (differ- two systems, the average price ence between supply and return for a conventional, mixing-type A simulation (version 1.21) was temperature) and reduced vol- system of nominal diameter used to estimate the energy ume flow rates at design point, DN65 was determined on the costs incurred for the glandless so that basis of the catalogue prices Riotec 50-100 pump during the 1. the main feed pipe is one given by 5 competitors. The heating period (table 10). Com- mixing-type configuration com- pared to the average price of a prises the following compo- mixing-type system, the invest- main feed circuit are one nents: ment costs for BOA-Systronic nominal diameter smaller • 3-way control valve would be approx. € 402 higher • swing check valve in the mix- in this case. If this extra price is nominal diameter smaller 2. the shut-off valves in the 3. the strainers in the main feed circuit are one nominal diameter smaller 4. a smaller circulator pump can be chosen 5. the measurement and control valves are one nominal output (table 08). ing line deducted from the electricity • balancing valve savings realized per heating The gross price of BOA-Sys- period, investment in BOA- tronic, by contrast, is somewhat Systronic will pay back after higher than the average price of roughly one year. a conventional mixing-type diameter smaller 6. differential pressure controllers for balancing the heat- Nominal system diameter ing circuits are not required DN25 to DN50 7. commissioning costs are re- DN65 to DN80 duced thanks to automatic initialization of the control Average extra price compared to 3-way mixing configuration in [%] 11 % 4% DN100 to DN150 13 % Tab. 07: Average extra prices for BOA-Systronic Heating circuit Unit Value Average gross price of 3-way mixing configuration, DN65 (prices of 2005) € 1,673 Gross price of BOA-Systronic, DN50 (prices of 2005) € 1,858 Gross price of LON module for Riotec pump, pre -initialized € 217 Difference +402 Tab. 08: Extra price for BOA-Systronic with Riotec pump (example: DN50) 24 060206_knowhow05_e_IS 24 06.02.2006, 12:50:27 Uhr 11 Payback period for BOA - Systronic Heating circuit Unit Value Difference Average gross price of 3-way mixing configuration, DN65 (prices of 2005) € 1,673 Gross price of BOA-Systronic, DN50 (prices of 2005) € 1,858 Gross price of LON -module forRio - Eco pump, non-initialized € 187 +372 Table 09: Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50) Cost factor Unit Value Average price of electricity € /kWh Difference 0.11 Average operating hours per heating period h 6,800 Average efficiency η of Riotec circulator pump % 35 Average pump power consumption/heating period; conv., mixing-type system DN65 kWh 5,000 Average pump power consumption/heating period; BOA-Systronic DN50 kWh 1,200 Average price of electricity/heating period; conv., mixing-type system DN65 € 548 Average price of electricity/heating period; BOA-Systronic DN50 € 131 -3,800 - 417 Table 10: Energy costs in fi rst year (example: DN 50) 11.2 Investment costs for heating circuit with Riotec pump If the extra price for BOA- present hourly rates (2005), this Systronic is deducted from the results in an additional € 45 reduced investment costs saved. (€ 1,059–€ 402), the investment costs for the main feed circuit Investment in BOA-Systronic By utilizing all saving potentials will be reduced to € 657 in this would, therefore, pay back im- offered by BOA-Systronic, the case. In addition, automated mediately, and the investment investment costs of the present commissioning further reduces and commissioning costs for heating circuit can be reduced the commissioning costs per the heating circuit would be re- by € 1,059. heating circuit by one hour. At duced substantially. Cost factor Unit Difference (1) Smaller nominal diameter of main feed pipe € -75 (2) 3 shut- off valves of smaller DN in main feed circuit € -123 (3) 1 strainer (standard mesh) of smaller DN in main feed circuit € -29 (4) 1 Riotec 50 - 60 circulator pump instead of Riotec 65 -100 € - 602 Measurement and control valves one DN smaller (BOA-Systronic) € see above € -230 € -1,059 (5) (6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch) Sum total of factors (1) to (6) Tab. 11: Reduced investment costs for heating circuit with Riotec pump, example (prices 2005) 25 060206_knowhow05_e_IS 25 06.02.2006, 12:50:28 Uhr 11 Payback period for BOA - Systronic 11.3 Investment costs for heating circuit with Rio - Eco pump If the extra price for BOA-Sys- Investment in BOA-Systronic tronic is deducted from the re- would, therefore, pay back im- duced investment costs (€ 933– mediately, and the investment € 372), the investment costs for and commissioning costs for the main feed circuit are re- the heating circuit would be By utilizing all saving potentials duced to € 561 in this case. In reduced substantially. offered by BOA-Systronic, the addition, automated commis- investment costs of the present sioning reduces the commis- heating circuit can be reduced sioning costs per heating circuit by € 933. by one hour. At present hourly (Table 12) rates (2005), this saves an additional € 45. Cost factor Unit Difference (1) Smaller nominal diameter of main feed pipe € -75 (2) 3 shut- off valves of smaller DN in main feed circuit € -123 (3) 1 strainer (standard mesh) of smaller DN in main feed circuit € -29 (4) 1 Rio - Eco 40 - 80 circulator pump instead of Riotec 65 -100 € - 476 (5) Measurement and control valves one DN smaller (BOA-Systronic) € see above € -230 € -933 (6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch) Sum total of factors (1) to (6) Table 12: Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005) 11.4 Total savings compari son Riotec / Rio - Eco In the present example, the Rio-Eco pump could be expected to pay back after approximately three years, compared to the Riotec pump. 26 060206_knowhow05_e_IS 26 06.02.2006, 12:50:28 Uhr 11 Payback period for BOA - Systronic Reduced investment costs for heating circuit (1) – (6) [€] Extra price for BOA-Systronic [€] -1,119 -34 -1,503 -933 372 Year 02 -455 -1,608 -48 Year 03 -455 -2,111 Year 04 -493 Year 05 Interest on savings (3% ) [€] Savings plus interest [€] Price of electricity [€ / kWh] Pump operating hours [h] -45 - 456 -1,062 -32 -1,094 0,11 6,800 -1,656 - 498 -1,592 - 48 -1,640 0.12 6,800 -63 -2,174 - 498 -2,138 - 64 -2,202 0.12 6,800 -2,667 -80 -2,747 -539 -2,741 - 82 -2,283 0.13 6,800 -493 -3,240 -97 -3,337 -539 -3,362 -101 -3,463 0.13 6,800 Year 06 -531 -3,868 -116 -3,984 -581 - 4,044 -121 - 4,165 0.14 6,800 Year 07 -531 -4,515 -135 -4,651 -581 - 4,746 -142 - 4,889 0.14 6,800 Year 08 -569 -5,220 -157 -5,376 - 622 -5,511 -165 -5,676 0.15 6,800 Year 09 -569 -5,945 -178 -6,124 - 622 - 6,298 -189 - 6,487 0.15 6,800 Year 10 -607 -6,731 -202 -6,933 - 664 -7,151 -215 -7,365 0.16 6,800 Year 11 -607 -7,540 -226 -7,766 - 664 - 8,029 -241 - 8,270 0.16 6,800 Year 12 -645 -8,411 -252 -8,663 -705 - 8,975 -269 -9,244 0.17 6,800 Year 13 -645 -9,308 -279 -9,588 -705 -9,949 -298 -10,248 0.17 6,800 Year 14 -682 -10,270 -308 -10,578 -747 -10,995 -330 -11,325 0.18 6,800 Year 15 -682 -11,260 -338 -11,597 -747 -12,072 -362 -12,434 0.18 6,800 Year 16 -720 -12,317 -370 -12,687 -788 -13,222 -397 -13,619 0.19 6,800 Year 17 -720 -13,407 -402 -13,809 -788 -14,407 - 432 -14,839 0.19 6,800 Year 18 -758 -14,567 -437 -15,004 - 830 -15,669 - 470 -16,139 0.20 6,800 Year 19 -758 -15,762 -473 -16,235 - 830 -16,969 -509 -17,478 0.20 6,800 Year 20 -758 -16,993 -510 -17,503 - 830 -18,308 -549 -18,857 0.20 6,800 Reduced operating costs [€] Savings [€] -45 Reduced operating costs [€] 402 Reduced commissioning costs for heating circuit [€] Reduced commissioning costs for heating circuit [€] -417 Extra price for BOA-Systronic [€] Savings plus interest [€] -1,059 Interest on savings (3% ) [€] Reduced investment costs for heating circuit (1) – (6) [€] Year 01 Rio - Eco (η =50%) Savings [€] Period Riotec (η =35%) Table 13: Outline of costs expected in 20 years of useful life 27 060206_knowhow05_e_IS 27 06.02.2006, 12:50:29 Uhr 11 Payback period for BOA - Systronic 0 -1000 -2000 -3000 -4000 -5000 -6000 -7000 Savings [€] -8000 -9000 -10.000 -11.000 -12.000 -13.000 -14.000 -15.000 -16.000 -17.000 -18.000 -19.000 -20.000 -21.000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Years [a] Riotec pump: Savings plus interest (parallel shift) Riotec pump: Savings plus interest (slope modification) Rio-Eco pump: Savings plus interest (parallel shift) Rio-Eco pump: Savings plus interest (slope modification) Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modifi cation and parallel shift (example) Period [a] 5 10 15 20 Reduced costs Unit Investment and commissioning € Riotec -702 Rio - Eco - 606 Difference 96 Pump operation € -2,313 -2,530 -217 Interest on savings (3 %) € -322 -327 -4 Total € -3,337 -3,463 -125 Annual savings € - 667 - 693 -25 Investment and commissioning € -702 - 606 96 Pump operation € -5,120 -5,600 - 480 Interest on savings (3 %) € -1,111 -1,159 - 49 Total € - 6,933 -7,365 - 433 Annual savings € - 693 -737 - 43 Investment and commissioning € -702 - 606 -96 Pump operation € - 8,381 -9,168 -787 Interest on savings (3 %) € -2,514 -2,660 -146 Total € -11,597 -12,434 - 837 Annual savings € -773 - 829 -56 Investment and commissioning € -702 - 606 -96 Pump operation € -12,095 -13,234 -1,139 Interest on savings (3 %) € - 4,706 -5,017 -311 Total € -17,503 -18,857 -1,354 Annual savings € - 875 -943 - 68 Tab. 14: Total savings 28 060206_knowhow05_e_IS 28 06.02.2006, 12:50:29 Uhr 12 References 12 References Since being released for sale in 2003, BOA-Systronic has been in operation in many heating systems in public and industrial buildings throughout Germany. The photo below shows three heating circuits equipped with BOA-Systronic systems of nominal diameter DN32. Fig. 23 Heating circuits with BOA-Systronic DN32 29 060206_knowhow05_e_IS 29 06.02.2006, 12:50:30 Uhr 13 Conclusion 13 Conclusion pressure control valves for bal- tions are prevented, and flow ancing the heating circuits are noises at the consumer points not required. They can be re- are avoided. BOA-Systronic reduces operat- placed by balancing valves, BOA-Systronic is gentle on the ing costs. which are less expensive. Even environment. in heating circuits already An analysis of load profiles in equipped with a LON-compat- Electricity is something you heating systems revealed that ible variable speed pump, in- cannot produce and store for heating circuits operate under vestment in BOA-Systronic will later use, but it must be avail- part-load conditions for more pay back in less than two years. able at the exact moment when it is needed. Burning fossil fuels than 95% of their operating time. From this finding, it is BOA-Systronic reduces the produces CO2 emissions of safe to conclude that in conven- commissioning costs for the roughly 0.53 kg per 1 kWh of tional mixing or injection-type heating circuit. electrical energy produced. Thanks to the drastic reduction systems cold return water is being circulated through the heat- The circulator pump and the in power consumption, BOA- ing circuit most of the time. control valves are initialized Systronic therefore makes a BOA-Systronic, by contrast, automatically. Static balancing positive contribution to envir- provides only the volume flow at the main feed manifold is onmental protection. actually required and can thus performed automatically by the save an average of 70% electri- pump. The hydraulic operation city costs for the circulator pump of the heating circuit is opti- over the heating period, which mized. The system immediately – depending on the thermal detects any air in the piping and output of the heating circuit – thus prevents unnecessary com- may amount to several hun- missioning work. Altogether, dreds of Euros in electricity the costs for heating circuit savings per year. commissioning are reduced. BOA-Systronic reduces the in- BOA-Systronic offers increased vestment costs for the heating comfort of use. circuit. The hydraulic operation of the In new or replacement installa- heating circuit is optimized tions, the investment costs for thanks to substantially reduced the main feed circuit can be re- discharge heads and volume duced without modifying the flow rates. Excessive discharge original planning. Differential heads under part-load condi- 30 060206_knowhow05_e_IS 30 06.02.2006, 12:50:32 Uhr List of figures Fig. 1 Hydraulics schematics of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Fig. 2 Comparison of systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Fig. 3 BOA-Systronic components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Fig. 4 Volume flow rates of 3-way valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Fig. 5 Reduced volume flow rates of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Fig. 6 Circulator pump heads (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Fig. 7 Heating circuit with branch circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Fig. 8 Excess circulator pump heads (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Fig. 9 Two-boiler system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Fig. 10 Return manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Fig. 11 Control cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Fig. 12 Heating controllers for West and East wings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Fig. 13 Main feed manifold, West and East wings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Fig. 14 Main feed circuit with BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Fig. 15 Main control valve of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Fig. 16 Mixing valve of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Fig. 17 Control unit of BOA-Systronic (Systrobox) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Fig. 18 External temperatures measured at the test installation in 2000 – 2002 . . . . . . . . . . . . . . . 20 Fig. 19 Volume flow rates measured at the main feed manifold in 2000 – 2002 . . . . . . . . . . . . . . . 21 Fig. 20 Differential pressure of the circulators, measured in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . 22 Fig. 21 Pump power input in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modification and parallel shift . . 29 Fig. 23 Heating circuits with BOA-Systronic DN32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 List of tables Table 1 Performance data of main feed circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Table 2 Reduced investment costs for circulator pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Table 3 Measured quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Table 4 Analysis of volume flow rates in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Table 5 Analysis of differential pump pressures in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Table 6 Savings in pump power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Table 7 Average extra prices for BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 8 Extra price for BOA-Systronic with Riotec pump (example: DN50) . . . . . . . . . . . . . . . . . . 24 Table 9 Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50) . . . . . . . . . . . . . . . . 25 Table 10 Energy costs in first year (example: DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Table 11 Reduced investment costs for heating circuit with Riotec pump, example (prices 2005) . . . 25 Table 12 Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005) . . 26 Table 13 Outline of costs expected in 20 years of useful life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Table 14 Total savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 31 060206_knowhow05_e_IS 31 06.02.2006, 12:50:32 Uhr Fax order form “KSB know-how” series At your request, we will be pleased to send you all “KSB know-how” brochures previously published as well as any volumes to be published in the future. All we need is your address and confirmation below. Company address or stamp: Company: Attn.: Street address: Post or ZIP code / City / Country: Please send me the following technical brochures: (tick where applicable) KSB Know-how Selecting Centrifugal Pumps KSB Know-how Volume 01 KSB Know-how Volume 02 Water Hammer Boa-Systronic ... copy and fax this form to: Fax: +49 (62 33) 86 34 39 KSB Aktiengesellschaft Johann-Klein-Straße 9 67227 Frankenthal Tel.: +49 (62 33) 86 21 18 Fax: +49 (62 33) 86 34 39 www.ksb.com 060206_knowhow05_e_IS 32 06.02.2006, 12:50:48 Uhr Reproduction in whole or in part without express permission of KSB is prohibited. © KSB Aktiengesellschaft 0508.023-10 kubbli Your local KSB representative: 11/06 We look forward to hearing from you. KSB Aktiengesellschaft • Bahnhofplatz 1 91257 Pegnitz (Germany) • www.ksb.com