Re-Model O`Reilly Auto Parts Store 321 SOUTH MAIN STREET
Transcription
Re-Model O`Reilly Auto Parts Store 321 SOUTH MAIN STREET
DISTRIBUTIONS: OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record Re-Model O'Reilly Auto Parts Store 321 SOUTH MAIN STREET FOUNTAIN INN, SC 29644 DOOR MARK ? WINDOW MARK BIDDING INFORMATION WWW.DESIGNBIDBUILD.NET/OREILLY *CLICK ON CURRENT PROJECTS LINK LOCATED ON SIGN IN PAGE TO VIEW INVITED GENERAL CONTRACTORS. DETAIL NUMBER X XX DETAIL MARK # O'REILLY AUTOMOTIVE STORES, INC. A MISSOURI CORPORATION (FORMERLY KNOWN AS O'REILLY AUTOMOTIVE, INC.) CORPORATE OFFICES 233 SOUTH PATTERSON SPRINGFIELD, MISSOURI 65802 417-862-2674 PHONE GRID MARK SHEET NUMBER ALL SUB-CONTRACTOR BIDS TO BE SUBMITTED TO INVITED GENERAL CONTRACTORS ONLY. AFF AC A/C ALT AL ALUM AB ARCH BSMT BRG BM BEL BLK BLKG BD BW BOT BF BOF BRK BLDG BUR CAB CLG CL C/O CC CLR COL CONC CMU CONST CONTR CONT CNTR CFL CISK CRS CF CY DL DEM DTL DIAG DIAM DIM DR DS D DWG DF E EIFS ELEC EWC EL ELEV ELEV EMER EQ EXG EXIST EXP EXT FOF FO FOM FOS FIN FFE FFL FE FEC FT FLG FLR FD FTG FDN FNDN FUR GA GV GALV GC GL GP GYP GWB HTG HVAC HT HC HM HK HOR HB INS ABOVE FINISHED FLOOR ACOUSTICAL AIR CONDITIONING ALTERNATE ALUMINUM ALUMINUM ANCHOR BOLT ARCHITECT (URAL) BASEMENT BEARING BENCH MARK BELOW BLOCK BLOCKING BOARD BOTH WAYS BOTTOM BOTTOM OF FOOTING BOTTOM OF FOOTING BRICK BUILDING BUILT-UP ROOFING CABINET CEILING CENTER LINE CENTER OF CENTER TO CENTER CLEAR COLUMN CONCRETE CONCRETE MASONRY UNIT CONSTRUCTION CONTRACTOR CONTINUOUS COUNTER COUNTER FLASHING COUNTERSUNK COURSE(S) CUBIC FOOT CUBIC YARD DEAD LOAD DEMOLISH, DEMOLITION DETAIL DIAGONAL DIAMETER DIMENSION DOOR DOWN SPOUT DRAIN DRAWING DRINKING FOUNTAIN EAST EXTERIOR INSULATION AND FINISH SYSTEM ELECTRIC(AL) ELECTRIC WATER COOLER ELEVATION ELEVATION ELEVATOR EMERGENCY EQUAL EXISTING EXISTING EXPOSED EXTERIOR FACE OF FINISH FACE OF FACE OF MASONRY FACE OF STUDS FINISH(ED) FINISHED FLOOR ELEV. FINISHED FLOOR LINE FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FIRE TREATED FLASHING FLOOR FLOOR DRAIN FOOTING FOUNDATION FOUNDATION FURRED(ING) GAGE, GAUGE GALVANIZED GALVANIZED GENERAL CONTRACT(OR) GLASS, GLAZING GYPSUM GYPSUM GYPSUM WALL BOARD HEATING HEATING/VENTILATING/AIR COND. HEIGHT HOLLOW CORE HOLLOW METAL HOOK(S) HORIZONTAL HOSE BIBB INSULATE(D), (ION) INSUL INT JST JT JNT KIT LH LF LTL L LL MACH MH MFR MAS MO MAX MECH MED MBR MET MTL M MWK MIN MISC MT NOM N NIC NTS OC OPG OPH OD OO OA OH PC PNT PTD PKG PLAM PL PWD PVC PSF PSI PT PL REM RET RH RD RFG RM RO SNT SLNT SEC SECT SHTHG SHT SIM SC S SF SI SY STD STO SUS SYM TEL TV THK T&G TM TOM TS TOS TW TOW TYP UON UNO VERT VT WSCT WC WWF W W WIN WO W/O WD INSULATE INTERIOR JOIST JOINT JOINT KITCHEN LEFT HAND LINEAL FOOT LENGTH LINTEL LIVE LOAD MACHINE MANHOLE MANUFACTURER MASONRY MASONRY OPENING MAXIMUM MECHANIC(AL) MEDIUM MODIFIED BITUMEN ROOFING METAL METAL METER(S) MILLWORK MINIMUM MISCELLANEOUS MOUNT(ED), (ING) NOMINAL NORTH NOT IN CONTRACT NOT TO SCALE ON CENTER(S) OPENING OPPOSITE HAND OUTSIDE DIAMETER OUT TO OUT OVERALL OVERHEAD PIECE PAINT(ED) PAINT(ED) PARKING PLASTIC LAMINATE PLATE PLYWOOD POLYVINYL CHLORIDE POUNDS PER SQUARE FT. POUNDS PER SQUARE IN. PRESSURE TREATED PROPERTY LINE REMOVE RETURN RIGHT HAND ROOF DRAIN ROOFING ROOM ROUGH OPENING SEALANT SEALANT SECTION SECTION SHEATHING SHEET SIMILAR SOLID CORE SOUTH SQUARE FOOT SQUARE INCH SQUARE YARD STANDARD STORAGE SUSPENDED SYMMETRY, (ICAL) TELEPHONE TELEVISION THICK(NESS) TONGUE & GROOVE TOP OF MASONRY TOP OF MASONRY TOP OF STEEL TOP OF STEEL TOP OF WALL TOP OF WALL TYPICAL UNLESS OTHERWISE NOTED UNLESS NOTED OTHERWISE VERTICAL VINYL TILE WAINSCOT WATER CLOSET WELDED WIRE FABRIC WEST WIDTH, WIDE WINDOW WITHOUT WITHOUT WOOD D1 / A3 JEREMY BASS PROJECT ADMINISTRATOR 417-862-2674 2949 BUILDING OFFICIAL CONTACT NUMBER: 864-409-3334 SHEET NUMBER COUNTY: ZIP CODE: GREENVILLE 29644 T1 GOVERNING CODES AND ORDINANCES BUILDING CODE: ACCESSIBILITY CODE: PLUMBING CODE: MECHANICAL CODE: ELECTRICAL CODE: FIRE CODE: ENERGY CODE: 2012 IBC ANSI A117.1 2012 IPC 2012 IMC 2011 NEC 2012 IFC 2012 IECC ASP1 USE GROUP & CONSTRUCTION TYPE USE GROUP: CONSTRUCTION TYPE: A. B. CONTRACT ADMINISTRATION (LIMITED SERVICE): THE ARCHITECT AND/OR ENGINEER OF RECORD INDICATED HEREIN ARE PROVIDING A LIMITED SERVICE AND NOT PROVIDING CONTRACT ADMINISTRATION SERVICES FOR THIS PROJECT WHICH IS THE RESPONSIBILITY OF OTHERS. THE ARCHITECT AND/OR ENGINEER ARE NOT RESPONSIBLE FOR FIELD ACTIVITIES ON THIS PROJECT WITHOUT DIRECT INSPECTION OF THE WORK IN PROGRESS. IF FIELD CONDITIONS ARE UNCOVERED THAT REQUIRE A CHANGE OR ADDITIONAL INFORMATION, THE ARCHITECT AND/OR ENGINEER DOES NOT DELEGATE AUTHORITY TO ANYONE ELSE FOR DETERMINING THE MEANING OF PLANS OR SPECIFICATIONS AS AUTHENTICATED HEREIN. DO NOT SCALE DRAWINGS. CONTACT PROFESSIONAL OF RECORD FOR CLARIFICATIONS NEEDED. 2. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOB SITE PRIOR TO START OF CONSTRUCTION, IF DISCREPANCIES ARE FOUND, THE OWNER SHALL BE NOTIFIED FOR CLARIFICATION PRIOR TO COMMENCING WORK. NOTIFY "PROFESSIONAL OF RECORD" IF METAL STUDS ARE NOTCHED OR MANIPULATED IN ANY MANNER TO ACCOMMODATE OVERHEAD WORK. GENERAL CONTRACTOR SHALL REVIEW ANY TENANT CRITERIA/HANDBOOKS AND COMPLY WITH ALL REQUIREMENTS THEREOF. 3. PRIOR TO SUBMITTING HIS BID THE GENERAL CONTRACTOR SHALL CAREFULLY STUDY ALL DRAWINGS AND VERIFY EXTENT OF DEMOLITION WORK (IF REQUIRED) WITH TENANT'S FIELD REPRESENTATIVE. 4. DETAILS ARE NOT INTENDED TO SHOW METHOD AND MANNER OF ACCOMPLISHING WORK. MINOR MODIFICATIONS MAY BE REQUIRED TO SUIT THE JOB DIMENSIONS OR CONDITIONS AND SHALL BE INCLUDED AS PART OF THE WORK. OBTAIN OWNERS REPRESENTATIVE APPROVAL PRIOR TO PROCEEDING WITH DEVIATION FROM DETAIL(S). 5. GENERAL CONTRACTOR SHALL PROVIDE PEDESTRIAN PROTECTION BARRICADES AND/OR CANOPIES AS REQUIRED BY LOCAL AUTHORITIES, LANDLORD OR AS NECESSARY FOR PEDESTRIAN SAFETY. 6. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. CONTRACTOR SHALL NOTIFY TENANT IMMEDIATELY UPON ANY/ALL DISCREPANCIES. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR FLOOR PATCHING, LEVELING, AND PREPARATION FOR AND OF FLOOR FINISH SUGGESTED INSTALLATION SPECIFICATIONS. 8. PROVIDE METAL TRIM OR CASING AT ALL EDGES OF PLASTER AND DRYWALL SURFACES WHERE THEY TERMINATE OR MEET ANY OTHER MATERIAL. PROVIDE METAL CORNER BEAD AT ALL OUTSIDE CORNERS OF PLASTERED OR DRYWALLED SURFACES, UNLESS NOTED OTHERWISE. 9. 10. 11. 26. COMBUSTIBLE INTERIOR FINISH PRODUCTS SHALL BE PROVIDED PER THE REQUIREMENTS OF THE RESPECTIVE OCCUPANCY CHAPTER OF THE LOCAL BUILDING CODE, THAT THE PROJECT IS BEING PERMITTED UNDER. PROVIDE VERIFICATION AT THE TIME OF FINAL INSPECTION THAT THE PRODUCTS COMPLY WITH THE REQUIREMENTS. 27. MATERIALS, EQUIPMENT, AND ASSEMBLIES SHOWN OR SPECIFIED ARE MINIMUM REQUIREMENTS OR PERFORMANCE STANDARDS. LOCAL JURISDICTIONS MAY REQUIRE PERFORMANCE STANDARDS BEYOND THOSE SHOWN OR SPECIFIED. FURTHERMORE, LOCAL JURISDICTIONS MAY PREVENT THE USE OF COMMONLY ACCEPTED MATERIALS. CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH ALL LOCAL REQUIREMENTS FOR LICENSING, MATERIALS, AND PERFORMANCE STANDARDS, PRIOR TO SUBMITTING BID. ALL CONFLICTS BETWEEN THE CONTRACT DOCUMENTS AND LOCAL REQUIREMENTS SHALL BE BROUGHT TO THE OWNER'S ATTENTION AND RESOLVED, BY MUTUAL AGREEMENT, PRIOR TO SUBMISSION OF BID OR HIGHEST PRICED WORK. LOCAL REQUIREMENTS VERSUS SPECIFIED REQUIREMENTS SHALL BE INCLUDED IN THE BID. 28. 29. THIS DESIGN CRITERIA IS PROVIDED FOR BUILDING OFFICIAL REVIEW CONVENIENCE ONLY AND IS NOT INTENDED FOR USE BY COMPONENT DESIGNERS OR MANUFACTURERS AS THEIR SOLE DESIGN CRITERIA WITHOUT VERIFICATION. EACH DESIGNER AND/OR MANUFACTURER MUST INDEPENDENTLY CONFIRM ALL CODE CRITERIA WITH WHICH HIS ELEMENTS OR COMPONENTS MUST COMPLY, INCLUDING BUT NOT LIMITED TO LOADING, APPLICATION, FUNCTIONALITY, ETC. PERFORMANCE CRITERIA PROVIDED ELSEWHERE BY A SPECIFIC DISCIPLINE SHOULD BE REGARDED AS THE MINIMUM STANDARDS ACCEPTABLE TO THE CLIENT. EACH SUPPLIER MUST EVALUATE THESE MINIMUMS AGAINST SPECIFIC INDUSTRY STANDARDS AS WELL AS CODES, LAWS, ORDINANCES AND UNDERWRITER REQUIREMENTS GOVERNING HIS PRODUCT AS WELL AS OWNER INSURER REQUIREMENTS, AS APPLICABLE. THE MOST STRINGENT OF THESE CRITERIA SHALL GOVERN. A VESTIBULE IS NOT BEING PROVIDED IN ACCORDANCE ASHRAE STANDARD 90.1-2010, ASHRAE STANDARD 90.1 DOES NOT REQUIRE A VESTIBULE IN CLIMATE ZONE 3 IN BUILDINGS UNDER 10,000 SF AND LESS THAN FOUR STORIES ABOVE STREET LEVEL. OCCUPANCY LOAD SUMMARY KEEP ALL PIPING AS CLOSE TO WALLS AND AS HIGH TO UNDERSIDE OF ROOF AS POSSIBLE. THE INFORMATION PROVIDED IN THIS DOCUMENT IS FROM DOCUMENTATION AVAILABLE AND MAY NOT REFLECT EXACT FIELD CONDITIONS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY ALL INFORMATION. BRING CONFLICTS TO THE ATTENTION OF THE OWNERS REPRESENTATIVE AND OBTAIN APPROVAL FROM THE OWNERS REPRESENTATIVE OR AUTHORITY HAVING JURISDICTION PRIOR TO PROCEEDING WITH ALTERNATE METHODS AND/OR MATERIALS, ETC. DRYWALL SHALL BE 5/8" GYPSUM BOARD ON 3 5/8" OR 6" X 18-20 GAUGE METAL STUDS AT 16" OC UNLESS NOTED OTHERWISE. GYPSUM BOARD SHALL BE TAPED AND SANDED TO 6" ABOVE FINISH CEILING AND READY TO RECEIVE PAINT. METAL GAUGE PER MANUFACTURERS RECOMMENDATIONS BASED ON HEIGHT LIMITATIONS. 13. ALL DOOR JAMBS ARE TO BE LOCATED 4" OFF THE FACE OF STUD OF ADJACENT WALL UNLESS NOTED OTHERWISE. 14. CONTRACTOR SHALL VERIFY EXISTING LOCATION OF MECHANICAL, ELECTRICAL, AND PLUMBING SERVICES AND EXTEND AS REQUIRED TO LOCATION SHOWN ON PLANS. REFER TO ELECTRICAL DRAWINGS AND STANDARD SPECIFICATION SHEETS FOR FULL SCOPE OF WORK. 15. ANY CONDUIT NOT USED SHALL BE CAPPED BELOW SLAB OR RUN ABOVE AND TERMINATED. 16. REFER TO ALL ARCHITECTURAL/STRUCTURAL/ ELECTRICAL/MECHANICAL/ PLUMBING DRAWINGS FOR ENTIRE SCOPE OF WORK. 17. ALL MATERIALS AND WORK PERFORMED MUST BE IN STRICT ACCORDANCE WITH ALL APPLICABLE RULES, REGULATIONS, STANDARDS, CODES, ORDINANCES, AND LAWS OF ALL LOCAL, CITY, COUNTY, STATE, AND FEDERAL ORGANIZATIONS HAVING JURISDICTION. 18. WHERE APPLICABLE, ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE LISTED BY UNDERWRITERS LABORATORIES (U.L.) AND TENANT'S RESPECTIVE INSURANCE CARRIER. 19. AS WORK PROGRESSES AND FOR THE DURATION OF THE CONTRACT, THE CONTRACTOR SHALL MAINTAIN A COMPLETE AND SEPARATE SET OF PRINTS OF THE CONTRACT DRAWINGS AT THE JOB SITE AT ALL TIMES. THE CONTRACTOR SHALL CLEARLY AND ACCURATELY RECORD ALL WORK COMPLETED AND ALL MODIFICATIONS AND CHANGES FROM THE ORIGINAL CONTRACT DRAWINGS. 20. CONTACT CITY BUILDING DEPARTMENT FOR ALL INSPECTIONS. 21. ALL CONSTRUCTION SHALL CONFORM TO ALL CURRENT GOVERNING CODES, ALL APPLICABLE ORDINANCES, REGULATIONS, THE SPECIFICATIONS AND THE DRAWINGS. 22. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY BARRIERS, LIGHTING, COVERING, FIRE PREVENTION, NECESSARY FOR THE SAFETY OF ALL PERSONNEL AND THE PROPERTY THROUGHOUT THE ENTIRE PERIOD OF THE CONSTRUCTION CONTRACT. 23. PROVIDE VENTILATION FOR ALL ELECTRICAL AND TELEPHONE EQUIPMENT ROOMS. PROVIDE VENTILATION IN ACCORDANCE WITH THE LOCAL BUILDING CODE. 24. SAFETY STANDARDS: IT IS THE INTENT OF THESE DOCUMENTS TO INCORPORATE THE SAFETY STANDARDS OF THE CITY AND STATE THAT THE PROJECT IS BEING PERMITTED UNDER. SUCH STANDARDS SHALL BE COMPLIED WITH WHETHER OR NOT SPECIFICALLY DETAILED. FLAME SPREAD FOR THE FINISH MATERIAL FOR INTERIOR WALLS AND CEILINGS SHALL COMPLY WITH THE LOCAL BUILDING CODE. P1 PLUMBING PLAN M1 HVAC PLAN M2 HVAC SCHEDULES E1 LIGHTING PLAN E2 POWER PLAN E3 ELECTRICAL SCHEDULES ES1 ENERGY SYSTEM (FOR REFERENCE ONLY) 83.73 OFFICE/TOILET ROOMS 225 100 2.25 TOTAL BUILDING OCCUPANCY LOAD 227.22 TOTAL BUILDING AREA (S.F.) 6974 PROJECT CONSULTANT CASCO 10877 WATSON ROAD ST. LOUIS, MO 63127 THE FOLLOWING INDIVIDUALS WERE TEAM MEMBERS INVOLVED IN THIS PROJECT UNDER THE DIRECT SUPERVISION OF THEIR RESPECTIVE PROFESSIONAL OF RECORD: .20 16.75 OFFICE/TOILET ROOMS 2.25 .20 0.45 ALL SIGNAGE TO BE PROVIDED UNDER SEPARATE PERMIT APPLICATION. FINISH PLAN 30 83.73 SIGNAGE NOTE F1 2512 PARTS AREA "C" INSURE THAT THERE ARE NO WATER LEAKS IN CONCEALED PLUMBING CHASES. RETURN AIR PATHS AND PLENUMS SHALL BE KEPT DRY. ALL EXISTING SUPPLY AIR PATHS AND ALL EXISTING DUCTWORK TO BE RE-USED SHALL BE CLEANED AND TREATED AS REQUIRED TO REMOVE THE POTENTIAL FOR MOLD AND MILDEW. ALL DAMP AREAS SHALL BE DRIED THOROUGHLY PRIOR TO ENCLOSURE. INTERIOR ELEVATIONS PARTS AREA "C" 6.75 8. A4 ENERGY SYSTEM (FOR REFERENCE ONLY) .20 ALL CONDENSATE DRAIN PANS SHALL BE CLEANED AND KEPT FREE FROM DEBRIS UNTIL AND WHEN THE FACILITY IS TURNED OVER TO THE OWNER OR TENANT. INSURE POSITIVE DRAINAGE AT ALL DRAIN PANS. INSURE THAT ALL "COLD" SURFACES ARE INSULATED AND COVERED WITH A FULLY SEALED AND CONTINUOUS VAPOR BARRIER. ("COLD" SURFACES INCLUDE, BUT ARE NOT LIMITED TO, DOMESTIC COLD WATER PIPING, CHILLED WATER PIPING, INTERIOR RAIN LEADERS, OUTDOOR AIR INTAKES, AND DUCTWORK CARRYING AIR CONDITIONED SUPPLY AIR.) EXTERIOR ELEVATIONS ES3 33.73 7. A3 33.73 PARTS AREA "B" ALL PENETRATIONS SHALL BE SEALED WATER-TIGHT TO PREVENT MOISTURE MIGRATION FROM ENTERING THE BUILDING OR WALL CAVITIES. DOOR DETAILS AND NOTES 30 1. 6. A2.2 1012 21.50 THE CONTRACTOR SHALL COMPLY WITH FEDERAL ENVIRONMENTAL AND OHSA REGULATIONS AND ALL LOCAL AND STATE HEALTH DEPARTMENT REQUIREMENTS AND RECOMMENDATIONS REGARDING MOLD AND MILDEW. DOOR SCHEDULE AND DETAILS PARTS AREA "B" .20 5. A2.1 ENERGY SYSTEM (FOR REFERENCE ONLY) 107.5 THE CONTRACTOR SHALL MAKE ALL REASONABLE EFFORTS TO AVOID CONDITIONS FAVORABLE TO THE DEVELOPMENT OF MOLD AND MILDEW, ESPECIALLY IN VOIDS WHICH WILL BE CONCEALED AND NOT VENTILATED. IN ALL CASES, INTERIOR SPACES AND INTERIOR FINISHED CONSTRUCTION SHALL BE MAINTAINED IN DRY AND WELL-VENTILATED CONDITIONS. REFLECTED CEILING PLAN ES2 PARTS AREA "A" 4. A1.2 107.50 THE FOLLOWING REQUIREMENTS SHALL APPLY TO ALL NEW AND REMODEL CONSTRUCTION PROJECTS. ONCE DISCOVERY OR SUSPICION OF MOLD AND/OR MILDEW IS MADE, THE CONTRACTOR SHALL TAKE ALL REASONABLE AND PRACTICAL PRECAUTIONS TO PROTECT ALL CONSTRUCTION PERSONNEL AND THE PUBLIC FROM EXPOSURE TO MOLD AND/OR MILDEW, AND SUCH PRECAUTIONS SHALL REMAIN IN PLACE UNTIL SUCH TIME AS THE OWNER OR HEALTH AUTHORITY DIRECTS OTHERWISE. CONSTRUCTION OPERATIONS SHALL NOT BE STOPPED OR CURTAILED, EXCEPT IN THE AREA OF MOLD/MILDEW CONCERN, DUE TO THESE REQUIRED PRECAUTIONS. FLOOR PLAN 30 REQUIRED EGRESS WIDTH 3. A1.1 3225 REQ'D WIDTH PER OCC. CONCURRENTLY, THE CONTRACTOR SHALL BE RESPONSIBLE TO RETAIN A MOLD AND MILDEW CERTIFIED TESTING AGENCY TO PERFORM AN INVESTIGATION AND TESTING AS REQUIRED TO EVALUATE THE NATURE AND EXTENT OF THE PROBLEM. IF THE TESTING AGENCY CONFIRMS HAZARDS, THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A MINIMUM OF TWO (2) BIDS FROM COMPANIES QUALIFIED AND LICENSED TO PERFORM ALL NECESSARY REMEDIATION WORK, COMPLYING WITH ALL LOCAL, STATE, AND FEDERAL ENVIRONMENTAL REGULATIONS, CODES, AND STATUTES. DEMOLITION PLAN PARTS AREA "A" OCC. 2. ARCHITECTURAL SITE PLAN OCCUPANTS PER AREA ROOM IN THE EVENT THE CONTRACTOR DISCOVERS, AT ANY TIME DURING DEMOLITION, CONSTRUCTION, AND/OR REMODELING OPERATIONS, EXISTING CONDITIONS THAT COULD INCLUDE THE PRESENCE OF MOLD AND/OR MILDEW, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER'S REPRESENTATIVE AND THE ARCHITECT/ENGINEER OF RECORD, IN WRITING, OF THE CONCERNS AND/OR SUSPICIONS. COVER SHEET AREA (S.F.) PER OCCUPANT EGRESS WIDTH CALCULATIONS MOLD AND MILDEW NOTES SHEET NAME AREA (S.F.) ROOM THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE EXACT LOCATION OF ALL UTILITY LINES AND INTERCEPT AS REQUIRED. 12. 25. GENERAL NOTES QUALITY STANDARDS AND BUILDING CODES: CONTRACTORS SHALL BE RESPONSIBLE FOR KNOWING THE QUALITY AND PUBLIC SAFETY REGULATIONS SET FORTH IN THE GOVERNING CODES AND OTHER APPLICABLE REGULATIONS OF LOCAL AND STATE AGENCIES HAVING JURISDICTION WHICH GOVERN EACH CONTRACTOR'S WORK. 1. D1 M (MERCANTILE) II-B (NON-COMBUSTIBLE / UNPROTECTED) NON-SPRINKLERED 22'-8" BUILDING HEIGHT: GENERAL NOTES DEMOLITION WORK SHEET INDEX CONTACT OWNERS REPRESENTATIVE FOR PROJECT INFORMATION: ABBREVIATIONS LEGEND PARKING LOT / ROOF BUILDING CODE WALL TYPE MARK ? ASP1 DESCRIPTION TOTAL EGRESS WIDTH REQUIRED 45.44 TOTAL EGRESS WIDTH PROVIDED 102.00 PROJECT DESCRIPTION REMODEL OF AN EXISTING RETAIL STORE. SCOPE IS TO REMOVE EXISTING MERCHANDISING EQUIPMENT, FIXTURES, SHELVING, CEILINGS, INTERIOR WALLS, AND FINISHES AS REQ'D. REWORK OR REPLACE HVAC AND REPLACE LIGHT FIXTURES & POWER OUTLETS AS REQUIRED BY NEW FLOOR PLAN. THE EXTERIOR OF BUILDING IS TO BE PAINTED. SITE SIDEWALKS, PARKING, ETC. ARE EXISTING. QUALITY CONTROL 1. WHERE REQUIRED, REFER TO STRUCTURAL DRAWINGS FOR SCHEDULE OF SPECIAL INSPECTIONS, IF INDICATED. 2. WHERE REQUIRED, THE OWNER SHALL PROVIDE THE SERVICES OF AN INDEPENDENT TESTING LABORATORY TO PERFORM TESTING AND SPECIAL INSPECTIONS INDICATED. TEAM MEMBERS: ARCHITECTURE: HVAC/PLUMBING: ELECTRICAL: QUALITY ASSURANCE: JESSI MUELLER CHRISTY QUIGLEY PETE WALKER CARON STEVENSON NOTE: THIS DESIGN CRITERIA IS PROVIDED FOR BUILDING OFFICIAL REVIEW CONVENIENCE ONLY AND IS NOT INTENDED FOR USE BY COMPONENT DESIGNERS OR MANUFACTURES AS THEIR SOLE DESIGN CRITERIA WITHOUT VERIFICATION. EACH DESIGNER AND/OR MANUFACTURER MUST INDEPENDENTLY CONFIRM ALL CODE CRITERIA WITH WHICH HIS ELEMENTS OR COMPONENTS MUST COMPLY, INCLUDING BUT NOT LIMITED TO LOADING, APPLICATION, FUNCTIONALITY, ETC. PERFORMANCE CRITERIA PROVIDED ELSEWHERE BY A SPECIFIC DISCIPLINE SHOULD BE REGARDED AS THE MINIMUM STANDARDS ACCEPTABLE TO THE CLIENT. EACH SUPPLIER MUST EVALUATE THESE MINIMUMS AGAINST SPECIFIC INDUSTRY STANDARDS AS WELL AS CODES, LAWS, ORDINANCES, AND UNDERWRITER REQUIREMENTS GOVERNING HIS PRODUCT AS WELL AS OWNER INSURER REQUIREMENTS, AS APPLICABLE. THE MOST STRINGENT OF THESE CRITERIA SHALL GOVERN. 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 SHEET NUMBER WT? SHEET NUMBER PROJECT: X XX SECTION NUMBER SECTION / ELEVATION MARK LANDLORD WORK PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 OWNER OR TENANT SYMBOLS LEGEND SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. ARCHITECT PROFESSIONAL OF RECORD WILLIAM A. BANDLE 10877 WATSON ROAD ST. LOUIS, MO 63127 MEP ENGINEERS PROFESSIONAL OF RECORD MIKE GRAPPERHAUS 10877 WATSON ROAD ST. LOUIS, MO 63127 HARRY AUMAN 10877 WATSON ROAD ST. LOUIS, MO 63127 DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 T1 SHEET 1 OF 1 GENERAL NOTES: WHITE: SYMBOL AND BACKGROUND BLUE: SYMBOL FIELD DISTRIBUTIONS: 1. GC TO PROVIDE POWER TO ALL SIGNAGE IF NOT ALREADY AVAILABLE. OWNER REVIEW 02/08/13 2. PRIOR TO INSTALLATION, GENERAL CONTRACTOR TO CONFIRM THAT LIGHT POLES, LANDSCAPING AND UTILITIES DO NOT CONFLICT WITH SIGN LOCATION SHOWN. IF ANY POTENTIAL CONFLICT IS DISCOVERED, GENERAL CONTRACTOR TO CONTACT THE O'REILLY PROJECT ADMINISTRATOR BEFORE PROCEEDING. PERMIT/BID 02/21/13 SIGN SIZE: 12" X 18" KEYED NOTES: STATE DISABLED PARKING PERMIT REQUIRED VAN ACCESSIBLE GREEN: LETTERS AND BORDER VAN ACCESSIBLE SIGN SIZE: 6" X 12" (@ VAN ACCESSIBLE SPACE ONLY) MOUNT AS REQ'D PER LOCAL AND/OR ADA STDS. VERIFY W/ LOCAL AUTHORITIES 24 ACCESSIBLE SIGN __________________________________________________ ASP1 SCALE: NONE EXISTING PARKING LOT: EXISTING PARKING LOT, INCLUDING ALL ACCESSIBLE PARKING STALLS, TO REMAIN, UNLESS NOTED OTHERWISE. LANDLORD CONTRACTOR TO REPAIR, RE-STRIPE AND SEAL AS SHOWN. EXISTING ACCESSIBILITY SYMBOL: EXISTING ACCESSIBILITY SYMBOL TO REMAIN. LANDLORD CONTRACTOR TO RE-PAINT NEW STRIPING: LANDLORD CONTRACTOR TO PAINT 4" STRIPING USING APPROVED COLORS. NEW WALL MOUNTED H/C PARKING SIGN: NEW WALL MOUNTED H/C PARKING SIGN BY LANDLORD. REFER TO DETAIL 24/ASP1 FOR MORE INFORMATION. EXISTING ACCESS AISLE: EXISTING ACCESS AISLE FLUSH WITH SIDEWALK TO REMAIN. William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. EXISTING ENTRANCE DOOR: EXISTING ENTRANCE DOORS TO REMAIN. VERIFY COMPLIANCE WITH ACCESSIBILITY REQUIREMENTS. NEW DELIVERY / EGRESS DOOR: NEW DELIVERY / EGRESS DOOR. REFER TO FLOOR PLAN AND DOOR SCHEDULE. EXISTING LIGHT POLE: EXISTING LIGHT POLE TO REMAIN. EXISTING BOLLARD: EXISTING BOLLARD TO REMAIN. EXISTING LOADING DOCK: EXISTING LOADING DOCK, STAIR, AND GUARDRAIL TO REMAIN. EXISTING GAS METER: EXISTING GAS METER TO REMAIN. LANDLORD TO ENSURE ROOF IS IN WATER-TIGHT CONDITION. REPAIR OR REPLACE AS REQUIRED. EXISTING ELECTRIC METER: EXISTING ELECTRIC METER TO REMAIN. EXISTING FIRE HYDRANT: EXISTING FIRE HYDRANT TO REMAIN. NEW MONUMENT SIGN: NEW MONUMENT SIGN TO BE INSTALLED UNDER SEPARATE PERMIT. FIELD VERIFY LOCATION. GC TO PROVIDE MONUMENT FOUNDATION, CONTACT P.A. FOR MORE INFO. O'Reilly Auto Parts PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 DELIVERY / EGRESS DOORS MAIN ENTRANCE 18'-0" MIN. 321 S. MAIN ST. FOUNTAIN INN, SC 29644 3 EQ SPACES = 29'-8 3/8" 3 SPACES = 27'-0" 3 EQ SPACES = 29'-11 1/4" 9 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 7 EX'G SPACES @ 9'-0" EA. = 63'-0" 7 EX'G SPACES @ 9'-0" EA. = 63'-0" PROJECT: 2'-0" VERIFY 8'-0" MIN. PROJECT LOCATION _______________________________________________________ ASP1 SCALE: N.T.S. DRAWN: CHECKED: DATE: JOB NO.: SHEET: 1 JAM CMS 02/08/13 313243 SITE PLAN _________________________________ ASP1 SCALE: 1/16" = 1'-0" SHEET 1 OF 1 GENERAL DEMOLITION NOTES: 1. A A 1 2. ALL DEMOLISHED MATERIALS SHALL BECOME PROPERTY OF CONTRACTOR FOR PROPER DISPOSAL UNLESS OTHERWISE NOTED. 3. GC TO VERIFY LOCATION OF EXISTING STRUCTURAL COLUMNS BEFORE DEMOLITION BEGINS. PROTECT ALL STRUCTURAL COLUMNS DURING DEMOLITION 4. REMOVE ALL TEMPERATURE CONTROLS AND ALL ASSOCIATED WIRING. 5. ALL EXISTING CONSTRUCTION SHOWN IS BASED ON LIMITED EXISTING CONSTRUCTION DOCUMENTS AND CAN BE USED FOR BIDDING PURPOSES. THE GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING SITE CONDITIONS, REVIEW ALL DRAWINGS, AND VERIFY ALL DIMENSIONS, ELEVATIONS, AND MEMBER SIZES PRIOR TO THE START OF DEMOLITION WORK. THE CONTRACTOR SHALL NOTIFY THE PROFESSIONAL-OF-RECORD IN WRITING OF ALL DISCREPANCIES AND EXCEPTIONS BEFORE PROCEEDING WITH THE WORK. 6. THE GENERAL CONTRACTOR SHALL DESIGN, PROVIDE, AND INSTALL ALL TEMPORARY SHORING, AS REQUIRED, PRIOR TO THE START OF ANY DEMOLITION WORK. 7. THE REMOVAL, CUTTING, DRILLING, ETC. OF EXISTING CONSTRUCTION SHALL BE PERFORMED WITH GREAT CARE IN ORDER NOT TO JEOPARDIZE THE STRUCTURAL INTEGRITY OF ANY EXISTING CONSTRUCTION. IF STRUCTURAL MEMBERS, MECHANICAL, ELECTRICAL, OR ARCHITECTURAL FEATURES NOT INDICATED FOR REMOVAL INTERFERE WITH THE NEW WORK, THE PROFESSIONAL- OF-RECORD SHALL BE IMMEDIATELY NOTIFIED AND PRIOR WRITTEN APPROVAL SHALL BE OBTAINED BEFORE THE REMOVAL OR MODIFICATION OF ANY STRUCTURAL MEMBERS. 1 38'-0" 6'-4" 6'-0" 2 REMOVE ALL EXISTING SITE CONSTRUCTION AND DELETERIOUS MATERIALS UNLESS OTHERWISE NOTED. 14'-8" 8. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD IMPOSED UPON THE EXISTING STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN CAPACITY OF THE EXISTING FRAMING AT THE TIME THE LOADS ARE IMPOSED. 9. THE GENERAL CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD. 10. THE GENERAL CONTRACTOR SHALL PROMPTLY REPAIR DAMAGE CAUSED DURING CONSTRUCTION WITH SIMILAR MATERIALS AND WORKMANSHIP. 11. THE GENERAL CONTRACTOR SHALL PROVIDE ADEQUATE SITE AND BUILDING BARRIERS AS REQUIRED TO PROTECT THE SAFETY AND WELFARE OF WORKERS AND PUBLIC DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION. 2 DISTRIBUTIONS: OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. PORTION OF EXISTING INTERIOR WALL TO BE REMOVED FOR INSTALLATION OF NEW IMPACT DOORS. PROTECT EXISTING STRUCTURAL COLUMNS DURING DEMOLITION. EXISTING EXTERIOR WALL OPENING TO BE WIDENED FOR INSTALLATION OF NEW DELIVERY DOORS. COORDINATE EXACT LOCATION WITH OWNER REPRESENTATIVE TO AVOID POSSIBLE EXISTING STRUCTURAL COLUMN INSIDE OF EXISTING EXTERIOR WALL. REFER TO SHEET A2.2 FOR MORE INFORMATION. 3 EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED COMPLETE. 3 LANDLORD SHALL REMOVE PREVIOUS TENANT'S FIXTURES, FLOOR COVERING, INVENTORY, TRASH & DEBRIS AND DELIVERY A SPACE THAT IS IN BROOM CLEAN CONDITION TO TENANT. GC TO PREPARE FLOOR SURFACE FOR NEW FINISH, SEE FINISH SCHEDULE FOR FURTHER INFORMATION. EXISTING SUSPENDED CEILING TILE AND GRID TO BE REMOVED COMPLETE. PATCH AND REPAIR DAMAGED WALL SURFACES TO LIKE NEW CONDITION TO RECEIVE NEW FINISHES. SEE FINISH SCHEDULE FOR FURTHER INFORMATION. PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 DEMOLITION KEYED NOTES: ALL EXISTING LIGHTING TO BE REMOVED COMPLETE UNLESS NOTED OTHERWISE. REMOVE AND PROPERLY DISPOSE OF EXISTING PLUMBING PIPING FROM PREVIOUSLY REMOVED FIXTURES. REMOVE ALL SANITARY PIPING ABOVE SLAB AND CAP SANITARY LINES FLUSH AT SLAB ELEVATION. REMOVE ALL VENT PIPING UP TO VENT THRU ROOF. CAP VENT THRU ROOF FOR POSSIBLE FUTURE USE. REMOVE ALL WATER PIPING BACK TO THE MAIN DOMESTIC WATER LINE. MAIN WATER SUPPLY SHALL BE CAPPED FOR FUTURE USE. 4 REMOVE AND PROPERLY DISPOSE OF ALL SUPPLY AND RETURN DUCTWORK WITHIN THE SPACE, FROM THE DROPS. THIS SHALL INCLUDE ALL MAIN AND BRANCH DUCT, FLEX DUCTS, AIR DEVICES AND ALL ASSOCIATED HANGERS AND SUPPORTS. 4 PATCH WALL OPENING FROM PREVIOUSLY REMOVED EXHAUST SYSTEM AIR- AND WATER-TIGHT WITH LIKE MATERIALS. FIELD VERIFY EXACT LOCATION. GC TO FIELD VERIFY EXISTING CANOPY LIGHTING. REUSE, REPAIR OR REPLACE AS REQUIRED. TYPICAL. EXISTING INSULATED PANELS IN STOREFRONT TO BE REMOVED COMPLETE. PATCH AND REPAIR ADJACENT SURFACES TO LIKE NEW CONDITION FOR INSTALLATION OF NEW STOREFRONT GLASS. REFER TO ELEVATIONS FOR MORE INFORMATION. 5 DEMOLITION FLOOR PLAN D1 SCALE: 1/8" = 1'-0" DEMOLITION SHORING NOTE: 1. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS AND METHODS OF ALL DEMOLITION WORK AND FOR PROVIDING ALL NECESSARY TEMPORARY SHORING, BRACING, AND PROTECTION AS NECESSARY FOR THE SAFETY, STABILITY, AND PROTECTION OF ALL BUILDING ELEMENTS AND STRUCTURE DURING CONSTRUCTION AND DEMOLITION. ALL TEMPORARY SHORING AND BRACING SHALL BE ADEQUATE TO RESIST ALL APPLIED LOADS INCLUDING DEAD LOADS, LIVE LOADS, SNOW LOADS, AND CONSTRUCTION LOADS TO PROVIDE STRUCTURAL STABILITY, AND TO PROVIDE FOR RESISTANCE TO WIND AND SEISMIC FORCES UNTIL ANY REQUIRED MODIFICATIONS TO THE STRUCTURE ARE COMPLETE. 8 DEMOLITION CEILING PLAN D1 SCALE: ______________________________________________________________________ SYMBOLS LEGEND EXISTING ITEMS TO BE REMOVED EXISTING ITEMS TO REMAIN 1/8" = 1'-0" 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 6 ___________________________________________________________________ PROJECT: 5 SPECIAL HAZARDOUS MATERIALS NOTE: 1. IF THIS PROJECT IS FOUND TO CONTAIN HAZARDOUS MATERIALS, CONTRACTOR IS TO PROVIDE IMMEDIATE NOTICE TO LL AND/OR OWNER FOR DIRECTION FOR PROPER HANDLING, REMOVAL AND DISPOSAL. 2. HAZARDOUS MATERIAL SURVEY NOT A PART OF ARCHITECTS SCOPE. VERIFY WITH PROPERTY OWNER. DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 D1 SHEET 1 OF 1 PROPOSED EXISTING A. B. M 3 5/8" (20 GA.) METAL STUDS AT EACH VERTICAL STUD. DEFLECTION CHANNELATTACH WITH (2) #10 TEK SCREWS EACH HORIZ. STUD PARALLEL TO JOISTS (2) #10 TEK SCREWS INTO JOIST (TYP.) KICKER ATTACHMENT DEFLECTION CHANNEL PARALLEL TO JOISTS ATTACH WITH (2) #10 SCREWS AT EACH JOIST 362T150-33 TRACK. ATTACH TO BOTTOM CHORD OF TRUSS W/ <6" (2) #10 TEK SCREWS EX'G EX'G 27'-1 1/2" PARTS AREA "C" 103 8'-0" CLEAR S43 TYP. 3 5/8" 4'-9 5/8" PROPOSED 20" 3 PROPOSED 58'-9 5/8" PARTS AREA "A" 100 S46 A1.1 S46 S44 (ABOVE) BOTTOM CHORD OF EXIST. STEEL JOIST EX'G S46 S44 (ABOVE) 3 5/8" 20" S41 EX'G1 20" S44 (ABOVE) S44 (ABOVE) S42 TYP. BOTTOM CHORD OF EXIST. STEEL JOIST KICKER: 3 5/8" (20 GA.) METAL STUDS @ 5'-0" O.C. MAX. 3 5/8" (20 GA.) METAL STUDS CONT. W/ (2) #10 TEK SCREW AT EACH STUD. 5 6 3 5/8" (25 GA) MTL RUNNER SECURED WITH HILTI X-U UNIVERSAL FASTENER (ICC ER 2269) W/ 1" EMBEDMENT @ 48" O.C., CONNECT MTL STUD W/ #10 TEK SCREW EACH SIDE FLOOR PLAN A1.1 SCALE: 1/8" = 1'-0" WALL TRIM: 1X4 WALL TRIM, PAINT TO MATCH WALL. TOP OF TRIM TO ALIGN WITH TOP OF NEW WALL. SEE 9/A1.2 FOR ADDITIONAL INFORMATION. EXISTING WALL: EXISTING WALL BETWEEN RECEIVING AND PARTS AREAS TO REMAIN. GC TO ENSURE A VAPOR BARRIER EXISTS ON THIS WALL, PROVIDE AND INSTALL IF REQUIRED. <6" 111'-10" LAY-IN-CLG 16 GA. CLIP ANGLE. ATTACH TO TRACK W/ (4) #10 SCREWS. KICKER ATTACHMENT PERPENDICULAR TO JOISTS ACOUSTICAL TILE CEILING IN PARTS AREA 'A' 100 EXISTING ______________________________________ EXISTING STEEL COLUMN: EXISTING STEEL COLUMN TO REMAIN. GC TO PAINT "O'REILLY GREEN" IN SHOWROOM ONLY. (4) #10 TEK SCREWS. 'J' EDGE (4) #10 TEK SCREWS PROPOSED Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. NEW STEEL STRONGBACK: ( REFER TO SHEET A2.2 ) 362T150-33 TRACK. ATTACH TO BOTTOM CHORD OF TRUSS W/ (2) #10 TEK SCREWS 3 5/8" (20 GA.) METAL STUDS @ MID SPAN OF KICKER ABOVE SHOWROOM CORNER BOX OUT : GC TO INSTALL PLYWOOD BACKING TO EACH FACE FROM 8'-0" TO 10'-0" A.F.F. FOR INSTALLATION OF SECURITY MIRRORS. William Bandle Jr. License #4914 Exp. Date: 06/30/13 KICKER ATTACHMENT PARALLEL TO JOISTS S46 S44 (ABOVE) ABOVE GROUND FLOOR SAFE : OWNER FURNISHED AND CONTRACTOR INSTALLED. INTERNATIONAL SYMBOL OF ACCESSIBILITY: G.C. TO INSTALL INTERNATIONAL SYMBOL OF ACCESSIBILITY AT MAIN ENTRANCE. REFER TO 4/A4. TOP CHORD OF EXIST. STEEL JOIST (1) #10 TEK SCREWS INTO EACH JOIST (TYP.) DEFLECTION CHANNEL ATTACH WITH (2) #10 TEK SCREWS AT EACH JOIST S46 MOP SINK: ( REFER TO M.E.P. PLANS ) TACTILE EXIT SIGNAGE: G.C. TO INSTALL TACTILE EXIT SIGNAGE. REFER TO 4/A4. 1/2" = 1'-0" DEFLECTION CHANNELATTACH WITH (2) #10 TEK SCREWS EACH HORIZ. STUD (2) #10 TEK SCREWS PARALLEL TO JOISTS INTO JOIST (TYP.) 14'-7 5/8" NEW RESTROOMS: NEW RESTROOM FIXTURES AND ACCESSORIES. SEE SHEET A4 FOR MORE INFORMATION. NEW TELEPHONE BOARD: ( REFER TO M.E.P. PLANS ) 3 5/8" (20 GA.) METAL STUDS AT EACH VERTICAL STUD. S46 EX'G1 8'-2" 30" 24" 30" 24" 30" 24" 53'-0" KEYED NOTES: NEW ELECTRICAL EQUIPMENT: ( REFER TO M.E.P. PLANS ) 106'-10" B.O. HEADER SCALE: REFER TO M.E.P. DRAWINGS FOR ADDITIONAL REQUIREMENTS. NEW WALL INFILL: G.C. TO INFILL EXISTING WALL OPENING TO MATCH ADJACENT WALL CONSTRUCTION. ______________________________________________________________ S44 (ABOVE) 02/21/13 EXISTING STOREFRONT: EXISTING ALUMINUM & GLASS STOREFRONT SYSTEM TO REMAIN. 19 HEADER WALL SECTION S44 (ABOVE) EX'G 4 (2) 800S162-33 METAL STUD BOX HEADER CONT. SEE DTL 10/A1.2. NOTE: USE (2) 800S162-43 FOR SPANS OVER 10'-0". PERPENDICULAR TO JOISTS 7'-0" EX'G1 3 5/8" 24" 30" 24" 30" 24" 30" TYP. PERMIT/BID EXISTING DOOR: EXISTING DOOR TO REMAIN. REPLACE EXISTING CORE WITH SCHLAGE 20-068 x US26D-E (VERIFY WITH EXISTING DOOR.) 5/8" GWB BOTH SIDES (2) 2X FIRE TREATED CONTINUOUS BLOCKING 02/08/13 FIRE EXTINGUISHER: FIRE EXTINGUISHER IS TO BE MULTIPURPOSE DRY CHEMICAL TYPE, UL LISTED ABC, 10 LBS. CAPACITY, SURFACE MOUNTED WITH MANUFACTURER'S STANDARD METAL BRACKETS AND FASTENERS AT 42" ABOVE FINISHED FLOOR. VERIFY EXACT LOCATIONS WITH PROJECT ADMINISTRATOR. 111'-10" LAY-IN-CLG HEADER WALL: 3 5/8" (20 GA.) MTL. STUDS @ 24" O.C. PARTS AREA "B" 101 18'-4 1/4" ACOUSTICAL TILE CEILING IN PARTS AREA 'A' 100 (4) #10 TEK SCREWS S44 (ABOVE) 16'-4" 32'-11 3/4" OFFICE 102 KICKER ATTACHMENT PERPENDICULAR TO JOISTS 6" S41 S42 TYP. S43 S43 ABOVE S44 (ABOVE) EX'G 16 GA. CLIP ANGLE. ATTACH TO TRACK W/ (4) #10 SCREWS. 3 5/8" (20 GA.) METAL STUDS CONT. W/ (2) #10 TEK SCREW AT EACH STUD. C. OWNER REVIEW REFER TO SHEET F1 FOR INTERIOR FINISH REQUIREMENTS AND OWNER FURNISHED AND INSTALLED FIXTURES AND EQUIPMENT. HI-LOW DRINKING FOUNTAIN: ( REFER TO M.E.P. PLANS ) (4) #10 TEK SCREWS. KICKER: 3 5/8" (20 GA.) METAL STUDS @ 5'-0" O.C. MAX. S43 2 BOTTOM CHORD OF EXIST. STEEL JOIST 3 5/8" (20 GA.) METAL STUDS @ MID SPAN OF KICKER 9'-0" CLEAR MEN'S TOILET RM. 104 EX'G 68'-0 5/8" WOMEN'S TOILET RM. 105 EX'G 11'-8" EX'G 6" 1 ALL DIMENSIONS TO ROUGH FACE OF ROUGH FRAMING, CONCRETE OR CENTERLINE OF STRUCTURE, UNLESS OTHERWISE NOTED. DISTRIBUTIONS: 3 5/8" (20 GA.) MTL. STUDS 5/8" GWB BOTH SIDES SEALED CONCRETE PROJECT: A GENERAL NOTES: TOP CHORD OF EXIST. STEEL JOIST (1) #10 TEK SCREWS INTO EACH JOIST (TYP.) PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 BOTTOM CHORD OF EXIST. STEEL JOIST POLISHED CONCRETE PARTS AREA 'A' 9 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 PERPENDICULAR TO JOISTS INTERIOR WALL SECTION _________________________________________________________________ A1.1 5/8" TYPE 'X' GWB EACH SIDE. TO ROOF DECK ON PARTS AREA 'B' & 'C' SIDE. TO 6" ABOVE FINISH CEILING ON PARTS AREA 'A' SIDE. 3-5/8" (25 GA.) MTL. STUDS AT 24" O.C. TO 12" ABOVE FINISH CEILING 3-5/8" (20 GA.) MTL. STUDS AT 24" O.C. TO STRUCTURE ABOVE S42 S46 1 WALL TYPES ______________________________________ A1.1 SCALE: 1 1/2" = 1'-0" S43 5/8" TYPE 'X' GWB EACH SIDE. TO ROOF DECK ON PARTS AREA 'B' & 'C'. TO 6" ABOVE FINISH CEILING ON PARTS AREA 'A'. 3/4" LATTICE TRIM PEGBOARD OVER 1/2" WD. BLOCKING @ 16" O.C. 6'-10" A.F.F. S41 3-5/8" (20 GA.) MTL. STUDS AT 24" O.C. TO STRUCTURE ABOVE. 5/8" TYPE 'X' GWB EACH SIDE. TO ROOF DECK ON PARTS AREA 'B' & 'C'. TO 6" ABOVE FINISH CEILING ON PARTS AREA 'A'. 5/8" TYPE 'X' GWB EACH SIDE 3-5/8" (20 GA.) MTL. STUDS (6" AT RESTROOM PLUMBING WALL) AT 24" O.C. T0 8'-6" A.F.F. 3 1/2" UNFACED BATT. SOUND INSULATION 3-5/8" (20 GA.) MTL. STUDS AT 24" O.C. TO STRUCTURE ABOVE. DBL. 3 5/8" (20 GA.) MTL. STUDS @ C.J. AS SHOWN. 111'-10" LAY-IN-CLG S44 NOTES: 1. REFER TO 9/A1.1 FOR TYPICAL SECURING OF BASE OF NEW WALL CONSTRUCTION. 2. REFER TO 10/A1.2 FOR TYPICAL HEADER & JAMB STUD CONSTRUCTION AT NEW INTERIOR WALLS. 3. PROVIDE FIRE STOPPING AND FIRE SEALANT MATERIALS AS REQUIRED AT ALL RATED WALL CONSTRUCTION MATERIAL TRANSITIONS AND PENETRATIONS. RATING TO BE EQUAL TO RATED WALL ASSEMBLY. 4. PROVIDE DIAGONAL BACKING BRACING ( 3" X 16 GA. FLAT STRIP ) AT CORNER FACES OF FREE STANDING PARTITION SYSTEMS. 5. PROVIDE MOISTURE RESISTANT TYPE 'X' GYPSUM BOARD IN TOILET ROOMS, BEHIND MOP SINK AND BEHIND DRINKING FOUNTAIN. 6. PROVIDE 'J' MOLDING REGLETS OR CORNER BEAD AT ALL DISSIMILAR WALL MATERIAL TRANSITIONS. 7. INSULATION SHALL HAVE A FLAME SPREAD RATING OF 0-25 AND A SMOKE DEVELOPMENT RATING OF 0-450. 1/2" = 1'-0" 'J' EDGE 6" 5/8" TYPE 'X' GWB ON (1) SIDE TO 6" ABOVE FINISH CEILING. SCALE: ACOUSTICAL TILE CEILING IN PARTS AREA 'A' 100 1/4" X 7/16" (1) PIECE VEE-SHAPED SLOT CONTROL JOINT @ BOTH SIDES OF HEADER 5/8" GWB EXISTING WALL 4" VINYL BASE FINISH FLOOR EX'G1 DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 GWB 4 CONTROL JOINT ______________________________________________ A1.1 SCALE: 1 1/2" = 1'-0" SHEET 1 OF 6 DISTRIBUTIONS: OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 A 1 OPEN TO STRUCTURE ABOVE William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. WOMEN'S TOILET RM. 105 OPEN TO STRUCTURE ABOVE CLNG HT 108'-6" PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 OFFICE 102 CLNG HT 108'-6" 3 OPEN TO STRUCTURE ABOVE PARTS AREA "A" 100 (1) 362T150-33 EACH SIDE. FULL HT. (1) 362T150-33 EACH SIDE. FULL HT. (2) 362S162-33 STUDS. FULL HT. 8" LONG SECTION OF 20 GA. RUNNER TRACK (WIDTH TO MATCH EXISTING STUDS) SCREW ATTACHED TO FULL HEIGHT STUD W/(6)#10-16 SCREWS AND TO HEADER W/(3)#10-16 SCREWS EACH FLANGE. SECTION A-A CLNG HT 111'-10" NOTE: CRIPPLE STUDS, AND THEIR BOTTOM TRACK ABOVE HEADER OVER OPENING, NOT SHOWN FOR CLARITY. (2) 362S162-33 STUDS FACE TO FACE. FULL HT. 4 CORNER POST HEADER ATTACHMENT (2) 20 GA. (U.N.O.) JAMB STUDS FACE TO BACK FULL HT. (WIDTH TO MATCH EXIST. STUDS) FASTEN W/#10 SCREWS EA. FLANGE AT 12"O.C. TOP TRACK ATTACH TOP AND BOTTOM TRACK USING: (2)#10-16 SCREWS AT 16"O.C. (2) 800S200-33 CONT. W/ (1) 362T150-33 CONT. TOP AND BOTTOM. USE (2) 800S200-43 CONT. W/ (1) 362T150-33 CONT. TOP AND BOTTOM WHEN SPAN IS GREATER THAN 10'-0" BOTTOM TRACK HEADER ATTACHMENT. SEE HEADER ATTACHMENT DETAIL ABOVE 14 CORNER POST DETAIL ___________________________________________________________ A1.2 SCALE: 1 1/2" = 1'-0" PARTS AREA "B" 101 6" (20 GA.) METAL JOISTS @ 24" O.C. ALIGN W/ WALL STUDS BELOW. CORNER BEAD (1) LAYER OF 5/8" TYPE 'X' GWB EA. SIDE. R-19 UNFACED BATT INSULATION 109'-0" T.O.W. 5 G.C. TO FIELD VERIFY EXISTING CANOPY LIGHTING. REUSE, REPAIR, OR REPLACE AS REQUIRED. REFER TO ELECTRICAL DRAWINGS FOR MORE INFO 1X4 WOOD TRIM (PAINT GRADE PINE) ATTACHED TO METAL STUD FRAMING WITH TECH 12 SCREWS AT 24" O.C. SET FLUSH. PAINT EXPOSED SURFACES TO MATCH WALL FINISH. 2"x 2"x 16GA. CLIP ANGLE, 1/2" LESS THAN STUD WIDTH. USE: (3)#10-16 SCREWS ON EACH LEG AS SHOWN BELOW. JAMB STUD ATTACHED W/ (1) 20 GA. (U.N.O.) JAMB STUD TRACK (WIDTH TO MATCH EXISTING STUDS) FROM FLOOR TO BOTTOM OF HEADER. ATTACH JAMB STUD TO TRACK W/(1)#10-16 SCREW AT 16"O.C. ON EACH LEG AND (2)#10-16 SCREWS INTO WEBS. WALL TRACK SECURED TO FLOOR W/ 1/4" TAPCON SCREWS AT 4'-0"O.C. REFER TO FLOOR PLAN FOR WALL TYPES. NOTE: 18 GA METAL FRAMING TO BE USED AT ALL EXTERIOR OPENINGS. PROVIDE MOISTURE RESISTANT GWB @ ALL WET LOCATIONS. 6 REFLECTED CEILING PLAN ____________________________________________________________________ A1.2 SCALE: 1/8" = 1'-0" INSULATION: REPLACE EXISTING INSULATION AS NEEDED: RETRO-FIT INSULATION: EXISTING STRUCTURAL ROOF SYSTEMS 6" FACED BLANKET INSULATION (R-19) INSTALLED BETWEEN STRUCTURAL SYSTEM. SUPPORT WITH WHITE METAL "C" CHANNEL THE WIDTH OF THE SPACE ON 24" CENTERS. WIRE TO CHORD OF JOIST OR EQUAL INSTALLATION. INSULATION FOR SUSPENDED ACOUSTIC CEILING : 6" BATT INSULATION INSTALLED ON TOP OF EXISTING AND OR NEW ACOUSTIC CEILING TILES G.C. SHOULD CONTACT PROJECT ADMINISTRATOR WITH QUESTIONS. (SEE COVER SHEET FOR CONTACT INFORMATION) 9 WALL / CLG. SECTION _________________________________________________________ A1.2 SCALE: 1 1/2" = 1'-0" HEADER 10 ATTACHMENT DETAIL _________________________________________________________ A1.2 SCALE: 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 2 MEN'S TOILET RM. 104 PROJECT: CLNG HT 108'-6" PARTS AREA "C" 103 1 1/2" - 1'-0" GENERAL NOTES: 1. SEE FINISH PLAN FOR ALL FINISHES. 2. SEE ELECTRICAL DRAWINGS FOR ALL ELECTRICAL INFORMATION. 3. SEE MECHANICAL DRAWINGS FOR ALL HVAC INFORMATION. DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 SHEET 2 OF 6 DOOR SCHEDULE EXISTING CMU WALL CONSTRUCTION ANCHOR PER MFR. RECOMMENDATIONS NEW 8" CMU JAMB UNIT W/ (2) #6 VERTICAL (W/ #5 DOWELS EPOXY GROUT INTO EXISTING FOUNDATION WALL 6" EMBEDMENT) GROUT CELL SOLID 21 HEAD 22 JAMB ___________________________ MATERIAL 1A EXISTING EX'G REFER TO FLOOR PLAN 1B EXISTING EX'G 2 PAIR 3'-0" x 7'-0" x 1-3/4" KEYED TYPE MATERIAL HEAD JAMB EX'G 1 A EX'G EX'G EX'G EX'G REFER TO NOTE 2 REFER TO FLOOR PLAN EX'G 1 A EX'G EX'G EX'G EX'G REFER TO NOTE 2 BB REFER TO FLOOR PLAN HOLLOW METAL 2 A 2 HOLLOW METAL 21/A2.1 22/A2.1 REFER TO NOTE 1, 2, 3, 5 DOUBLE ACTING IMPACT DOOR, MFR. PRE-FINISHED 16/A2.1 17/A2.1 REFER TO NOTE 1 A2.1 SCALE: 3 PAIR 3'-0" x 6'-10" DD 4 3'-0" x 7'-0" x 1 3/4" C REFER TO FLOOR PLAN 5 3'-0" x 7'-0" x 1 3/4" C REFER TO FLOOR PLAN C REFER TO FLOOR PLAN 3'-0" x 7'-0" x 1 3/4" GLAZING 3 --- 1 HOLLOW METAL, MFR. PREFIN. SOLID WOOD 4 --- 2 HOLLOW METAL 11/A2.1 12/A2.1 REFER TO NOTE 1, 4 SOLID WOOD 5 --- 2 HOLLOW METAL 11/A2.1 12/A2.1 REFER TO NOTE 1, 4 2 HOLLOW METAL 12/A2.1 REFER TO NOTE 1, 4 REFER TO GLAZING SCHEDULE SOLID WOOD 5 --- FOR INTERIOR WALL CONST. REFER TO FLOOR PLAN AND WALL TYPES FOR INTERIOR WALL CONST. REFER TO FLOOR PLAN AND WALL SECTIONS 100 COURCHELLE DRIVE NICHOLASVILLE, KY 40356 CONTACT: PAM PEEL DOOR - SEE DOOR SCHEDULE HOLLOW METAL FRAME, REFER TO DOOR SCHEDULE FOR TYPE (RATED WHERE REQUIRED). 16 HEAD ___________________________ 17 JAMB ___________________________ 1 1/2" - 1'-0" A2.1 SCALE: FOR INTERIOR WALL CONST. REFER TO FLOOR PLAN AND WALL TYPES FOR INTERIOR WALL CONST. REFER TO FLOOR PLAN AND WALL SECTIONS BOX HEADER CONSISTING OF 2 - 6" (20 GA.) MTL. STUDS W/ 3 5/8" TRACK TOP AND BOTTOM. SEE 10/A1.2. DOUBLE STUDS AT JAMBS. SEE 10/A1.2. PART DESCRIPTION MANUFACTURER 1 CYLINDER 20-062 X US26D - "E" KEYWAY (REMOVABLE CORE) KEYED EXTERIOR SIDE SCHLAGE 2 18 FRAME TYPES _________________________________________ A2.1 SCALE: 3" - 1'-0" 1 DEADBOLT MS1850S X US28 ADAMS RITE 1 DEADLOCK LEVER 4550 X US28 ADAMS RITE 1 STRIKE MS4002 X US28 ADAMS RITE 1 CLOSER 4040BC X AL ( ADJ. TO 5# ) LCN 1 PAIR OFFSET PIVOTS 195/188 X US26D RIXON 1 SET PUSH / PULLS CO-12/CPII X US26D KAWNEER 1 SET WEATHERSTRIP WOOL PILE, CONT., REPLACEABLE PEMKO 1 SWEEP RETRACTING RESILIENT SEAL TYPE PEMKO 1 THRESHOLD ANSI AND ADA COMPLIANT PEMKO SET NUMBER 2 ( DOOR MARK 2 ) SEALANT BOTH SIDES (TYP.) INSTALL 3 (MIN.) JAMB ANCHORS EACH JAMB. FRAME REINFORCING PER MFR'S RECOMMENDATIONS AT ALL HARDWARE LOCATIONS. 3 5/8" SEALANT BOTH SIDES (TYP.) HOLLOW METAL FRAME, REFER TO DOOR SCHEDULE FOR TYPE (RATED WHERE REQUIRED) DOOR - SEE DOOR SCHEDULE. DOOR - SEE DOOR SCHEDULE. HOLLOW METAL FRAME, REFER TO DOOR SCHEDULE FOR TYPE (RATED WHERE REQUIRED) 4" 11 HEAD 12 JAMB ___________________________ SCALE: WELDED HOLLOW METAL FRAME (16 GA.) W/ (3) MIN. ANCHORS PER JAMB (REFER TO GENERAL FINISH NOTES THIS SHEET FOR COLORS) 1 1 1/2" - 1'-0" NO. REQUIRED HARDWARE FURNISHED WITH STOREFRONT DOOR SYSTEM PREFINISHED HOLLOW METAL FRAME BY MFR. WHERE WALL OCCURS A2.1 SCALE: GENERAL FINISH NOTES FOR INTERIOR DOORS & FRAMES: A. WOOD DOORS SHALL BE CUSTOM GRADE ROTARY SLICED NATURAL BIRCH WITH FACTORY PREFINISH. FINISH SHALL BE EQUAL TO GRAHAM #300-MEDIUM BROWN. ANY VARIANCE MUST BE APPROVED BY O'REILLY AUTO PARTS. B. INTERIOR HOLLOW METAL FRAMES SHALL BE SHOP PRIMED AND FIELD PAINTED WITH 2 COATS SEMI-GLOSS ENAMEL GLIDDEN "O'REILLY GREEN". 1 1/2" - 1'-0" NO. PART DESCRIPTION MANUFACTURER 3 PAIR HINGES ECBB1100 - 4.5" X 4.5" - NRP, US26D HAGER 2 EXIT DEVICE 9400 B 426 / 439 / 689 - PRT03 630 THRU-BOLTED ITEM W / SEX BOLTS DORMA 1 RIM CYLINDER 20-057 RIM CYLINDER IC, W/ SCHLAGE E KEYWAY (LARGE FORMAT) - 26D - W/ 2 SECURITY KEYS AND 1 CORE KEY PER LOCK, 1 BITTED SCHLAGE 2 CLOSER 8616DST HD GR 1, ADJ #3 x 689 FINISH W/COVER THRU-BOLTED ITEM W/SEX BOLT INCLUDES HOLD OPEN ARM W/ THUMBTURN DORMA 1 LATCHGUARD LG100Z/SF W/PIN W/ SEX BOLTS LATCHGUARD 2 KICKPLATE 8 X 34 X .050 SS FINISH HAGER 1 THRESHOLD 60" ALUM MILL ADA COMPLIANT POSTEL 2 SWEEP CONCEALED ALUM MILLVINYL BULB POSTEL 1 SET WEATHERSTRIP JAMBS: KERFED QEBD-550 HEADER: ADHESIVE QDST-675 SCHLEGEL 1 DOOR VIEWER 698B-190 DEGREE WIDE ANGLE - 26D IVES SET NUMBER 3 ( DOOR MARK 3 ) NO. PART DESCRIPTION MANUFACTURER ALL DOOR HARDWARE TO BE FURNISHED BY THE DOUBLE-ACTING IMPACT DOOR MANUFACTURER AND INSTALLED BY THE CONTRACTOR. SET NUMBER 4 ( DOOR MARK 4 ) NO. PART DESCRIPTION MANUFACTURER 1 OFFICE LOCK SET AU5307LN X US26D YALE 1 WALL BUMPER 409 X US26D ROCKWOOD 1.5 PAIR HINGES BB1279 X 4.5 X 4.5 X US26D HAGAR SET NUMBER 5 ( DOOR MARK 5 AND 6 ) GLAZING SCHEDULE 1 =1" INSULATED SAFETY GLAZING ( 1/4" GREEN ( SOLEXIA ) EXTERIOR PANE ) ( 1/4" CLEAR INTERIOR PANE ) SHADING COEFFICIENT .57 4'-8 3/4" 4'-9 3/8" 1 4'-7 7/8" 1 A 1 STOREFRONT ELEVATIONS ____________________________________________________________________ A2.1 SCALE: 1/4" = 1'-0" CAUSING BUCKLING, STRESSING ON GLASS, FLAURE OF JOINT SEALS,UNDUE STRESS ON STRUCTURAL ELEMENTS, DAMAGING LOADS ON FASTENERS, REDUCTION OF PERFORMANCE, OR OTHER DETRIMENTAL EFFECTS. OPERATING DOORS AND WINDOWS SHALL FUNCTION NORMALLY OVER THIS TEMPERATURE RANGE. TEST PROCEDURES AND PERFORMANCE: AIR INFILTRATION: TEST UNITS IN ACCORDANCE WITH ASTM E 283 AT STATIC AIR PRESSURE DIFFERENCE OF 6.24 PSI. AIR INFILTRATION SHALL NOT EXCEED 0.06 CMF/FT MAXIMUM PER SQUARE FOOT OF FIXED WALL AREA. 2. WATER RESISTANCE: a. TEST UNITS IN ACCORDANCE WITH ASTM E 331. b. THERE SHALL BE NO WATER LEAKAGE AT A STATIC PRESSURE OF 12.0 PSF. 3. UNIFORM LOAD DEFLECTION: a. TEST UNITS IN ACCORDANCE WITH ASTM E 330. b. DESIGN AND SIZE MEMBERS TO WITHSTAND NOT LESS THAN 30 PSF MINIMUM POSITIVE AND NEGATIVE DESIGN WIND PRESSURE NORMAL TO THE PLANE OF THE WALL, UNLESS GREATER LOADS ARE REQUIRED BY LOCAL CODE REQUIREMENTS. C. DEFLECTION UNDER DESIGN LOAD SHALL NOT EXCEED L/175 OF THE CLEAR SPAN. 4. STRUCTURAL UNIFORM LOAD: a. TEST UNITS IN ACCORDANCE WITH ASTM E 330 AT NOT LESS 1.5 TIME THE DESIGN WIND PRESSURE SPECIFIED (MINIMUM 60 PSF). b. AT CONCLUSION OF THE TEST, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS, STOREFRONT PARTS, OR ANY OTHER DAMAGE THAT WOULD CAUSE THE STOREFRONT TO BE DEFECTIVE. 5. CONDENSATION RESISTANCE FACTOR: a. TEST UNITS IN ACCORDANCE WITH ASTM 1503.1. b. CONDENSATION RESISTANCE FACTOR (CRF) SHALL NOT BE LESS THAN 59. 6. THERMAL TRANSMITTANCE: a. TEST UNITS IN ACCORDANCE WITH ASTM 1503.1. b. CONDUCTIVE THERMAL TRANSMITTANCE (U-VALUE) SHALL NOT BE LESS THAN 0.63 BTU/HR/DEGREE F/SF. PART 2 - PRODUCTS 2.01 MATERIAL A. GLAZING: MEETING REQUIREMENTS OF SECTION 08 80 00 AND AS SCHEDULED ON DRAWINGS. B. MANUFACTURERS: EFCO "S-403" SPECIFIED. APPROVED EQUALS: KAWNEER "TRIFAB 451T" AND VISTAWALL "FG-3000-S. C. ALUMINUM ENTRANCES AND STOREFRONT: 1. FRAMING: a. SIZE: 2"x 4 1/2", HEAVY DUTY MULLION EFCO SERIES 9314/9323, Ixx=8.207. b. ALUMINUM: 6063 T5 OR T6 ALLOY AND TEMPERED, MEETING REQUIREMENTS OF ASTM B 221, ALLOY GS 10A-T5. c. CONSTRUCTION: THERMAL BROKEN WITH SCREW SPLINE CONNECTIONS PER MANUFACTURERS STANDARDS. d. GLAZING STOPS: SNAP IN TYPE WITH "DRY" EDPM GASKETS ON BOTH EXTERIOR AND INTERIOR. UNITS SHALL BE 1-INCH INSULATED DOUBLE GLAZED CONSISTING OF 1/4-INCH EXTERIOR PANE, 1/2-INCH AIR SPACE, 1/4-INCH INTERIOR PANE INSTALL FROM EXTERIOR SIDE. William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. NO. PART DESCRIPTION MANUFACTURER 1.5 PAIR HINGES BB1279 X 4.5 X 4.5 US26D HAGAR 1 PRIVACY LOCKSET AU5302LN X US26D YALE 1 WALL BUMPER 409 X US26D AT DOOR NUMBER 6 ROCKWOOD 1 FLOOR STOP 440 X US26D AT DOOR NUMBER 5 ( MOUNT AS CLOSE TO CORNER AS POSSIBLE) ROCKWOOD FASTENERS: ALUMINUM OR NON-MAGNETIC STAINLESS STEEL. CONCEALED FASTENERS SHALL BE CADMIUM OR ZINC-PLATED STEEL. 2. DOOR TYPE: a. SIZE: AS SCHEDULED. EFCO SERIES NUMBER D300. b. ALUMINUM: 6063 T5 OR T6 ALLOY AND TEMPERED, MEETING REQUIREMENTS OF ASTM B 221, ALLOY GS 10A-T5. c. STILES AND TOP RAILS: 3-1/2"x 1-3/4"x 0.125" THICK, PLUS OR MINUS 0.005, GLAZING STOP SECTION 0.050" WALL THICKNESS. d. BOTTOM RAIL: 10" MINIMUM x 1-3/4"x 0.125" THICK, PLUS OR MINUS 0.005, GLAZING STOP SECTION 0.050" WALL THICKNESS. e. CONSTRUCTION: MANUFACTURERS STANDARD. f. GLAZING STOPS: SNAP IN TYPE WITH "DRY" EDPM OR NEOPRENE BULB-TYPE GLAZING. UNITS SHALL BE DOUBLE GLAZED, 1-INCH INSULATED UNIT, FROM EXTERIOR SIDE. g. WEATHERSTRIPPING: NEOPRENE BULB TYPE, REPLACEABLE. 3. FINISH: ORGANIC, AA-M12-C42-R1X, KYNAR 500/HYLAR 5000 FLUROPON, IN ACCORDANCE WITH AAMA 605.2. COLOR AS SELCECTED FROM MANUFACTURERS STANDARDS AND SCHEDULED ON DRAWINGS. 4. DOOR HARDWARE: REFER TO DOOR HARDWARE SCHEDULE AND SECTION 08 71 00. D. AUXILLIARY MATERIALS: 1. PROVIDE ALL OTHER MATERIALS, NOT SPECIFICALLY DESCRIBED BUT REQUIRED FOR A COMPLETE, WEATHERTIGHT, AND PROPER INSTALLATION OF DOORS AND FRAMING SYSTEMS, SUBJECT TO ACCEPTANCE BY THE ARCHITECT. a. DEFLECTION CHANNELS: AS RECOMMENDED BY SYSTEM MANUFACTURER. b. CONTINOUS SILL FLASHING SHEET METAL: 0.040-INCH THICK ALUMINUM SHEET, FINISH TO MATCH MULLION SECTIONS WHERE EXPOSED. c. COLUMN CLADDING SHEET METAL: 0.040-INCH THICK ALUMINUM SHEET, FINISH TO MATCH MULLION SECTIONS WHERE EXPOSED. d. THERMAL BARRIER: BARRIER MATERIAL SHALL BE POURED-IN-PLACE TWO PART POLYURETHANE. A NONSTRUCTURAL THERMAL BARRIER IS UNACCEPTABLE. PART 3 - EXECUTION 3.01 INSTALLATION A. TAKE FIELD MEASUREMENTS BEFORE FABRICATION WHERE POSSIBLE; DO NOT DELAY JOB PROGRESS. B. INSTALL MATERIAL AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. INSTALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM APPEARANCE. COORDINATE WITH WORK OF OTHER SECTIONS. C. ANCHOR SECURLY IN PLACE TO STRUCTURE; INSTALL PLUMB, LEVEL AND IN TRUE ALLIGNMENT. ISOLATE DISSIMILAR MATERIALS TO PREVENT CORROSION. D. COORDINATE WITH GLASS AND GLAZING WORK; INSTALL HARDWARE AND ADJUST FOR SMOOTH, PROPER OPERATION. E. SEAL FRAMES WITH AN APPROVED SEALANT, IN COMPLIANCE WITH SECTION 07 92 00, IN COLOR TO MATCH FRAMES. MAKE A NEAT, FULLY WEATHERPROOF JOB. F. CLEAN AND PROTECT COMPLETED SYSTEM; REPAIR DAMAGE. END OF SECTION COULTER & COMPANY 13711 E. 66TH ST. N. OWASSO, OK 74055 PHONE: (918) 272-4494 FAX: (918) 272-7908 EMAIL: [email protected] CONTACT: BRENDA OR KEN 4'-9 3/8" 1 PROVISIONS FOR THERMAL MOVEMENTS: SYSTEM PERFORMANCE TO PROVIDE FOR EXPANSION AND CONTRACTION WITHIN SYSTEM COMPONENTS CAUSED BY TEMPERATURE e. ___________________________ 1 1/2" - 1'-0" 1'-2 3/8" A2.1 5 3/4" INSTALL 3 (MIN.) JAMB ANCHORS EACH JAMB. FRAME REINFORCING PER MFR'S RECOMMENDATIONS. BY MFR. HOLLOW METAL FRAME, REFER TO DOOR SCHEDULE FOR TYPE (RATED WHERE REQUIRED). 3 5/8" SET NUMBER 1 ( DOOR MARK 1A & 1B ) 3 5/8" ANCHOR PER MFR. RECOMMENDATIONS A. b. HARDWARE SCHEDULE BY MFR. DOOR - SEE DOOR SCHEDULE 02/21/13 PROVIDE FIVE YEAR WARRANTY UNDER PROVISIONS OF GENERAL CONDITIONS INCLUDING COVERAGE FOR INSULATED GLASS UNITS. 1.04 TEST PROCEEDURES AND PERFORMANCE a. SEALANT BOTH SIDES (TYP.) 2" PERMIT/BID B. 1. PHONE 800-887-4307 EXT 133 FAX 859-881-5499 EMAIL: [email protected] DOUBLE STUDS AT JAMBS. SEE 10/A1.2. 02/08/13 1.03 QUALITY ASSURANCE A. COMPLY WITH GOVERNING CODES AND REGULATIONS. PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS, WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICES FOR THREE YEARS. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE AND STORE MATERIAL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. B. LOCKNET SEALANT BOTH SIDES (TYP.) A2.1 11/A2.1 NOTES: 1. ALL DOORS SHALL BE SHOP PREPARED FOR HARDWARE. 2. ALL EXTERIOR DOORS TO BE KEYED ALIKE. CONTRACTOR TO FIELD VERIFY AND MATCH CORE OF DOOR MARKED "1". 3. EXTERIOR DOOR, FRAME AND HARDWARE SUPPLIED BY OWNER, CONTRACTOR INSTALLED. 4. IT IS THE CONTRACTORS OPTION TO DIRECT ORDER AND PURCHASE INTERIOR DOORS, HOLLOW METAL FRAMES AND HARDWARE THROUGH LOCKNET. 5. FRAME FOR INDICATED DOOR TO HAVE A 4" HEAD. 1 1/2" - 1'-0" BOX HEADER CONSISTING OF (2) 6" (20 GA.) MTL. STUDS W/ 3 5/8" TRACK TOP AND BOTTOM. SEE 10/A1.2. SCALE: REMARKS SET # REFER TO FLOOR PLAN 6 ___________________________ 1 1/2" - 1'-0" 3 5/8" SWING SEALANT BOTH SIDES (TYP.) HOLLOW METAL FRAME, REFER DOOR SCHEDULE FOR TYPE SCALE: TYPE DETAILS OWNER REVIEW 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 HOLLOW METAL DOOR AND FRAME SYSTEM, REFER SCHEDULE FOR TYPE SEALANT BOTH SIDES (TYP.) A2.1 SIZE ( W x H x D ) ANCHOR PER MFG. RECOMMENDATIONS FRAME DISTRIBUTIONS: PROJECT: EXTERIOR MATCH EXISTING EXTERIOR PRE-FINISHED SHEET METAL (24 GA.) CLOSURE TRIM AND FLASHING. COLOR TO MATCH CMU. DOOR MK NEW STEEL LINTEL - W8 x 10 BEAR 8" MIN. EA. END. REFER TO DETAIL 16/A2.2 FOR ADDITIONAL INFORMATION. DOOR HARDWARE SECTION 08 41 13 ALUMINUM ENTRANCES AND STOREFRONTS PART 1 - GENERAL 1.01 SUMMARY A. PROVIDE ALUMINUM ENTRANCES AND STOREFRONTS. 1. EXTERIOR ENTRANCE DOORS. 2. FRAMES AND ENTRANCES. 3. STOREFRONT TYPE FRAMING SYSTEMS. 4. TRANSOMS. 5. SIDELIGHTS. 1.02 SUBMITTALS A. NONE REQUIRED UNLESS SUBMITTING FOR APPROVED EQUALS. PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 MATCH EXISTING 1 NOTE: NEW STOREFRONT GLASS TO MATCH EXISTING. FIELD VERIFY EXISTING COLOR, HEIGHT, GLAZING, AND FRAMING. STOREFRONT NOTES: 1. FIELD VERIFY FINAL ROUGH OPENING PRIOR TO FABRICATION. 2. REFER TO COVER SHEET FOR DESIGN CRITERIA. 3. IT IS THE CONTRACTORS OPTION TO DIRECT ORDER AND PURCHASE STOREFRONT AND GLASS FROM COULTER & COMPANY. 4. SECURITY SHUTTERS MAY BE REQUIRED ON THIS PROJECT. CONTACT YOUR PROJECT ADMINISTRATOR FOR VERIFICATION. 5. WHEN THE WIND SPEED IS EQUAL TO OR GREATER THAN 120 MPH, A STORM PANEL SYSTEM WILL BE OWNER FURNISHED AND INSTALLED ON THIS PROJECT. CONTACT YOUR PROJECT ADMINISTRATOR TO VERIFY/COORDINATE. ( NOT USED ) (INSULATED) FLUSH HOLLOW METAL (18 GA.) (REFER TO GENERAL FINISH NOTES ON THIS SHEET FOR FINISHES) AA BB 4 SOLID CORE WOOD DOOR (REFER TO GENERAL FINISH NOTES ON THIS SHEET FOR FINISHES) CC DOOR ELEVATIONS ___________________________________________________ A2.1 SCALE: 1/4" = 1'-0" MFR. PRE-FINISHED DOUBLE ACTING IMPACT DOORS NOTE: DASHED IN DOOR AND DOUBLE LETTER INDICATE PAIRED DOOR LOCATIONS DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 A2.1 SHEET 3 OF 6 SPECIAL INSPECTIONS 1. 1. TYPE, SIZE, AND EMBEDMENT OF ANCHOR/REINFORCING CONTINUOUS 2. ANCHOR/REINFORCING INSTALLATION PROCEDURES CONTINUOUS MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS 2. THE SPECIAL INSPECTION IDENTIFIED ON PLANS ARE, IN ADDITION TO , AND NOT A SUBSTITUTE FOR, THOSE INSPECTIONS REQUIRED TO BE PERFORMED BY A CITY'S BUILDING INSPECTOR. 3. THE SPECIAL INSPECTOR SHALL BE CERTIFIED BY THE LOCAL JURISDICTION, DEVELOPMENT SERVICES, IN THE CATEGORY OF WORK REQUIRED TO HAVE SPECIAL INSPECTION. 4. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR: 1/2" DRILL & ADHERE 4 1/2" INTO EXISTING SOLID GROUTED CMU W/ HILTI HIT-HY150 MAX ADHESIVE ANCHORING SYSTEM. GROUT CELLS SOLID A MINIMUM OF 24 HOURS PRIOR TO INSTALLING ANCHORS, WHERE VOID. 3/4" NON-SHRINK GROUT EXIST. CMU WALL NEW STEEL LINTEL-W8x10. 3/8" 3/8" 3/16 B. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE PROFESSIONAL OF RECORD, AND THE CONTRACTOR. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, SUBMIT A COMPLETE LIST OF ALL OUTSTANDING DISCREPANCIES ON A WEEKLY BASIS TO THE OWNER, THE BUILDING OFFICIAL, AND THE PROFESSIONAL-OF-RECORD, UNTIL ALL CORRECTIONS HAVE BEEN COMPLETED. REMOVE EXISTING MASONRY AND REBUILD WITH NEW MASONRY TOOTHED INTO EXISTING MASONRY 8" 2-18 7x1/4 x CONT. STEEL PLATE. C. A PROPERTY OWNER'S FINAL REPORT FORM FOR WORK REQUIRED TO HAVE SPECIAL INSPECTIONS , TESTING, AND STRUCTURAL OBSERVATIONS MUST BE COMPLETED BY THE SPECIAL INSPECTING AGENCY'S PROFESSIONAL ENGINEER AND SUBMITTED TO THE INSPECTION SERVICES DIVISION. WIRE TRIANGLE TIES WELDED TO BEAM @ MORTAR JOINTS @ 16" O.C. (DUR-O-WALL OR EQUAL) (2) - #6 VERTICAL EA. JAMB (WITH #5 DOWELS EPOXY GROUT INTO EXISTING FOUNDATION WALL 6" EMBEDMENT). GROUT CELLS SOLID. REMOVE EXISTING MASONRY AFTER REMAINING WALL IS SHORED NEW M.O. VARIES - SEE PLAN FRONT ELEVATION WHERE SPECIAL INSPECTION REQUIREMENTS DUPLICATE THE REQUIREMENTS OF OTHER SPECIFIED TESTING, DUPLICATE INSPECTIONS SHALL NOT BE REQUIRED. 6. REFERENCE THE FOLLOWING TABLE FOR INSPECTION REQUIREMENTS. 7. STRUCTURAL OBSERVATION (AS DEFINED IN CHAPTER 17 OF THE BUILDING CODE) IS NOT REQUIRED, UNLESS SPECIFICALLY REQUIRED BY THE BUILDING OFFICIAL. 1. WORK SHOWN IS NEW UNLESS INDICATED AS EXISTING. 2. EXISTING CONSTRUCTION SHOWN IS BASED UPON EXISTING CONDITIONS & CAN BE USED FOR BIDDING PURPOSES. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING JOB CONDITIONS, REVIEW ALL DRAWINGS & VERIFY DIMENSIONS, ELEVATIONS, & MEMBER SIZES PRIOR TO CONSTRUCTION OR MATERIAL PURCHASE. THE CONTRACTOR SHALL NOTIFY THE PROFESSIONAL OF RECORD IN WRITING OF ALL DISCREPANCIES & EXCEPTIONS BEFORE PROCEEDING WITH THE WORK. 3. THE REMOVAL, CUTTING, DRILLING, ETC. OF EXISTING CONSTRUCTION SHALL BE PERFORMED WITH GREAT CARE IN ORDER NOT TO JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF STRUCTURAL MEMBERS OR MECHANICAL, ELECTRICAL, OR ARCHITECTURAL FEATURES NOT INDICATED FOR REMOVAL INTERFERE WITH THE NEW WORK, THE PROFESSIONAL OF RECORD SHALL BE IMMEDIATELY NOTIFIED & PRIOR WRITTEN APPROVAL SHALL BE OBTAINED BEFORE REMOVAL OR MODIFICATION OF MEMBERS. 4. THE CONTRACTOR SHALL PROMPTLY REPAIR DAMAGE CAUSED DURING CONSTRUCTION WITH SIMILAR MATERIALS & WORKMANSHIP. 5. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS & METHODS OF ALL DEMOLITION WORK & FOR PROVIDING ALL NECESSARY TEMPORARY SHORING, BRACING & PROTECTION AS NECESSARY FOR SAFETY, STABILITY & PROTECTION OF ALL BUILDING ELEMENTS & STRUCTURE DURING CONSTRUCTION & DEMOLITION. TEMPORARY SHORING & BRACING SHALL BE ADEQUATE TO RESIST ALL APPLIED LOADS INCLUDING DEAD LOADS, LIVE LOADS, SNOW LOADS & CONSTRUCTION LOADS, TO PROVIDE STABILITY, & TO PROVIDE FOR RESISTANCE TO WIND & SEISMIC FORCES UNTIL ANY REQUIRED MODIFICATIONS TO THE STRUCTURE ARE COMPLETE. 5) FLOOR AND ROOF DECK WELDS SECTION VIEW 16 STEEL LINTEL - BEARING DETAIL SCALE: PERMIT/BID 02/21/13 William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. EXISTING CONSTRUCTION NOTES ______________________________________________________________________________________ A2.2 5. 1) COMPLETE AND PARTIAL PENETRATION GROOVE WELDS 5/16" REMOVE EXISTING MASONRY AND REBUILD WITH NEW MASONRY TOOTHED INTO EXISTING MASONRY 02/08/13 1" = 1'-0" PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 8" OWNER REVIEW A. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS. THE INSPECTOR MAY NOT ALTER, MODIFY, ENLARGE OR WAIVE ANY OF THE REQUIREMENTS OF THE DOCUMENTS. 1/4" STEEL PLATE. 4" HOOK EACH END THE OWNER WILL EMPLOY THE SERVICES OF ONE OR MORE SPECIAL INSPECTORS TO PROVIDE SPECIAL INSPECTIONS DURING CONSTRUCTION FOR THE REQUIRED SPECIAL INSPECTION ITEMS. DISTRIBUTIONS: STRUCTURAL STEEL 1. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING GRADES: WIDE FLANGE SHAPES............................................................A992 (Fy=50 KSI) ALL CHANNELS, ANGLES, PLATES, ETC. (U.N.O.).................A36 (Fy=36 KSI) STRUCTURAL TUBE..................................................................A500 (Fy=46 KSI) BOLTS.........................................................................................A325 (U.N.O.) ANCHOR RODS.........................................................................F1554, GRADE 36 WELDING ELECTRODES..........................................................E70XX 2. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE AISC CODE OF STANDARD PRACTICE (2005), EXCEPT AS MODIFIED IN THESE NOTES AND THE PROJECT SPECIFICATIONS. 3. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED WITHOUT WRITTEN APPROVAL OF THE PROFESSIONAL-OF-RECORD. REINFORCED MASONRY SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH, f'm = 1500 PSI. MASONRY UNITS SHALL BE NORMAL WEIGHT BLOCK CONFORMING TO ASTM C90, GRADE N, TYPE 1, AND SHALL HAVE A MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1900 PSI. MORTAR SHALL CONFORM TO ASTM C270, TYPE S. GROUT SHALL CONFORM TO ASTM C476 AND SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2000 PSI. 2. MASONRY REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, UNLESS NOTED OTHERWISE. 3. CONTINUOUS WIRE REINFORCING (JOINT REINFORCING) SHALL BE GALVANIZED TRUSS OR LADDER TYPE FORMED FROM 9 GAUGE COLD-DRAWN STEEL WIRE COMPLYING WITH ASTM A82. JOINT REINFORCING SHALL BE SPACED AT 16" O.C. VERTICALLY IN ALL MASONRY WALLS. 4. ALL REINFORCED CELLS AND ALL CELLS BELOW THE FINISHED FLOOR ELEVATION SHALL BE GROUTED SOLID. 5. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL BLOCK CORE, IT SHALL NOT BE SLOPED MORE THAN ONE HORIZONTAL IN SIX VERTICAL. DOWELS MAY BE GROUTED INTO A CELL IN VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN ADJACENT CELL TO THE VERTICAL WALL REINFORCING. GROUT THE CELL FOR THE FULL HEIGHT OF THE DOWEL. ALL REINFORCING STEEL SHALL BE CENTERED IN THE MASONRY UNIT CELL, UNLESS NOTED OTHERWISE. TYP. 4" 1/4" CLOSURE CAP - SEAL WELD ALL AROUND HSS 4x4x1/4 POST 6. 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 UNDERSIDE OF EXISTING ROOF DECK TYP. 1. PROJECT: REINFORCED MASONRY 4" 2" 2" 1'-4" TYP. NEW OPENING 1 IN EXISTING WALL _____________________________________________________ 1/8" = 1'-0" 2" HILTI HAS RODS - DRILL & ADHERE 4 1/2" INTO EXISTING SOLID GROUTED C.M.U. W/ HILTI HIT HY-150 MAX ADHESIVE ANCHORING SYSTEM. GROUT CELLS SOLID A MINIMUM OF 24 HOURS PRIOR TO INSTALLING ANCHORS WHERE VOID. 3/16 (3) SIDES 7. ALL REINFORCING STEEL SHALL BE SECURED IN PLACE BEFORE GROUTING STARTS. 8. ALL REINFORCING BARS SHALL HAVE A MINIMUM GROUT COVER OF 1/2" TO THE INSIDE FACE OF THE MASONRY UNIT, A MINIMUM OF TOTAL MASONRY COVER OF 2". 9. ALL REINFORCING BARS IN WALLS SHALL HAVE NOT LESS THAN ONE BAR DIAMETER NOR 1" CLEAR BETWEEN BARS. 10. VERTICAL CELLS THAT WILL BE GROUTED SHALL HAVE A VERTICAL ALIGNMENT TO MAINTAIN A CONTINUOUS UNOBSTRUCTED CELL AREA NOT LESS THAN 3"x4". 11. GROUTING SHALL BE STOPPED 1 1/2" BELOW THE TOP OF A COURSE SO AS TO FORM A KEY AT THE POUR JOINT. 12. GROUTING OF MASONRY BEAMS AND LINTELS OVER OPENINGS SHALL BE DONE IN ONE CONTINUOUS OPERATION. 13. ALL BOLTS, ANCHORS, ETC., INSERTED IN THE WALLS, SHALL BE GROUTED SOLID INTO POSITION. SIM. SCALE: ADHERE 4 1/2" INTO EXISTING SOLID GROUTED C.M.U. W/ HILTI HIT HY-150 MAX ADHESIVE ANCHORING SYSTEM. GROUT CELLS SOLID A MINIMUM OF 24 HOURS PRIOR TO INSTALLING ANCHORS WHERE VOID. 8" L4x4x1/4x12" (EACH SIDE) ANCHOR TO EXISTING A2.2 L4x4x1/4x4" (EACH SIDE) @ 48" O.C. MAX. ANCHOR TO EXISTING SOLID GROUTED C.M.U. WALL W/ 2" NEW STEEL LINTEL. SEE 16/A2.2 3/16 2 DETAIL __________________________________ A2.2 SCALE: 1 1/2" = 1'-0" (3) SIDES - 4" LONG SIDE CENTER 3 DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM JLH 02/08/13 313243 DETAIL __________________________________ A2.2 SCALE: 1 1/2" = 1'-0" SHEET 4 OF 6 DEMOLITION KEYED NOTES: LANDLORD TO REMOVE EXISTING BUIDLING SIGNAGE COMPLETE. DISTRIBUTIONS: OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 EXISTING INSULATED PANELS IN STOREFRONT TO BE REMOVED COMPLETE. PATCH AND REPAIR ADJACENT SURFACES TO LIKE NEW CONDITION FOR INSTALLATION OF NEW STOREFRONT GLASS. EXISTING DOOR, FRAME & HARDWARE, AND PORTION OF EXISTING EXTERIOR WALL TO BE REMOVED AS NECESSARY FOR INSTALLATION OF NEW DELIVERY DOORS. SEE DEMOLITION PLAN AND FLOOR PLAN FOR MORE INFORMATION. TENANT G.C. TO REMOVE EXISTING WOOD AND METAL PANELS COMPLETE. PATCH AND REPAIR EXISTING FRAMING & SHEATHING TO REMAIN AS REQUIRED FOR INSTALLATION OF NEW EIFS SYSTEM. PAINT SPECIFICATION TOP OF CANOPY ELEV. 112'-6" KEYED NOTES: O'REILLY RED SHERWIN WILLIAMS MIX BASE---B65R338/B60V30-GALLON FORMULA QV-45 TW-15 CLEAR COAT--DIAMOND CLAD CLEAR COAT URETHANE B65T105/B65V105/B65C105-3 COMPONENT SIGN: APPROXIMATE OUTLINE OF SIGN. PROVIDE BLOCKING AS REQUIRED FOR MOUNTING OF SIGN, COORDINATE WITH SIGN COMPANY FOR EXACT SIGN PLACEMENT. OWNER FURNISHED AND INSTALLED LOGO. REFER TO SIGN PACKET INFORMATION FOR FURTHER DETAIL. 12' TYP FINISH FLOOR HEIGHT ELEV. 100'-0" EXISTING STOREFRONT SYSTEM: EXISTING ALUM. AND GLASS STOREFRONT SYSTEM TO REMAIN. NEW STOREFRONT GLASS: INFILL OPENING WITH NEW GLASS STOREFRONT TO MATCH EXISTING. EXISTING BUILDING EIFS: EXISTING BUILDING EIFS TO REMAIN. GC TO PAINT TO MATCH REST OF BUILDING. VERIFY EXISTING COLOR WITH LANDLORD. NEW BUILDING EIFS: G.C. TO INSTALL NEW BUILDING EIFS ON EXISTING CANOPY AS SHOWN. GC TO PAINT "O'REILLY RED". REFER TO EXTERIOR FINISH SCHEDULE FOR MORE INFORMATION. COLD WEATHER APPLICATIONS: SHERWIN WILLIAMS PAINT (1) COAT S-W LOXON BLOCK SURFACER (NO LESS THAN 8 MILS) (2) COATS S-W ULTRACRETE SOLVENT BORNE SMOOTH B46 (NO LESS THAN 8 MILS EACH COAT OR 16 MILS TOTAL) EXISTING BUILDING MASONRY: EXISTING BUILDING MASONRY TO REMAIN. GC TO PAINT TO MATCH REST OF BUILDING. VERIFY EXISTING COLOR WITH LANDLORD. NEW DOOR AND FRAME: (REFER TO DOOR SCHEDULE AND EXTERIOR FINISH SCHEDULE) EXISTING DOWNSPOUT: EXISTING DOWNSPOUT & GUTTER TO REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. VERIFY EXISTING PAINT COLOR WITH LANDLORD. 16 RIGHT SIDE ELEVATION _____________________________________________________________ A3 SCALE: EXISTING GAS METER: EXISTING GAS METER TO REMAIN. 1/8" = 1'-0" EXISTING ELECTRICAL EQUIPMENT: EXISTING ELECTRICAL EQUIPMENT TO REMAIN. EXISTING STEEL COLUMN: EXISTING STEEL COLUMN TO REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. TOP OF PARAPET ELEV. 122'-8" EXISTING LOADING DOCK: EXISTING LOADING DOCK, STAIR, HANDRAIL & GUARD RAIL TO REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. TOP OF BUILDING ELEV. 115'-4" INTERNATIONAL SYMBOL OF ACCESSIBILITY: G.C. TO INSTALL INTERNATIONAL SYMBOL OF ACCESSIBILITY AT MAIN ENTRANCE. REFER TO 4/A4. TOP OF CANOPY ELEV. 112'-6" TOP OF STOREFRONT ELEV. 111'-10" Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. ADDRESS NUMBERS: 6" HIGH VINYL BY GC. COLOR TO BE WHITE. CONCRETE BLOCK SHERWIN WILLIAMS PAINT (1) COAT S-W PREPRITE BLOCK FILLER B25W25 (NO LESS THAN 8 MILS) (2) COATS S-W CONFLEX XL SMOOTH ELASTOMERIC A5-400 (NO LESS THAN 5.7 MILS EACH COAT) BOTTOM OF CANOPY ELEV. 109'-4 7/8" William Bandle Jr. License #4914 Exp. Date: 06/30/13 PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 TOP OF PARAPET ELEV. 122'-8" EXISTING CANOPY: EXISTING CANOPY REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. BOTTOM OF CANOPY ELEV. 109'-4 7/8" EXISTING WALL LIGHT: EXISTING WALL LIGHT TO REMAIN. REFER TO ELECTRICAL DRAWINGS. NEW WALL PACK LIGHT: REFER TO ELECTRICAL DRAWINGS. FINISH FLOOR HEIGHT ELEV. 100'-0" EXISTING WALL VENT: EXISTING WALL VENT TO REMAIN. TYPICAL. FINISH FLOOR HEIGHT ELEV. 100'-0" EXISTING METAL CAP FLASHING: EXISTING METAL CAP FLASHING TO REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. VERIFY EXISTING PAINT COLOR WITH LANDLORD. METAL CAP FLASHING: METAL CAP FLASHING. COLOR TO BE FIELD PAINTED "O'REILLY RED" TO MATCH E.I.F.S. REFER TO EXTERIOR FINISH SCHEDULE. 11 LEFT SIDE ELEVATION __________________________________________________________ A3 SCALE: EXISTING BUILDING MASONRY: EXISTING BUILDING MASONRY TO REMAIN. GC TO TOUCH UP EXISTING PAINT AS NEEDED. VERIFY EXISTING PAINT COLOR WITH LANDLORD. 1/8" = 1'-0" PROJECT: TOP OF BUILDING ELEV. 115'-4" FINISH FLOOR HEIGHT ELEV. 100'-0" A3 SCALE: PROPOSED 8 REAR ELEVATION ________________________________________________ 1/8" = 1'-0" A3 SCALE: 1/8" = 1'-0" 63" O'REILLY WITH 31" "AUTO PARTS" CHANNEL LETTERS TOP OF PARAPET ELEV. 122'-8" 10'-10" EXTERIOR FINISH SCHEDULE TYPE: TOP OF STOREFRONT ELEV. 111'-10" COMPANY TYPE: COLOR: EXTERIOR INSULATION AND FINISH SYSTEM (E.I.F.S.) DRYVIT - OUTSULATION PLUS MD SANDBLAST FINISH "O'REILLY RED" ORAP011030S WITH DRYVIT STRATOTONE HIGH PERFORMANCE COLORANT (FACTORY MIXED ONLY) EXTERIOR DOORS OWNER PAINT TO MATCH BUILDING FIELD COLOR OWNER "O'REILLY RED" (VERIFY MIX BELOW MATCHES E.I.F.S. COLOR) SHERWIN WILLIAMS MIX BASE: ---B65R338-B60V30-GALLON FORMULA QV: 45 TW: 15 CLEAR COAT--DIAMOND CLAD CLEAR COAT URETHANE B65T105/B65V105/B65C105-3 COMPONENT 321 FINISH FLOOR HEIGHT ELEV. 100'-0" EXISTING 1 FRONT ELEVATION ___________________________________________________ A3 SCALE: 1/8" = 1'-0" 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 EXISTING 6 REAR ELEVATION ________________________________________________ PROPOSED 3 FRONT ELEVATION ___________________________________________________ A3 SCALE: 1/8" = 1'-0" SHEET METAL CAP FLASHING AT E.I.F.S. DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 A3 SHEET 5 OF 6 GENERAL NOTES: TOILET ACCESSORIES 9'-0" A.F.F. T.O.W. MK 9'-0" A.F.F. T.O.W. 3'-0" A.F.F. TO SPOUT 27" 21 INTERIOR ELEVATION 23 INTERIOR ELEVATION _________________________________________________________ SCALE: _________________________________________________________ 1/4" = 1'-0" SCALE: A4 1/4" = 1'-0" EX'G 1'-6" B 3 5/8" 8'-10" CC CC B MEN'S RESTROOM 104 WOMEN'S RESTROOM 105 CL S43 MEN'S RESTROOM 104 G CL E 2'-2" E S43 CL J 3'-8" 7'-4" F G 1'-5" GRAB BAR BOBRICK B-6806 X 36" 33"-36" TO T.O. GRAB BAR REFER TO 5/A4 GRAB BAR BOBRICK B-6806 X 18" 39"-41" TO B.O. GRAB BAR REFER TO 5/A4 SANITARY NAPKIN RECEPTACLE BOBRICK B-270 27" A.F.F. TO TOP AT WOMEN'S RM ONLY SOAP DISPENSER ( BY OWNER ) 38" A.F.F. TO SOAP BY OWNER ( N.I.C.) PAPER TOWEL DISPENSER ( BY OWNER ) 4'-0" TO TOWELS BY OWNER ( N.I.C.) BOBRICK ROCKWOOD ROCKWOOD B-293-1836 18" W X 36" H 38" A.F.F. TO B.O. REFLECT. SURFACE METAL EDGE BF687 BLUE 60" A.F.F. TO CENTER WHITE TEXT ON BLACK BACKGROUND REFER TO 4/A4 60" A.F.F. TO CENTER WHITE TEXT ON BLACK BACKGROUND REFER TO 4/A4 60" A.F.F. TO CENTER N/A BF688 BLUE REFER TO SHEET P1 (REFER TO PLUMBING SHEETS FOR WATER HEATER SPECIFICATIONS) H 18" CLR. SCALE: A4 39-41" C GRAB BAR 36" LONG - SEE 5/A4 39-41" TO 18" BOTTOM 33"-36" T.O. GRAB BAR CL6" FLOOR DRAIN: ( REFER TO M.E.P. PLANS ) MOP SINK: ( REFER TO M.E.P. PLANS ) EYE WASH / STATION: PLACE @ 48" ABOVE FINISH FLOOR ( REFER TO M.E.P. PLANS ) DRINKING FOUNTAIN: ( REFER TO M.E.P. PLANS ). William Bandle Jr. License #4914 Exp. Date: 06/30/13 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. PAINT: ( REFER TO FINISH SCHEDULE ) FRP PANEL: ( REFER TO FINISH SCHEDULE ) DOOR: ( REFER TO FINISH SCHEDULE ) BASE: ( REFER TO FINISH SCHEDULE ) CLEAR FLOOR SPACE: 60" x 56" CLEAR FLOOR SPACE AT TOILET. CLEAR FLOOR SPACE: 60" CLEAR TURNING DIAMETER. WALL TRIM: 1X4 WOOD TRIM, PAINT TO MATCH WALL. WALL HUNG URINAL: ( REFER TO M.E.P. PLANS ) CC GRAB BAR 18" LONG - SEE 5/A4 18" 1/4" = 1'-0" 17" D SANITARY NAPKIN RECEPTACLE E SOAP DISPENSER F 40" MAX TO 1/4" = 1'-0" WALL HUNG LAVATORY: ( REFER TO M.E.P. PLANS ) PAPER TOWEL DISPENSER REFLECTIVE SURFACE SCALE: 36" CL 48" A4 GRAB BAR 48" LONG REFER TO 5/A4 CL TO TOWELS 1/4" = 1'-0" B 38" SCALE: MEN'S 13 RESTROOM ELEVATION _____________________________________________________________ TISSUE PAPER DISPENSER 27" A4 ACCESSIBILITY 12 CLEARANCE PLAN __________________________________________________ A TO SOAP ENLARGED 11 RESTROOM PLAN ________________________________________________ 33"-36" T.O. GRAB BAR 15"-48" A.F.F. 1'-5" TO RIM NOTE: FOR ACCESSIBILITY CLEARANCES SEE 12/A4. CL 48" 02/21/13 WATER CLOSET: ( REFER TO M.E.P. PLANS ) CLEAR FLOOR SPACE: 30" x 48" CLEAR FLOOR SPACE AT URINAL. C 6" L PERMIT/BID KEYED NOTES: CLEAR FLOOR SPACE: 48" DEEP CLEAR FLOOR SPACE WITH 12" AT STRIKE EDGE AT DOOR. 3'-0" 7"-9" CL 02/08/13 REFER TO FINISH SCHEDULE ON SHEET F1 FOR MATERIAL FINISH TYPES AND LOCATIONS. CLEAR FLOOR SPACE: 48" DEEP CLEAR FLOOR SPACE WITH 24" AT STRIKE EDGE AT DOOR. FLUSH CONTROLS TO BE ON WIDE SIDE OF TOILETS. OWNER REVIEW CLEAR FLOOR SPACE: 30" x 48" CLEAR FLOOR SPACE AT LAVATORY. ALL EXPOSED PIPING TO BE COVERED W/ INSULATION. K B. REFER TO PLUMBING / ELECTRICAL PLANS FOR SYSTEMS AND TYPES WOOD BLOCKING: 2" SOLID FIRE TREATED WOOD BLOCKING. 2. IT IS THE CONTRACTORS OPTION TO DIRECT ORDER AND PURCHASE TOILET ACCESSORIES THROUGH LOCKNET (EXCLUDING ITEMS LABELED "OWNER SUPPLIED". REFER TO SHEET A2 FOR CONTACT INFORMATION. CL A. WALL CONSTRUCTION: ( REFER TO FLOOR PLAN FOR TYPES ) NOTE: 1. CONTRACTOR TO PROVIDE FIRE TREATED WOOD BLOCKING FOR INSTALLATION OF ALL TOILET ACCESSORIES C S43 WOMEN'S RESTROOM 105 REFER TO 5/A4 WATER HEATER 3 5/8" 4'-5" C BY OWNER ( N.I.C. ) 33"-36" TO T.O. GRAB BAR K D 15"-48" A.F.F TO B.O. ROLL B-6806 X 48" WOMEN'S ACCESSIBLE RR SIGNAGE A REMARKS BOBRICK MOP HANGER A MOUNTED HEIGHT GRAB BAR MEN'S ACCESSIBLE RR SIGNAGE 6" 6'-10" ( BY OWNER ) TILT MIRROR 16'-5 5/8" MODEL NUMBER MANUFACTURER TISSUE PAPER DISPENSER H 3'-6" A.F.F. TO SPOUT J A4 DESCRIPTION PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 NOTE: REFER TO DETAIL 4/A4 FOR RESTROOM SIGNAGE DETAILS. DISTRIBUTIONS: G TILT MIRROR ACCESSORY 14 MOUNTING HEIGHTS _______________________________________________________ D 1/4" = 1'-0" A4 SCALE: 18" CLR. 18" CLR. WOMEN'S 7 RESTROOM ELEVATION _____________________________________________________________ MEN'S 8 RESTROOM ELEVATION _____________________________________________________________ 1/4" = 1'-0" A4 SCALE: MEN'S 9 RESTROOM ELEVATION _____________________________________________________________ 1/4" = 1'-0" 27" MIN. ALL EXPOSED PIPING TO BE COVERED W/ INSULATION. 5'-0" MIN. A4 SCALE: 1/4" = 1'-0" 11" MIN. 17" MIN. 10 LAVATORY CLEARANCES ________________________________________________________________ A4 SCALE: 1/2" = 1'-0" 6" (TYP.) CEILING CL SHEET ROCK REFER TO SHEET F1 FOR FINISH OPEN OPEN OPEN OPEN OPEN OPEN 1 FLOOR TO CEILING HEADER ELEVATION A4 SCALE: 1/4" = 1'-0" H RAISED GENDER TEXT (TYP.) J RAISED BRAILLE GENDER TEXT (TYP.) NOTES: 1. SIGNS SHALL CONFORM TO ANSI OR LOCAL ACCESSIBILITY GUIDELINES WHICHEVER IS MORE STRINGENT. 2. ALL BUILDINGS AND ENTRANCES THAT ARE ACCESSIBLE AND USABLE BY PERSONS WITH DISABILITIES SHALL BE IDENTIFIED WITH A MINIMUM OF ONE INTERNATIONAL SYMBOL OF ACCESSIBILITY. 3. G.C. TO PROVIDE TACTILE "EXIT" SIGNS AT ALL GRADE LEVEL EXIT DOORS PER CODE. 4. SIGNS TO BE INSTALLED ON THE LATCH SIDE OF THE DOOR, OR IF NO SPACE ON THE NEAREST WALL PREFERABLY ON THE RIGHT. SIGNAGE SHALL HAVE NON GLARE FINISH W/ A CONTRASTING BACKGROUND. SEE A1.1 FOR LOCATION OF SIGNAGE. P _________________________________________________________________________________________________ INTERNATIONAL SYMBOL OF ACCESSIBILITY GRAB BAR SUPPORT BAR FASTENER & MOUNTING SUPPORT SHALL BE ABLE TO WITHSTAND 250#/FT. IN BENDING, SHEAR & TENSION. RAISED GENDER SYMBOLS (TYP.) 9" FROM DOOR FRAME TO OF SIGN - TYP. 6'-10" OPEN GRADE 2 BRAILLE WITH DOTS 1/10" ON CENTER AND 2/10" SPACE BETWEEN CELLS RAISED 1/40" PER CODE CL RAISED DISABLED SYMBOLS (TYP.) 8" (TYP.) PEGBOARD AND FACE TRIM TO BE PAINTED FLAT BLACK OPEN CHARACTER HEIGHT SHALL BE A MINIMUM OF 3" PER CODE INSTALL LATTICE TRIM BEFORE BLOCKING AND TRIM REFER TO WALL TYPE DETAIL PAINT INSIDE TRIM CUSTOM COLOR "OREILLY GREEN" 11'-10" 8" MIN. 5'-0" A.F.F. TO OF SIGN - TYP. SCALE: A 1'-6" CLR. 5'-0" MIN. WOMEN'S 6 RESTROOM ELEVATION _____________________________________________________________ B A 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 A C PROJECT: B A 9" MIN. C D FLUSH CONTROLS TO BE ON WIDE SIDE OF TOILETS. C 17"-19" L 18" CLR. A4 CC 29" MIN. FLUSH CONTROLS TO BE ON WIDE SIDE OF TOILETS. G E 38" MAX. C CC ALL EXPOSED PIPING TO BE COVERED W/ INSULATION. F 1 1/2" MIN. CLR. G E 2'-10" TO RIM 17"-19" 1 1/2" MIN. CLR. B REFER TO PLUMBING SHEETS FOR FIXTURE TYPES. ALL EXPOSED PIPING TO BE COVERED W/ INSULATION. F 2'-10" TO RIM REFER TO PLUMBING SHEETS FOR FIXTURE TYPES. 1/4" = 1'-0" 34" MAX. SCALE: A4 NOTES: 1. WIDTH VARIES DEPENDING ON AMOUNT OF WALL UNITS REQUIRED. 2. REFER TO FIXTURE PLAN FOR DETAILS. 3. REFER TO FLOOR PLAN FOR DIMENSIONS. 4 ACCESSIBLE SIGNAGE A4 SCALE: _____________________________________________________________ 1 1/2" = 1'-0" MIN. 1 1/4" MAX. 1 1/2" 1 1/2" TYP. 5 GRAB BAR DETAIL A4 SCALE: __________________________________________________ 1 1/2" = 1'-0" DRAWN: CHECKED: DATE: JOB NO.: SHEET: JAM CMS 02/08/13 313243 A4 SHEET 6 OF 6 DISTRIBUTIONS: FINISH SCHEDULE A MARK ROOM * FLOOR * BASE NORTH EAST SOUTH WEST CEILING CEILING HEIGHT NOTES 100 PARTS AREA ( A ) F-1 B-1 W-3 W-3 W-3 W-3 C-1 11'-10" 2 101 PARTS AREA ( B ) F-2 --- W-3 W-3 W-3 W-3 E'XG EXPOSED 1 102 OFFICE F-2 B-1 W-3 W-3 W-3 W-3 C-2 8'-6" 1 103 PARTS AREA (C) F-2 --- W-3 W-3 W-3 W-3 E'XG EXPOSED 1 104 MENS REST ROOM F-2 B-1 W-5 W-5 W-5 W-5 C-3 8'-6" 1 105 WOMENS REST ROOM F-2 B-1 W-5 W-5 W-5 W-5 C-3 8'-6" 1 OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 M 1 MEN'S TOILET RM. 104 24" 30" 3'-0" 27" 8'-0" 5'-0" 3'-4" ( * REFER TO FINISH LEGEND FOR DETAILS ) (EX'G: EXISTING) W-1: NOT USED PARTS AREA "C" 103 Professional of Record W-3: PAINT (2) COATS ICI PAINTS (GLIDDEN) "LIGHT NAVAJO" : ULTRA HIDE INT LATEX FLAT BASE 1210-0110N WHITE TINT BLK 0 P 6 YOX 0 P 20 OXR 0 P 2 COLOR # 40YY 76/112 5'-6" W-4: PAINT (2) COATS "O'REILLY GREEN" : GLIDDEN EXTERIOR SEMI GLOSS LATEX BASE 2407-500 YOX 3P 42 TBL 4P48 GRN 3P14 WHT 2P COLOR # CUSTOM OFFICE 102 3'-2" 34" C-1: 5'-0" 12'-0" 12'-4 7/8" 45" 30" 4'-6" 30" 2'-11 1/2" 4'-6" 8'-2" 2'-11 1/2" PARTS AREA "B" 101 14'-0" C-3: PAINT (2) COATS ICI PAINTS ( GLIDDEN ) " LIGHT NAVAJO " ULTRA HIDE INT LATEX SEMI GLOSS BASE 1416-0110 WHITE TINT BLK 0 P 5 YOX 0 P 20 FFR 0 P 4 COLOR # 40YY 76/112 NO SUBSTITUTE NOTES: 1. EXTERIORS OF 102 - OFFICE, 104 AND 105 - RESTROOMS PAINTED WITH W-4 AND PROVIDE BASE B-1. 2. LOCATION OF BASE INDICATED ON DRAWING. FINISH LEGEND 8'-0" F-1: POLISHED CONCRETE: IF EXISTING CONCRETE FLOORS CANNOT BE FINISHED TO O'REILLY'S STANDARDS OF SATISFACTION, G.C. SHALL CONTACT THE P.A. BEFORE PROCEEDING. 2" 5 2'-0" X 4'-0" ACOUSTICAL LAY-IN: LAY-IN EXPOSED WHITE METAL GRID, INTERMEDIATE DUTY-DOUBLE WEB CONSTRUCTION (.013 MTL. THICKNESS) WITH LAY-IN PANELS OF ARMSTRONG #1729 "FINE FISSURED" MINABOARD TEST DATA: FIRE RESIST/FLAME SPREAD: CLASS A (UL) ASTM CLASSIFICATION: TYPE III, FORM 2, PATTERN: C E C-2: PAINT (2) COATS ICI PAINTS (GLIDDEN) "LIGHT NAVAJO" : ULTRA HIDE INT LATEX FLAT BASE 1210-0110N WHITE TINT BLK 0 P 6 YOX 0 P 20 OXR 0 P 2 COLOR # 40YY 76/112 35" F1 FLOOR FINISH IN SHADED AREA (PARTS AREA "A") ONLY. 6'-2" 11'-0 3/8" 30" 2'-11 1/2" 8'-2" 4'-6" 4 4'-0" 8'-2" 2'-11 1/2" 4'-6" 30" 30" 24" 30" 24" 30" 24" 30" 24" 30" 24" 30" 24" 30" 24" 36" 10'-0" 26'-8" 2'-11 1/2" 3 W-5: NUDO FIBER - LITE FRP LINER PANEL (OR APPROVED EQUAL) .090 TEXTURED MODEL NO. LP-F9 (WHITE) PARTS AREA "A" 100 4'-6" SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 44'-0" William Bandle Jr. License #4914 Exp. Date: 06/30/13 W-2: NOT USED 12'-0" 30" 4'-0" 2 24" 30" 24" 30" 24" 4'-5 7/8" WOMEN'S TOILET RM. 105 3'-7 3/4" 6'-0" 30" 24" 30" 24" 32" F-2: SEALED CONCRETE IF EXISTING CONCRETE FLOORS CANNOT BE FINISHED TO O'REILLY'S STANDARDS OF SATISFACTION, G.C. SHALL CONTACT THE P.A. BEFORE PROCEEDING. AREA/EGRESS PLAN: SCALE: 1/8" = 1'-0" B-1: BASE: DOOR "B" 69" EXIT MFG: VPI SPECIFIED: EQUIVALENT BY JOHNSONITE, ROPPE, AFCO. OR APPROVED EQUAL. COLOR: JET #01 SIZE: 4" X 1/8" THICK COVE TOE. NOTE: PROVIDE PIECES OF 2' LENGTH BASE FOR INSTALLATION AT END OF FIXTURES AT ENTRANCE OF PARTS AREA ( B ). M GENERAL NOTES: A. DIMENSIONS TO ROUGH FACE OF FRAMING OR TO FINISH EDGE UNLESS OTHERWISE NOTED. B. FIXTURES AND EQUIPMENT ARE FOR REFERENCE ONLY. (N.I.C.) C. MATERIAL SYMBOLS ARE FOR GRAPHIC PURPOSES ONLY AND MAY NOT REFLECT JOINT LAYOUT REQUIREMENTS. DOOR A COMMON 74'-0" PATH TRAVEL 142'-4" DISTANCE DOOR B 37'-10" 37'-10" RESTROOMS PARTS AREA "C" 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 F1 PROJECT: 6 FINISH PLAN ______________________________________ OFFICE COMMON PATH TRAVEL DISTANCE DOOR A DOOR B 10'-2" 57'-10" 79'-2" 105'-6" COMMON PATH TRAVEL DISTANCE DOOR A DOOR B 4'-0" 25'-8" 68'-6" 79'-4" PARTS AREA "B" PARTS AREA "A" DRAWN: CHECKED: DATE: JOB NO.: SHEET: DOOR "A" 33" EXIT JAM CMS 02/08/13 313243 F1 SHEET 1 OF 1 1 M 1 T 2 HVAC OUTDOOR AIR REQUIREMENTS KEYED NOTES: A M CO EXISTING ROOFTOP UNIT TO REMAIN. BALANCE OUTSIDE AIR AS INDICATED ON SCHEDULE (SHEET M2). CONTRACTOR SHALL SERVICE EXISTING AIR CONDITIONING SYSTEM COMPLETELY INCLUDING, BUT NOT LIMITED TO, CLEANING INTERIOR AND EXTERIOR OF ALL COMPONENTS, TOUCH UP PAINTING, REPLACING AIR FILTERS, INSPECTING AND REPLACING FAN BELTS, CHECKING EVAPORATOR AND CONDENSER FANS AND FAN MOTORS, CLEANING AND COMBING EVAPORATOR AND CONDENSER COILS, CHECKING AND TRIMMING REFRIGERANT CHARGE, CHECKING COMPRESSOR AMP DRAW, CHECKING DAMPER OPERATION AND DAMPER MOTORS, CLEANING CONDENSATE DRAIN & TRAP, ETC., TO ENSURE PROPER OPERATION. SHOULD ANY REPAIRS BE REQUIRED, CONTRACTOR SHALL IMMEDIATELY NOTIFY OWNER'S REPRESENTATIVE AND SUBMIT A WRITTEN COST PROPOSAL INCLUDING COMPLETE COST TO PLACE UNIT IN "LIKE NEW" CONDITION AND TIME ESTIMATE TO COMPLETE REPAIRS. MECHANICAL LEGEND SUPPLY DIFFUSER (4-WAY) 1. SHOWROOM = 6611 SQUARE FEET 2. OFFICE = 83 SQUARE FEET DISTRIBUTIONS: OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 SUPPLY DIFFUSER (1-WAY) RETURN AIR GRILLE 2006 INTERNATIONAL MECHANICAL CODE REFERENCES: TABLE FOR REQUIRED OUTDOOR VENTILATION AIR EXHAUST REGISTER X1 (TYP. 2) 75 8x6 75 WOMEN'S TOILET RM. 105 COM S2 S2 200 200 200 200 G1 G1 G1 G1 XRTU-2 S 4 8 (TYP.5) 24x22 7 5 TO RELATED THERMOSTAT EF-1 2 (TYP.3) 6 DTS 3 G1 G1 265 265 PARTS AREA "C" 103 XRTU-2 G1 G1 265 150 1 PROVIDE TRANSITION AS REQUIRED TO CONNECT NEW SUPPLY & RETURN DUCTS TO EXISTING DROPS. SEE PLAN FOR DUCT SIZES. FIELD VERIFY EXACT LOCATION, SIZES, ETC. OF DUCT DROPS. SD 10 3 675 S1 3590 cfm 9 4 PROVIDE TEE WITH TURNING VANES AND VOLUME DAMPER IN EACH DIRECTION. TRANSITION TO ROUND DUCT WITH A CONCENTRIC FITTING. 5 MOUNT UNIT HEATER ON WALL AS HIGH AS POSSIBLE, PER MANUFACTURER'S INSTRUCTIONS. SEE SCHEDULE ON SHEET M2 FOR MORE INFORMATION. 6 INSTALL DUCT TEMPERATURE SENSOR (DTS) IN SUPPLY DUCT DROP FROM ROOF TOP UNIT. 7 WALL CAP - MOUNT AS HIGH AS POSSIBLE. 8 MOUNT "ZSM" IN THIS LOCATION. SEE DETAIL 2/M1 FOR INSTALLATION. 9 INSTALL DUCT SMOKE DETECTOR IN MAIN RETURN DUCT PER LOCAL CODE. 10 COVER OPEN END OF RETURN DUCT WITH A MESH FRAME, PER DETAIL ON SHEET M2. 11 12"x12" DUCT WITH ELBOW UP FROM "R2" TO JUST ABOVE THE CEILING PLATFORM. R2 TO RELATED THERMOSTAT 30x18 3 3 UH-2 COM 5 INSTALL COMMUNICATIONS CABLE FROM THERMOSTATS TO THE HUB MODULE MOUNTED WITH THE "EMS" SYSTEM (SEE SHEET ES2) - TYPICAL OF 2. SEE SHEET E2 FOR MOUNTING OF ADM EQUIPMENT. 150 OFFICE 102 SALES: ("SPECIALTY SHOPS - HARDWARE" OCCUPANCY) 6611 (SQ. FT.) / 1000 (SQ. FT.) = 6.611 6.611 X 8 (PERSONS PER 1000 SQ. FT.) = 53 PEOPLE 53 PEOPLE X 15 (CFM PER PERSON) = 795 CFM OUTSIDE AIR REQ'D OFFICE: ("OFFICES - OFFICE SPACES" OCCUPANCY) 83 (SQ. FT.) / 1000 (SQ. FT.) = 0.083 0.083 X 7 (PERSONS PER 1000 SQ. FT.) = 1 PERSON 1 PERSONS X 20 (CFM PER PERSON) = 20 CFM OUTSIDE AIR REQ'D G1 S1 EXISTING EXHAUST REGISTER RECTANGULAR OR ROUND DUCT 795 CFM + 20 CFM = 815 CFM (REQUIRED) XRTU-1 XRTU-2 EXISTING DUCT (VERIFY SIZE/SHAPE) 410 CFM OUTSIDE AIR 410 CFM OUTSIDE AIR EXISTING FLEX DUCT - FIELD VERIFY TOTAL PROVIDED = 820 CFM FLEXIBLE DUCT (MAXIMUM LENGTH = 5'-0") NOTE: UTILIZATION OF FLEX DUCT SHALL BE ONLY AS INDICATED ON HVAC PLAN CONSTRUCTION DOCUMENTS WERE PREPARED FROM PHOTOGRAPHS AND A FIELD SURVEY REPORT (BY OTHERS). SOME ASSUMPTIONS WERE MADE REGARDING EXISTING STRUCTURE, EQUIPMENT, SIZES, AND LOCATIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING A BID. CONTRACTOR SHALL CONTACT ENGINEER OR ARCHITECT OF RECORD WITH ANY CONFLICTS. S2 600 EXISTING RETURN AIR GRILLE NOTE: 11 675 EXISTING SUPPLY DIFFUSER T THERMOSTAT S ZONE SENSOR MODULE (ZSM) COM CATEGORY 5 COMMUNICATION CABLE DTS DUCT TEMPERATURE SENSOR MOTORIZED DAMPER NOTE: MOUNT NEW DUCTWORK TIGHT TO STRUCTURE. ALL BRANCH TAKE-OFFS FROM ROUND DUCT SHALL HAVE SADDLE TAP FITTINGS. ALL AIR DEVICES SHALL BE PLACED SO AS NOT TO INTERFERE WITH LIGHTING OR FIXTURE PLACEMENT. C CONDENSATE PIPING R REFRIGERANT PIPING AIR FLOW INDICATOR PARTS AREA "A" 100 SADDLE TAP FITTING TURNING VANES 150 675 675 S1 S1 Professional of Record SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. DUCT SMOKE DETECTOR SD M PARTS AREA "B" 101 MICHAEL C. GRAPPERHAUS License #29412 Exp. Date: 06/30/14 G1 AIRFLOW (CFM) REQUIRED AIR DEVISE MARK # KEYED NOTE REFERENCE PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 MEN'S TOILET RM. 104 100 UH-1 2 650 G1 4 20x18 N.I.C. NOT IN CONTRACT NTS NOT TO SCALE EX. EXISTING F.V. FIELD VERIFY 28x18 VOLUME DAMPER 3 XRTU-1 675 1 S1 TO RELATED THERMOSTAT COM SD 9 8 CONTINUOUS VAPOR BARRIER S XRTU-1 5 SNAPLOCK SHEETMETAL ROUND DUCT HVAC PLAN SCALE: 1/8" = 1'-0" 4" WIDE SEALING STRIP SECURED IN PLACE W/ 100% ADHESIVE COVERAGE DUCTS MUST BE AIR TIGHT UNLESS OTHERWISE NOTED DUCT WRAP SHALL BE 1 1/2" THICK 1 LB. DENSITY DRAWING IS DIAGRAMMATIC AND NOT TO BE SCALED. REFER TO ARCHITECTURAL PLANS OR FIELD MEASUREMENTS FOR DIMENSIONS. 2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES NOTED ON THE COVER SHEET. 3. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONSTRUCTION PRIOR TO SUBMITTING HIS BID. NO EXTRAS WILL BE PAID DUE TO UNANTICIPATED FIELD CONDITIONS. 4. ALL ROOF AND WALL PENETRATIONS SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR. PROVIDE ALL SLEEVES, FLASHINGS, CURBS, REINFORCING ANGLES, SUPPORTING FRAMES, ETC. REQUIRED UNLESS THEY ARE SPECIFICALLY CALLED OUT TO BE FURNISHED BY OTHERS. 5. A SUBMITTAL OF ALL MATERIALS AND EQUIPMENT PROPOSED TO BE USED ON THE JOB SHALL BE PREPARED AS SOON AS POSSIBLE AFTER AWARD OF THE CONTRACT. THE SUBMITTAL WILL BE REVIEWED BY THE OWNER FOR EQUAL QUALITY AND PERFORMANCE TO THE ITEMS SPECIFIED. ALL CONTROL DEVICES SHALL BE INCLUDED IN THE SUBMITTAL. 6. PROPER PERFORMANCE OF THE CONTROL SYSTEM IS THE RESPONSIBILITY OF THE CONTRACTOR. 7. THE CONTRACTOR SHALL COOPERATE AND COORDINATE HIS WORK WITH THE WORK OF OTHER SUBCONTRACTORS OF THE PROJECT. COORDINATION DOES NOT MEAN "I WAS HERE FIRST". 8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE AND FUNCTIONAL SYSTEM IN ACCORDANCE WITH THE INTENT OF THE PLAN, WHETHER OR NOT EVERY ELEMENT THEREOF IS SPECIFICALLY CALLED OUT. 9. DUCT DIMENSIONS ON PLANS ARE TO BE FINISHED INSIDE DIMENSIONS. PROVIDE MECHANICAL FASTENERS WHERE REQUIRED. ROUND DUCT 5 WRAP INSULATION M1 1/4" THICK FOAM RUBBER OR CORK PAD. MOUNTING SCREWS PENETRATE PAD INTO SUITABLE SUPPORTING WALL MEMBER. PAD TO COMPLETELY COVER BACK OF SENSOR FLOOR RTU ZONE SENSOR MODULE "ZSM" SEE 1/M1 FOR THERMOSTAT LOCATIONS T 2 CONTINUE TO HUB MODULE (SEE SHEET ES2) 3 M1 LINER JOINTS MUST BE AT CORNERS DUCT LINER WHERE REQUIRED FLOW RTU EMS WIRING SQUARE OR RECTANGULAR ELBOW JOINTS TIGHTLY BUTTED TOGETHER W/ 100% ADHESIVE COVERAGE SINGLE THICKNESS VANES UP TO 16" LONG. DOUBLE THICKNESS VANES OVER 16" LONG. 12. ALL WORK IS TO BE GUARANTEED FOR ONE YEAR UPON OCCUPANCY. 13. NO EQUIPMENT OR FIXTURE SUBSTITUTIONS (THAT ARE NOT CURRENTLY LISTED) WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER. 14. UPON COMPLETION, BALANCE SYSTEMS TO AIRFLOWS SHOWN. REPORT THE BALANCING MEASUREMENTS ON THE "AS BUILT" DRAWINGS. 15. MOUNT NEW CONDENSATE AND REFRIGERANT LINES AS HIGH AS POSSIBLE. SHEETMETAL DUCT DUCTS MUST BE AIR TIGHT UNLESS OTHERWISE NOTED DUCT LINING SHALL BE 1" THICK 1 1/2 LB. DENSITY. COM WALL ZONE SENSOR 2 MODULE INSTALLATION SHEETMETAL DUCT ZONE SENSOR MODULE (ZSM) S COM M1 DUCT SIZES GIVEN ARE CLEAR INSIDE 11. INSULATE NEW HVAC CONDENSATE DRAIN PIPING WITH 1/2" ARMAFLEX. FLOW CO M MOUNTED "ZSM" AT 7'-3" A.F.F. TO BOTTOM OF SENSOR DUCT THERMOSTAT SENSOR (DTS) FLOW ZSM 10. DUCT MATERIALS SHALL MEET THE LATEST EDITION OF SMACNA HVAC DUCT CONSTRUCTION STANDARDS. INSTALL TURNING VANES IN ALL ELBOWS. DO NOT SUBSTITUTE RADIUSED ELBOWS. SEE DIFFUSER INSTALLATION DETAILS ON SHEET M2. LINING SECURED TO DUCT WITH 100% COVERAGE OF ADHESIVE COM M1 1. DUCT SIZES GIVEN ARE CLEAR INSIDE 7'-3" 1 GENERAL NOTES: 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 900cfm (TYP.4) 650 PROJECT: S1 R1 6 48x14 675 CONNECTION OF NEW TO EXISTING G1 TO RELATED THERMOSTAT DTS COM 16. CONTROL WIRING BY HVAC CONTRACTOR, FINAL CONNECTIONS BY HVAC CONTRACTOR. 17. ALL CAULKING ON BUILDING PENETRATIONS SHALL BE A ONE-COMPONENT NON-SAG URETHANE ELASTOMERIC SEALANT. ANY CONTRACTOR WHO USES SILICONE OR ANY OTHER CAULKING WILL BE REQUIRED TO REMOVE AND REPLACE IT AT HIS OWN EXPENSE. PROVIDE MECHANICAL FASTENERS WHERE REQUIRED. 18. THE HVAC SYSTEM SHALL BE CONSTRUCTED IN ACCORDANCE WITH NFPA 101:7-2 AND NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS." RECTANGULAR 4 DUCT LINER INSULATION 6 M1 M1 TURNING VANES 19. ALL HVAC SYSTEM FLUES AND VENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH NFPA 54 (LATEST EDITION). DRAWN: CHECKED: DATE: JOB NO.: SHEET: CLQ MCG 02/08/13 313243 M1 SHEET 1 OF 2 DISTRIBUTIONS: EXISTING ROOFTOP UNIT SCHEDULE SELF-TAPPING SHEET METAL SCREWS AT 6" O.C. RETURN DUCT - SEE PLAN FOR SIZE MARK DESCRIPTION XRTU-1 XRTU-2 EXISTING ROOFTOP UNIT (GAS) MFR. MODEL NO. DISCHARGE TONS ESP CFM OUTSIDE AIR TRANE YSC120E3E VERTICAL 10 VERIFY 4000 410 ENTERING AIR CONDITIONS (ARI) NET COOLING CAPACITY (MBH) ARI EER 113 11.3 ELECTRICAL MCA/ HEATING CAPACITY (IN/OUT) VOLTS/PH/HZ MOCP 200/160 208-230/3/60 50.3/60 UNIT WEIGHT ACCESSORIES REPLACE EX. WITH TS1, DTS, ZSM, SD OWNER REVIEW 02/08/13 PERMIT/BID 02/21/13 EX. NOTES: 1. INFORMATION PROVIDED ABOVE IS BASED ON SURVEY AND/OR INFORMATION SUPPLIED BY OTHERS. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BID. ** **PERFORMANCE DATA SCHEDULED ABOVE IS BASED ON MANUFACTURER'S AVAILABLE LITERATURE AND MUST BE VERIFIED / ADJUSTED FOR EXISTING FIELD CONDITIONS. 2. ALSO REFER TO KEYED NOTE #1 ON SHEET M1. ACCESSORIES - O'REILLY SUPPLIED AND FIELD INSTALLED 3. ADJUST OUTDOOR AIR QUANTITIES INDICATED ABOVE (ALSO REFER TO CHART ON M1). 4. CONTRACTOR SHALL CONFIRM BREAKER SIZE MATCHES NAME PLATE ELECTRICAL DATA. NOTIFY OWNER'S REPRESENTATIVE OF ANY DISCREPANCIES. TS1 - T-STAT - ADMMicro MODEL TS-300 COMMUNICATING THERMOSTAT WITH AUTO-CHANGEOVER, 2-STAGE COOLING, 2-STAGE HEATING, (NO SUBSTITUTIONS) DTS - DUCT TEMPERATURE SENSOR. - ADMMicro MODEL DTS-1 TEMP. SENSOR (NO SUBSTITUTIONS) 5. CONTRACTOR SHALL FIELD CONFIRM SIZE OF ANY EXISTING SUPPLEMENTAL HEAT. CONTACT PROFESSIONAL OF RECORD IF REVISIONS MAY BE REQUIRED. 1" MESH ZSM - ZONE SENSOR MODULE - ADMMicro MODEL ADM-ZSM-00 (NO SUBSTITUTIONS) INSTALL FRAME (WITH 1" FILTER) AT OPEN END OF RETURN DUCT Professional of Record GRILLE AND DIFFUSER SCHEDULE (RETURN DUCTS ONLY) SNAPLOCK SHEET METAL FLAT OVAL DUCT FINISH MOUNTING BRANCH DUCT SIZE EPL 24x24 WHITE LAY-IN SEE PLAN ANEMOSTAT E-1-D 12x12 WHITE SURFACE SEE PLAN DT SUPPLY GRILLE ANEMOSTAT S20H 14x8 WHITE DUCT SEE PLAN OB R1 RETURN GRILLE ANEMOSTAT S3HD-81 24x24 WHITE LAY-IN N/A R2 RETURN GRILLE ANEMOSTAT S3HD-81 12x12 WHITE SURFACE N/A X1 EXHAUST GRILLE ANEMOSTAT 12x12 WHITE SURFACE DESCRIPTION MFR. S1 SUPPLY DIFFUSER ANEMOSTAT S2 SUPPLY DIFFUSER G1 CAT. NO. S3HS - 5 4/M2 (SIM.) SEE PLAN 4/M2 (SIM.) OB 2. UNLESS NOTED OTHERWISE - NECK SIZE OF DIFFUSER WILL MATCH DUCTWORK RUNOUTS TO THE DIFFUSERS. 3. 1-WAY AIR FLOW 4. 4-WAY AIR FLOW 5. PROVIDE 1" FIBERGLASS FILTER FOR GRILLE. * KRUEGER UNIT HEATER SCHEDULE MARK MFG/MODEL CFM HTG. KW WEIGHT UH-1, 2 REZNOR EGHB10AK2 700 10 45lbs. ELECT. VOLT / PH ACC'S. REMARKS 1, 2 1 ACCESSORY OPTIONS: 1. CL5 THERMOSTAT (SEE ELEC. FOR INSTALLATION) 2. DISCONNECT REMARKS: 1. HORIZONTAL WALL MOUNT WITH SUPPLIED MOUNTING KIT PER MANUFACTURER'S INSTRUCTIONS. EXHAUST FAN SCHEDULE MARK EF-1 DESCRIPTION MFR. DOUBLE RESTROOM COOK IN-LINE EXHAUST FAN CAT. NO. GN-340 ACCESSORIES DIFFUSER IN LAY-IN PANEL OR CENTERED IN CEILING TILE. SEE SCHEDULE. REFER TO PLAN FOR DIRECTION OF THROW. 3/M2 (SIM.) DIRECTIONAL TABS. 3" WIDE GALVANIZED STRAP SUPPORT AT 5'-0" O.C. SQUARE x ROUND ADAPTER 5 DT - CLAMP AND TAPE ALL FLEX DUCT JOINTS SADDLE TAP FITTING (IF FROM ROUND DUCT) WITH BALANCING DAMPER EQUIVALENT TO "AIR TIGHT TAKEOFF" #CATDR JONESBORO AR. PHONE# 1-870-935-8483 - DIRECTIONAL TABS, ADJUST TO PROVIDE THROW AS INDICATED ON PLANS. SCALE: N.T.S. ROUND DUCT WITH DUCT WRAP INSULATION. 4/M2 1. 2 INSULATED DUCT INSTALLATION UL LISTED CLASS 1 PREINSULATED FLEX DUCT RUNOUT TO DIFFUSER, NOT OVER 8 FEET LONG. SIZE SAME AS DIFFUSER NECK. 1, 2, 3 OPPOSED BLADE DAMPER. ALL TRANSVERSE DUCT JOINTS SHALL BE SEALED WITH DUCT SEALANT (SMACNA SEAL CLASS "C"). DUCT SEALANT SHALL BE OF THE SYNTHETIC ELASTOMERIC TYPE EQUAL TO "UNITED" "UNI-SEAL". DUCT TAPE SHALL NOT BE USED AS THE PRIMARY SEALANT INSULATED DUCT SEE DETAILS ON M1 3/M2 OB - * CARNES * PRICE INDUSTRIES SUPPORT DIFFUSER FROM ROOF FRAMING WITH WIRE AS REQUIRED TO PREVENT SAGGING OF CEILING 2, 4 REMARKS GRILLES, DIFFUSERS, AND DAMPERS * TUTTLE AND BAILEY * NAILOR * ARROW * TITUS M2 REF. DETAIL ACCESSORIES APPROVED ALTERNATE MANUFACTURER'S 8" WIDE X 20 GAUGE GALVANIZED STEEL PLATE SHIELD REQUIRED AT EACH HANGER, FULL WIDTH OF DUCT AND AT EACH POINT OF CONTACT WITH STRUCTURE ABOVE DUCT REMARKS ACCESSORIES BD DS WC - BACK DRAFT DAMPER - DISCONNECT SWITCH, PRE WIRED - WALL CAP - COOK #WCA-2, ALUMINUM CFM (NOM) 200 STATIC MOTOR PRESS. H.P. 0.125 132W ELECTRICAL ACC.'S REMARKS VOLTS/PH 120/1 BD, DS, WC REF. DETAIL 1, 2 - REMARKS 1. ADJUST FOR CFM REQUIRED 2. EXHAUST FAN SHALL BE WIRED BY THE ELEC. CONTRACTOR TO OPERATE WITH EITHER RESTROOM LIGHT SWITCH. APPROVED ALTERNATE MANUFACTURER'S FANS: * GREENHECK * CARNES PROJECT: 20 GAUGE GALVANIZED SHEET METAL STRAPS ATTACHED TO STRUCTURE ABOVE SIZE (IN.) MARK PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 SCALE: N.T.S. - SMOKE DETECTOR - DUCT SMOKE DETECTOR - PROVIDE MODEL COMPATIBLE WITH EMS EQUIPMENT. SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. 1 REMOVABLE FRAME M2 SD MICHAEL C. GRAPPERHAUS License #29412 Exp. Date: 06/30/14 M2 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 3 TYPICAL LAY-IN DIFFUSER SCALE: N.T.S. INSULATED ROUND DUCT (WHERE APPLICABLE) FRAMING SPACING 16" O.C. 5/8" SHEETROCK (EACH SIDE) 6" METAL STUDS SURFACE MOUNTED SUPPLY AIR GRILLE 12" x 12" CEILING OPENING 13" 4 SURFACE MOUNTED DIFFUSER M2 SCALE: N.T.S. DRAWN: CHECKED: DATE: JOB NO.: SHEET: CLQ MCG 02/08/13 313243 M2 SHEET 2 OF 2 PLUMBING FIXTURE SCHEDULE 1 CW 3 PIPING REQUIREMENTS MARK CW TP WOMEN'S TOILET RM 105 FD S S 4 MEN'S TOILET RM 104 FD S FD MB URN WASTE VENT SUPPLY REMARKS AMERICAN STANDARD CADET RIGHT HEIGHT 16-1/2"H PRESSURE ASSISTED WATER CLOSET #2467.016 CHURCH 9500CT WHITE OPEN FRONT SEAT COMPLETE WITH BOLT CAPS. 4" 2" 1/2" LOW CONSUMPTION, 1.6gpf (MAX.) - MEETS ADA GUIDELINES & "ANSI A117.1" ZURN, ELJER URN URINAL (WALL-MOUNTED) AMERICAN STANDARD LYNBROOK 1.0gpf 6601.012 SLOAN ROYAL #186-1 FLUSH VALVE, JAY R. SMITH SERIES #600 FLOOR-MOUNTED URINAL SUPPORT 2" 1-1/2" 3/4" - KOHLER ELJER, CRANE LAV HANDICAP ACCESSIBLE LAVATORY (WALL MOUNTED) AMERICAN STANDARD LUCERNE 0355.012 4" CENTERS 2" 1-1/2" 3/4" SEE NOTE 2 ZURN, ELJER, WADE HDF BARRIER-FREE TWO STATION HI/LO DRINKING FOUNTAIN ELKAY 1-1/2" 1-1/2" 1/2" FD FLOOR DRAIN JAY R. SMITH 2005-A-(PB) (CAST IRON) 2" 2" - UPPER HEIGHT 40" A.F.F. LOWER HEIGHT 33" A.F.F. ADA COMPLY - CO CLEANOUT (INTERIOR) JAY R. SMITH 4100 SEE PLAN - - SAME SIZE AS LINE URN S HW ACCESSORIES CLASSIC CENTERSET FAUCET, JAY R. SMITH #0700-M31 FLOOR MOUNTED LAVATORY SUPPORTS EZSTL8LC ACCESSORY APRON #LKAPREZL ON UPPER UNIT (THREE SIDES OF CONTROL) (ADA COMPLIANT WHEN MOUNTED ON EXPOSED WALL) CARPET CLAMPING RING AS REQUIRED THERMAL MIXING VALVE TOILET ROOMS NOTE: REFER TO SANITARY & WATER RISER DIAGRAMS FOR PIPE SIZING. WADE, ZURN KEY KEY 2 ENL. WATER PLAN SCALE: 3/8" = 1'-0" P1 ENL. SANITARY PLAN SCALE: 3/8" = 1'-0" 1/2"CW 2"V PPP, INC. P1-500 TAPPED P-TRAP ADAPTOR - - 1/2" SEE 7/P1 - WHA WATER HAMMER ARRESTER SIOUX CHIEF 652-A - - - - - JAY R. SMITH, WADE, ZURN MB MOP BASIN FIAT FIAT MSB-2424 FIAT #832-AA HOSE & BRACKET, #889-CC-24" HANGER, SPEAKMAN SC-5811-RCP FAUCET 3" 2" 3/4" WITH VACUUM BREAKER HAWS, ZURN EW EYE WASH SPEAKMAN SEF-9000 - - - 1/2" - - BFP BACKFLOW PREVENTOR WATTS 007M10T-S IF REQUIRED. FIELD VERIFY - - 1" DOUBLE CHECK VALVE TYPE FEBCO, ZURN 1. COORDINATE ROUGH-IN OF ALL PLUMBING FIXTURES WITH ARCHITECTURAL DRAWINGS. 2. SINKS AND LAVATORIES FOR HANDICAPPED ACCESS SHALL BE INSTALLED WITH OFFSET TAILPIECES. ALL SINK AND LAVATORY DRAIN AND WATER LINES SHALL BE INSULATED WITH PROTECTIVE DEVICES EQUAL TO "McGUIRE" #PW 2150 WC WHITE MOLDED CLOSED CELL VINYL, OR "TRUEBRO" #103W, WHITE MOLDED VINYL. 3/4"CW 3"V 3" DUAL VOLTAGE = 240 OR 208 @ 25% REDUCED INPUT) 40AMPS, 9.5 kW (MIN. WIRE = #8 AWG) EX95T 2" FD 1 3/4"HW 3/4"CW FD 4 2"V 4" 2"V 4" 1/2" NO SUBSTITUTIONS 1 1/2"V 3/4"CW 4" 2" LAV 3 LAV SCALE: NOT TO SCALE P1 EXTEND NEW 1" WATER FROM EXISTING MINIMUM 1" OR LARGER WATER, PRIOR TO SERVICE TO ANY RESTROOM FIXTURES. PROVIDE SHUT OFF VALVE, METER WITH REMOTE READER OR SUB-METER, BACKFLOW PREVENTOR, PRESSURE REDUCING VALVE, ETC. AS REQUIRED. FIELD VERIFY EXACT SIZE, LOCATION, PRESSURE, ETC. OF EXISTING PIPING PRIOR TO ROUGHING IN OR INSTALLING NEW PIPING. VERIFY EXACT UTILITY REQUIREMENTS. 3" HDF 4 EXTEND NEW 4" VENT THROUGH ROOF, OR USE EXISTING IF FIELD VERIFIED IN CLOSE PROXIMITY TO NEW RESTROOMS. COORDINATE NEW ROOF PENETRATION REQUIREMENTS WITH LANDLORD'S ROOFING CONTRACTOR. 1 1/2"V 2" 4" 2" WATER RISER 2 FD 2" HWC EXTEND NEW SANITARY (SEE RISER FOR SIZE) TO NEAREST EXISTING 4" MINIMUM SANITARY. FIELD VERIFY EXACT LOCATION, INVERT, FLOW, ETC. PRIOR TO ROUGHING IN OR INSTALLING NEW SANITARY PIPING. 2" 1 1/2"V 4" GENERAL PLUMBING NOTES: 1 URN HWC WH 4 4" FD 1 1/2" 3" NOTE: SEE APPLICABLE PLUMBING CODE FOR MINIMUM WASTE PIPING SLOPE. 4" 2" ROUTE NEW 2" SANITARY IN WALL AND DROP TO 4" SANITARY AT MOP BASIN, TO MINIMIZE WORK BELOW THE SLAB. FIELD VERIFY REQUIRED SLOPE, INVERT, ETC. PRIOR TO ROUGHING IN OR INSTALLING NEW PIPING. CO CW SANITARY RISER 2. ALL PLUMBING WORK IS TO BE DONE IN ACCORDANCE WITH THE APPLICABLE CODE(S) NOTED ON THE COVER SHEET. 3. PIPING MATERIAL (UNDERGROUND & ABOVE GROUND WATER, DRAIN, WASTE & VENT) SHALL BE PER APPLICABLE CODE NOTED ON THE COVER SHEET. 4. VALVES ON WATER LINES SHALL BE BRONZE BALL VALVES. DO NOT SUBSTITUTE GATE OR GLOBE VALVES. VALVES SHALL BE THE SAME SIZE AS THEIR INLET PIPING. 5. ALL PLUMBING FIXTURES ARE TO BE FURNISHED COMPLETE WITH NECESSARY STOPS, TRAPS, TAILPIECES, TRIM, ETC. 6. THE CONTRACTOR SHALL COOPERATE AND COORDINATE WITH ALL OTHER CONTRACTORS AND SUBCONTRACTORS IN LAYING OUT AND INSTALLING THIS WORK. 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE AND FUNCTIONAL SYSTEM IN ACCORDANCE WITH THE INTENT OF THE PLANS, WHETHER OR NOT EVERY ELEMENT THEREOF IS SPECIFICALLY CALLED OUT. 8. DO NOT INSTALL CAPPED AIR CHAMBERS AT FIXTURES. INSTALL WATER HAMMER ARRESTORS AS CALLED FOR ON PLAN. ARRESTORS ARE TO BE RATED FOR INSTALLATION IN CONCEALED LOCATIONS. 9. ALL HOT AND COLD WATER SUPPLY PIPING CONNECTIONS TO FIXTURES SHALL BE 1/2" UNLESS NOTED OTHERWISE. 10. PLUMBING PIPING SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. PROVIDE REQUIRED CLEARANCES PER "N.E.C.". COORDINATE ELECTRICAL PANELS LOCATIONS WITH THE ELECTRICAL CONTRACTOR. 11. INSTALL PIPE INSULATION ON ALL DOMESTIC WATER LINES ABOVE FINISHED FLOOR BALL VALVE CW CW NOTE: SET WATER HEATER CONTINUE HOT AND COLD WATER LINES AS SHOWN ON ENLARGED SUPPLY PIPING PLAN CW MOP HANGER 12. CONTRACTOR SHALL COORDINATE WITH ALL STATE AND LOCAL BUILDING REGULATION AGENCIES AND UTILITY COMPANY(S) IN THE PROCUREMENT OF AND PAYMENT OF ALL PERMITS, LICENSES, FEES AND CHARGES REQUIRED FOR THE PERFORMANCE OF THE WORK. 3/4" X 1/2" TEE. HW TRAP PRIMER VALVE WITH INTEGRAL BACKFLOW PREVENTER AND VACUUM BREAKER PORT. PRECISION PLUMBING PRODUCTS MODEL P1-500. COLD WATER SUPPLY HW HOT AND COLD WATER LINES INSIDE WALL 1" EXPOSED CW SHUT OFF VALVE. SEE ENLARGED PIPING PLAN. DISTRIBUTION UNIT #DU-2 WH HW AND CW LINES TO LAV NEW INSTANTANEOUS WATER HEATER 1/2" PEX POLYETHYLENE TUBING. ROUTE THRU PARTITION OR IN WALL AND UNDER SLAB BELOW FLOOR TO P-TRAPS, SEE PLAN. LAV EYEWASH (EW) 2'-5" FAUCET 10-3/4" WH 8" UNION (TYP) DISTRIBUTION UNIT TO BE MOUNTED (ABOVE CEILING) HWC EXPOSED HW OUT (INSULATED) 2-7/8" 5" 5-1/4" MOP BASIN (MB) 18. INSTALL ACCESS PANELS OR DOORS WHERE EQUIPMENT AND/OR VALVES ARE INSTALLED IN CONCEALED LOCATIONS. FINISHED FLR. WATER HEATER MOUNTING HGT. TAPPED P-TRAP ADAPTER, PPP INC. OR EQUAL P1 HOT WATER PIPING WASTE LINE P-TRAP WALL BASE SCALE: NOT TO SCALE 15. ALL CAULKING ON BUILDING PENETRATIONS SHALL BE ELASTOMERIC POLYURETHANE (NO EXCEPTIONS) EQUIVALENT TO "VULKEM" 116. ANY CONTRACTOR WHO USED SILICONE OR ANY OTHER CAULKING WILL BE REQUIRED TO REMOVE AND REPLACE WITH ELASTOMERIC POLYURETHANE AT HIS OWN EXPENSE. 17. PLUMBING SUB-CONTRACTOR SHALL INFORM THE ELECTRICAL SUB-CONTRACTOR OF THE VOLTAGE AND POWER REQUIREMENTS OF ALL PLUMBING EQUIPMENT TO BE INSTALLED. NO FITTINGS BELOW SLAB ALLOWED 6 14. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ROUTE ALL WATER PIPING AROUND SPACES WITH TEMPERATURES BELOW FREEZING (i.e. ATTICS, CHASES, EXTERIOR WALLS, ETC.) IF FREEZING OF ANY WATER PIPING OCCURS IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR THE PIPING THRU A NON-FREEZING SPACE TO THE FIXTURE / APPLIANCE ORIGINALLY SERVED BY THE FROZEN PIPING. FINISH FLOOR EXPOSED CW (INSULATED) 48" HOSE BRACKET 13. PROVIDE CHROME ESCUTCHEON COVERPLATES AT ALL PIPE PENETRATIONS OF FINISHED WALL SURFACES. 16. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FROM THE DATE OF ACCEPTANCE BY THE OWNER ON ALL WORK PERFORMED. 10-1/4" 36" DRAWING IS DIAGRAMMATIC AND IS NOT TO BE SCALED. REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS. SCALE: NOT TO SCALE 1" CW DISTRIBUTION. SEE ENLARGED PIPING PLAN. ELV. AT MOP BASIN 1. 4" 1" INCOMING CW. SEE ENLARGED PIPING PLAN. 54" - ATTN: SANDI YOUNG - DIRECT LINE: (314) 573-2082 / [email protected] or SAM CAST - DIRECT LINE: (314) 573-2081 / [email protected] TOLL FREE PHONE: (800) 289-5254 TOLL FREE FAX: (888) 280-0128 GRAYBAR ELECTRIC CO., INC. 11885 LACKLAND RD. ST. LOUIS, MO 63146 KEYED NOTES: 4" 3 NO FLAT VENTING ALLOWED. DRY VENTS SHALL RISE VERTICALLY TO 6" (MIN.) ABOVE FLOOR LEVEL RIM OF HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. P1 - UL LISTED FOR USE WITHOUT PRESSURE RELIEF VALVE. 3"V 4"V HWC SCALE: NOT TO SCALE FOR HANDICAPPED-ACCESSIBLE WATER CLOSETS, FURNISH AND INSTALL WITH FLUSH HANDLE ON THE WIDE SIDE OF THE RESTROOM. 233 South Patterson Springfield, MO 65802 Phone: (417) 862-2674 3/4"CW 3/4"HW 1/2"CW 1"CW HWC URN 5 SHEETS BEARING THIS SEAL ARE AUTHENTICATED, RESPONSIBILITY FOR ALL OTHER PLANS, SPEC'S OR INSTRUMENTS ARE DISCLAIMED. 1 1/2"V MB 4" P1 3. WHA MB 3 INSTANT WATER HEATER EEMAX "THERMOSTATIC" WATER HEATER SHALL BE DIRECT ORDERED AND OR RELEASED FROM THE LISTED ELECTRICAL EQUIPMENT DISTRIBUTOR: W 1/2" 1/2" HDF MICHAEL C. GRAPPERHAUS License #29412 Exp. Date: 06/30/14 Professional of Record 2"V 2 1"C W "C - TRAP PRIMER WH LAV TMV 3/8" OWNER SUPPLIED, CONTRACTOR INSTALLED 4"VTR LAV TMV - 02/21/13 NOTE: 2"V TP - TP TOILET ROOMS NOTE: REFER TO SANITARY & WATER RISER DIAGRAMS FOR PIPE SIZING. 3/4 - PERMIT/BID WADE, ZURN MAX. TEMP. PER ANSI/ASSE CO P1 USG-B HDF HDF 1 WATTS 02/08/13 HALSEY TAYLOR 3/8" TEMPERED OUTLET, TMV OWNER REVIEW PROJECT: CW LAV LAV LAV WH CATALOG NO. HANDICAP ACCESSIBLE WATER CLOSET (TANK TYPE) CW LAV MANUFACTURER APPROVED MANUFACTURERS HWC S EW MEN'S TOILET RM 104 CW FD HWC HW CW WOMEN'S TOILET RM 105 HWC MB HWC DESCRIPTION S S HW HWC DISTRIBUTIONS: PROJECT MANAGERS 10877 Watson Road St. Louis, MO 63127 Phone: (314) 821-1100 SEE 3 & 5/P1 7 P1 TRAP PRIMER PIPING LEGEND HW HOT WATER CW COLD WATER S WASTE (BELOW GRADE) S WASTE (ABOVE GRADE) VENT SCALE: NOT TO SCALE WATER HAMMER ARRESTER DRAWN: CHECKED: DATE: JOB NO.: SHEET: CLQ MCG 02/08/13 313243 P1 SHEET 1 OF 1