HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS

Transcription

HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 1 di 10
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1)
for PROFIBUS
ID: HT000014.HTM
Summary
This purpose of the document is to explain how to configure the Sofnet -S7 libraries for PROFIBUS.
This document has been realized by carrying out the following hardware and software configurations:
l
Windows XP Professional + service pack1
l
Movicon 9.1 (release 605)
l
Simatic NET version 6.1
l
Sofnet -S7 for PROFIBUS (6GK1704 -5CW61 -3AA0)
l
Scheda Siemens CP 5611
l
PLC Siemens S7 series
Solution
At the end of this proposed configuration communication with the PLC Siemens S7 series will be
consented in two ways:
l
Communication with "Siemens S7 Optimized (Sapi-S7 Library) driver.
l
Communication with the Movicon OPC Editor.
Sofnet-S7 Installation:
Two different Sofnet-S7 versions exist, the version 6.0 is supported in Windows NT4 and Windows
2000 operating systems; while the version 6.1 is to be installed in the Window XP operating systems.
There may be a few slight differences in the user interface between the two versions, and also in the
different service packs in the same Sofnet-S7 version, in any case the basic configuration
methodology always remains the same.
The installation process must be carried out with the CdRom supplied by Siemens, during which the
software retrieves any net cards installed in the computer, or other Siemens property cards, and
predisposes them for using. All the software presented on the CdRom are installed: AuthorsW,
SIMATIC NCM PC, SIMATIC NET PC. Carefully read the notes during the SIMATIC NET Software
installation.
Sofnet-S7 Licence:
During the installation phase you will be asked to install the software licence straight away or do it
later. Without the software licence you cannot configure the libraries but you can communicate.
As anticipated the software licence can be installed later with the "AuthorsW" software.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 2 di 10
Hardware Check:
When the installation procedure has terminated or after the computer restart, you can verify whether
the software has been installed correctly by controlling the 'Device manager' window to see if a new
"SIMATIC NET" folder has been added with a "CP 5611" card inside. The 'Device manager' window is
accessed from the Windows XP control panel found in the 'system' icon's 'hardware' tab.
A new "Simatic" folder with all the Siemens programs to be used for configuring has been added to
the Windows 'start' menu. Besides the Windows application bar there are also two new icons which
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 3 di 10
indicate the "Station Configuration Editor" and "SIMATIC NET Information Service" service status.
The Siemens programs and services we are going to use to configure the Sofnet -S7 library have
been listed below:
l
Configuration Console
l
Station Configuration Editor
l
SIMATIC NCM PC Wizard or SIMATIC NCM PC Manager
Configuration Console:
The configuration console permits you to configure the properties of each PC object used from the
siemens library for communicating.
1.
The first thing you need to do is select "Mode of the module ->Configured mode” in the
"General" folder of the CP5611 Modul and assign "Index->1”. Then press the " apply " button
to confirm selection.
2.
After this, you have to go to the "Access Points " folder and set the " CP5611(PROFBUS9)"
interface in any of the elements in the list (eg. CP_L2_1). The selection is done by selecting
the interface from the list proposed after double clicking on the "Access Point's" name in the
list. You can also create a new "Access Point" but we advise you to use one of those already
on the list between "CP_L2_1" and "CP_L2_2".
3.
In cases where you want to use an OPC type communication you need to decide which
protocol to enable for this type of communication. The S7 protocols permit you to select the
single internal PLC areas in the communication's configuration, which will result most
satisfactory when having to communicate with intelligent devices (PLC or other) which
implement this protocol.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 4 di 10
Station Configuration Editor:
The Station Configuration Editor corresponds to our station configuration inside the PC. We should
find the CP5611 card already in the "1" index, we need to insert all the other components, we need to
use, in the spaces below. There are two types of components that can be added:
l
Application ->this must be used when you want interface Sofnet -S7 with the "S732.dll"
library. You need to add this component when you want to use the "Siemens S7 Optimized"
driver to communicate with Movicon.
l
OPC Server ->this must be used when you want to interface Sofnet -S7 with an OPC client.
You need to add this component when you want to use the Movicon OPC Editor for
communication purposes.
Simatic NCM PC Wizard:
The Simatic NCM PC Wizard permits you to automatically create a project which has same
configurations that were setup with the "Station Configuration Editor".
As an alternative you can also use the " Simatic NCM PC Manager ", in which case the NCM project, to
be loaded, should already be disposed, by being retrieved from another system or previously created
with the wizard.
To create a project with the wizard you need to:
1. Startup " SIMATIC NCM PC Wizard"
2. Select "Create a new project and configuration " from the first mask and press the "Next"
button.
3. Select "Create a copy of the local PC station" from the second mask, insert a name in the
“Project name ” box and press "Next" button.
4. Select "Open a project with the SIMATIC NCM Manager " from the third mask and press the
"End" button.
Upon termination the SIMATIC NCM PC Manager " program will automatically start with the project
that has just been created with the wizard.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 5 di 10
Simatic NCM PC Manager:
The Simatic NCM PC Manager permits you to configure the details of every aspect of your PC station.
In this section the details regarding the components inserted in the "Station Configuration Editor" will
be configured, in our case: the net card, application and OPC server.
The project realised with the Wizard has to be configured like this:
1.
Open " SIMATIC NCM PC Config" with a double click on the "Configuration " (1) icon.
2.
Open the CP5611 card's configuration window with a double click (2). You need to assigne a
Profibus address to the card and set the the "SubNet->PROFIBUS(1) " in the interface property
so that "yes" will display in the "Networked" camp of the previous window, consenting the use
of the card for communicating with Siemens. Also the "Application " and "OPC Server "
components can be configured, with the usual double click, but normally the predefined
properties are left as they are.
Pressing this button, (3) on the tool bar, saves and compiles any modifications carried out.
3.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
4.
Pressing this button, (4) on the tool bar, opens the "NetPro" program used for configuring the
net.
5.
You need to highlight the "Application " or "OPC Server " box so that the new "localID" can be
added to the table below which are just the input points for the driver or the Movicon OPC
Editor. Then, by double clicking on the first line of the 'LocalID' table, you can go and
configure the access point by setting the following property:
a. In the first window specify "Station ->Unspecified" and "Connection Type ->S7
connection" and press the "OK " button.
Pagina 6 di 10
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
b.
Pagina 7 di 10
In the second window you need to set the Profibus address in the PLC port and then
press the "Address Details... " button. The Profibus address must be valid, meaning
that it is not being used by components of the same Profibus network.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
c.
In the third and last window you need to configure the "Rack/Slot" position the PLC
S7's CPU and the "Connection Resource" in the "Partner" section.
The position
"Rack/Slot" is generally 0/2 but it can vary according to the hardware configurations of
the electric cabinet which contains the PLC S7; while the "Connection Resource" must
always be set at value "3".
d.
Confirm exit from all the windows, previously opened and configured, with the 'OK'
button. This will return you back to the window at the beginning where you can set
other "LocalIDs" if you need to communicate with other PLCs on the same Profibus
network.
Pagina 8 di 10
It is not possible to configure the " LocalID " on different components (VFD
Name) with Movicon, therefore all the configured " localID " must be belong to
the same component "Application " or "OPC Server".
6.
7.
When you have finished the configurations you need to press the button (6) to save and
compile it all. We suggest you to select the "Compile and check everything" compilation
option. When the compilation procedure has finished a "No errors" message should appear
but if on the contrary you will have to check and put right any apparent problems, the
recompile and close the window returning back to the previous " Simatic NCM PC Config "
program.
Close the "Simatic NCM PC Config " program which will return you back to the beginning with
"Simatic NCM PC Manager ".
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
8.
9.
Pagina 9 di 10
Now all you have to do is transfer the project to the PC station with button (8) on the the
"Simatic NCM PC Manager'" program's tools bar remembering that you must first of all
highlight the name of the actual station, which generally coincides with the name of the
computer, first. The downloading of the applied NCM should be successful, otherwise you will
have to check the "Station Configuration Editor " component list to see if their names coincide
with those of the NCM application's.
Before terminating the "Simatic NCM PC Manager " application you can archive the project
with the appropriate command from the File menu, where it then can be reused in other
computers with the same architecture.
Movcion Configuration:
The communication configuration in the Movicon application can be setup with the OPC Editor, in
which case the "OPC Server" components should have been included in the Siemens configuration; or
with the Siemens S7 Driver Optimized and in which case the "Application" component should already
have been included in the Siemens configuration.
l
OPC Editor ->In the add a new item in the selected " OPC.SimaticNET" OPC Server group, the
connection (localID) configured in the "Simatic NCM PC Manager " on the "OPC Server "
component can be seen.
l
Siemens S7 Optimized ->When selecting " Application Access Point->CP_L2_1 " the
connection (localID), configured in "Simatic NCM PC Manager " program in the "Application"
components, will be activated. Remember that the "CP_L2_1" has been configured in the
"Configuration Console" as a access point in PROFIBUS with the CP5611 card.
file://D:\Web%20ENG%20Support%20Progea\WebHelp\Knowledgebase\Movicon%209... 13/04/2004
HOWTO: How to configure the Sofnet-S7 (ver.6.0 e ver.6.1) for PROFIBUS
Pagina 10 di 10
DownLoad :
l
Document in PDF format
l
Simatic NCM PC Manager project
References
Additional query words: Siemens, Simatic, Profibus, CP5611
Version: Movicon: 9
Platform: Windows 9x/NT/2000/XP
Issue type: kbhowto