cv 4-6000 e - Europower Components Ltd

Transcription

cv 4-6000 e - Europower Components Ltd
VPN = 4242 V
Voltage Transducer CV 4-6000
For the electronic measurement of voltages: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VPM
VS
KN
RL
CL
VC
IC
Primary nominal voltage rms
Primary voltage, measuring range
(Analog) secondary voltage @ VP maxi
Conversion ratio
Load resistance
Capacitive loading
Supply voltage (± 5 %)
Current consumption
4242
0 .. ± 6000
10
6000 V / 10 V
≥2
≤5
± 15
35 + VS / R L
V
V
V
Features
• Closed loop (compensated) voltage
transducer
kΩ
nF
V
mA
• Isolated plastic case recognized
according to UL 94-V0
• Patent pending.
Advantages
Accuracy - Dynamic performance data
XG
Overall accuracy @ VP maxi
TA = 25°C
- 25°C .. + 70°C
TA = 25°C
- 25°C .. + 70°C
VO
Offset voltage @ VP = 0
tr
BW
Response time 1) to 90 % of VPN step
Frequency bandwidth (- 3 dB) @ 50 % of VPN
Maxi
±1
±2
± 30
± 60
%
%
mV
mV
≅ 25
DC .. 11
µs
kHz
•
•
•
•
Very good linearity
Low thermal drift
Low response time
Bandwidth.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Uninterruptible Power Supplies
General data
(UPS)
TA
TS
P
R1
m
Ambient operating temperature
Ambient storage temperature
Total primary power loss
Primary resistance
Mass
Standards
- 25 .. + 70
°C
- 40 .. + 85
°C
4.28
W
4.20
MΩ
600
g
EN 50155: 1995
EN 50178: 1997
• Power supplies for welding
applications
• Railway overhead line voltage
measurement.
Application Domain
• Traction
• Industrial.
Note:
1)
With a dv/dt of 1000 V/µs.
page 1/3
061129/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com
Voltage transducer CV 4-6000
Isolation characteristics
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
9 1)
kV
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative Tracking Index (Group I)
188
124
600
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
8000 V
1000 V
Reinforced isolation
5600 V
1000 V
dCp, dCI, V W
Note:
1)
Between primary and secondary.
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
page 2/3
061129/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com
Dimensions CV 4-6000
(in mm. 1 mm = 0.0394 inch)
Front view
Left view
Right view
Top view
Connection
Mechanical characteristics
• General tolerance
• Transudcer fastening
Recommended fastening torque
• Connection of primary
• Connection of secondary
• Recommended fastening torque
Remarks
± 0.5 mm
4 slots ∅ 6.5 mm
4 M6 steel screws
5 Nm or 3.7 Lb. - Ft.
M5 threaded studs
M5 threaded studs
2.2 Nm or 1.62 Lb. -Ft.
• VS is positive when VP is applied on terminal +HT.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
page 3/3
061129/5
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com