seisco quick guide - radiant floor heat
Transcription
seisco quick guide - radiant floor heat
Quick Guide SH Models for Radiant Floor Heating Compliance & Listings: ANSI/UL 834, CSA, NSF, HUD, NEC TANKLESS ELECTRIC WATER HEATERS ROOM THERMOSTAT This new micro-boiler is the ideal replacement for traditional boilers and tank-type heaters and is the enabling technology for use with active renewable energy systems such as solar and geothermal systems. CIRCULATING PUMP EXPANSION TANK Hot Water 120 V Power Air Separator (Bleeder) SHUT OFF VALVES Check Valve *Warranted for Space Heating Applications only. Not to be used for Water Heating. Return Water RADIANT In-Floor Tubing MANIFOLD 240 V Power SEISCO Space Heater BKR BKR Return Water Double-Pole Breakers Features • ANSI/UL 834 Approval Listing for Space Heating Systems • Works with tubing and manifold systems • No minimum flow activation required • Built-in DSM Utility Integration option • Compatible with Home Energy Management Systems • Heats fluid mixtures including ethylene glycol (antifreeze) • No moving parts • Very small & compact • Light weight modular construction • No restriction to flow • Standard 3/4 inch plumbing connections • Microprocessor digital control • Power sharing & variable power control technology • Continuous venting • Heats continuously only when needed, no storage • Self-diagnostics • Redundant safety devices • High performance polymer nylon chamber material • Built-in Leak detector and alarm • Rust & corrosion resistant SEISCO FLOW RATES, TEMPERATURE RISE & HEAT RATINGS Seisco Model SH-09 SH-11 SH-14 SH-18 SH-22 SH-28 Heat Output Rating (BTU) 30,710 37,540 47,780 61,430 75,080 95,560 Max. GPM for Temp. Rise of 10°F 6.1 7.5 9.6 12.3 15.0 19.1 Max. GPM for Temp. Rise of 20°F 3.1 3.8 4.8 6.1 7.5 9.6 Max. GPM for Temp. Rise of 48°F 1.3 1.6 2.0 2.6 3.1 4.0 Max. GPM for Temp. Rise of 64°F 1.0 1.2 1.5 2.0 2.3 3.0 Max. GPM for Temp. Rise of 76°F 0.8 1.0 1.3 1.6 2.0 2.5 GPM = Gallons per minute (Flow Rate) SPACE HEATING & Active Renewable Energy Back-up SYSTEM Requirements HEATING SYSTEM Radiant Floor Hydro-Heat Baseboard Heat Dual Heating Solar Backup Heat Geothermal Backup Suggested Seisco Model(s) All Models* SH-28+ SH-28* SH-28+ SH-28, 22 SH-28, 22 Seisco Temp Setting 100-120 F 125-135 F 130-140 F 120 F 120-135 F 120-135 F Typical Heat Loss Rates for New Homes Sq. Ft. BTU Loss 3,000+ 80,000 to 125,000 2,500+ 50,000 to 80,000 1,500+ 35,000 to 50,000 800+ 20,000 to 35,000 ** Plumbed in Parallel Seisco Selection (Use 2 SH-18’s or 2 SH-22s)** (Use 1 SH-28 or 1 SH-22) (Use 1 SH-18 or 1 SH-22) (Use 1 SH-14 or 1 SH-18) * The “Heat Loss Rate” (BTU/Hr.) should be calculated by a qualified heating contractor. Select a Seisco Model BTU Rating using 125% of the calculated Heat Loss Rate for the area that is being heated. SEISCO MODEL SPECIFICATIONS Seisco Model Weight (LBS) Height (INCHES) Width (INCHES) Depth (INCHES) Plumbing Fittings (INCHES) SH-09 15 15 ¾ 10 ¼ 6¼ SH-11 15 15 ¾ 10 ¼ 6¼ SH-14 15 15 ¾ 10 ¼ 6¼ SH-18 23 15 ¾ 15 ¾ 6¼ SH-22 23 15 ¾ 15 ¾ 6¼ SH-28 23 15 ¾ 15 ¾ 6¼ ¾ ¾ ¾ ¾ ¾ ¾ Models Models SH-28 SH-22 SH-18 SH-14 SH-11 SH-09 Heating Elements (WATTS X NO.) 4500 X 2 Energy Factor 0.99+ 5500 X 2 0.99+ 7000 X 2 0.99+ 4500 X 4 0.99+ 5500 X 4 0.99+ 7000 X 4 0.99+ SEISCO ELECTRICAL RATINGS Seisco Model SH-09 SH-11 SH-14 SH-18 SH-22 SH-28 Maximum Power Rating (kW) 9 11 14 18 22 28 Voltage Rating (VAC) 240 240 240 240 240 240 Maximum Current Rating (AMPS) 37.5 46 58 75 91 116 Number of Circuits Required (Two Wire) 1 1 2* 2 2 4** Number of Circuit Breakers Required (Double Pole) 1 1 2* 2 2 4** Circuit Breaker Size (AMPS) 50 60 40 50 60 40 * Optional one (1), 75 AMP circuit supply – Check with manufacturer for jumpers that must be installed on control board for this option.