Reznor V3-UESA Gas Fired Unit Heater

Transcription

Reznor V3-UESA Gas Fired Unit Heater
UESA
HIGH EFFICIENT GAS-FIRED condensing UNIT HEATERS
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
REZNOR has over 35 years experience in designing
and refining high efficient gas-fired unit heaters.
The UESA is a condensing gas-fired unit heater and is
designed for up to 104% heat input (Hi).
The units are available in 4 different sizes, from 35 till
102 kW gas output.
Simplicity and ease of use
 Up to 25 % lighter than the previous model and easy to install.
 The unit can be easily suspended from 4 suspen-
sion points.
 All units have a factory installed gas line nipple to the exterior of the cabinet for easy gas service
connection.
 The MacroChannel secondary heat exchanger has a
Reliable and safe
3/4” PVC pipe for attaching a coupling, thus simplify-
 The UESA combustion circuit is separated from ing installation and cleaning of the required
condensate drain.
 Thanks to the the vacuum combustion circuit the space to be heated.
 All connections (gas and electricity) are accessible the unit is extra safe and approved for all European countries.
at one side of the heater.
 The internal security system protects the unit from overload and keeps the flue gas
temperature down in the flue gas circuit.
Main standard features
 The Tcore3TM high efficiency heat exchanger and
single burner combustion system.
 The titanium stabilized aluminized steel primary heat exchanger with extruded aluminium
MacroChannelSM secondary heat exchanger.
 The vibration and noise isolated fan motor.
 The sealed control compartment houses all electrical
components.
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
Guaranteed high efficiency
A conventional unit-heater does not use all available
combustion heat.
An important part of the heat is still present in the
exhausted flue gases.
The Reznor UESA is able to extract the residual heat by
leading the flue gases through a second heat
exchanger, so they cool down to a temperature below
Side view: each compartment has its own door.
the dewpoint.
Design
Environmentally friendly
The unit heaters are designed to provide all the features
Heating by gas is the most environmentally friendly
you expect in a REZNOR heater plus improved
heating method.
efficiency, easier installation and a new look ~ both
A condensing gas-fired unit heater has a higher heat
inside and out.
gain than for example a fuel oil condensing unit.
Look for the unique white unit with no visible front and
The flue gases extracted from natural gas contain less
bottom hardware, deep red louvres and angled corner
harmfull substances and the condensate is less
to know you have a genuine REZNOR unit.
corrosive.
DIMENSIONS
SIDE VIEW
FRONT VIEW
REAR VIEW
1. combustion air inlet
2. flue connection
3. gas connection
4. electrical connections
5. service panel
6. condensate drain
Dimensions (mm)
A
B
C
D
E
F
UESA 035-055
112
140
366
1512
510
456
UESA 083-102
99
225
470
1520
866
812
The dimensions are purely informative and are published with reservation.
TOP VIEW
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
BALANCED FLUE WALL AND
ROOF TERMINAL
OR
C-type: the allowed length between the unit heater and the flue terminal amounts to 9 m,
a 90° bend offering an equivalent resistance of 1,5m and a 45° bend -0,75m.
Advice: the high efficient balanced roof terminal avoids icicles.
TECHNICAL DATA
Model
UESA
035
055
Gas category
083
102
II2H3+ (UK)
Comb. air & flue, type B 1
B22p
Comb. air & flue, type C
C12, C32, C42, C52, C62, C82
1
Heat input Hs
kW
37,74
58,60
88,01
107,66
Heat input Hi
kW
34,00
52,80
79,30
97,00
Heat output
kW
34,87
54,77
82,20
99,49
Thermal efficiency
%
102,60
103,70
103,70
102,60
Gas consumption
G20
m³/h
3,60
5,60
8,40
10,30
G25
m³/h
4,20
6,50
9,80
11,90
G31
kg/h
2,70
4,10
6,20
7,60
26
26
27
27
3900
6100
9060
10570
Gas pipe connection (not Ø supply line size)
3/4”
Temperature rise ΔT ± 1
K
Air flow (15°C)
m³/h
Nominal motor speed
RPM
900
1400
900
900
Recommended mounting height 2
m
3,50
3,50
4
4
Horizontal throw
m
25
40
34
36
dB (A)
67
75
74
73
4
dB(A)
45
53
52
51
Sound pressure 5
dB(A)
52
60
59
58
Total electrical rating 6
W
628
816
990
1300
Condensate amount
l/h
2,30
3,10
6,60
7,50
Connection collars
mm
100
100
130
130
Net weight
kg
148
151
222
230
3
Sound power
Sound pressure
Electrical service (protection IP20)
230/240V 1N~50Hz
1. Gas Appliance Classifications for Approved Venting Methods based on CEN-report CR1749:2001
2. Height from floor to bottom surface of heater. These are recommendations only. Positioning of unit heaters for proper performance is application dependent. Operation is affected by other air moving equipment in the space, obstructions to the airflow, draughts and/or close proximity to doors or windows, etc… Care should taken to avoid mounting the heaters above these recom-
mendations, unless downturn nozzle options are used, as significant stratification may occur resulting in poor floor coverage and higher energy losses through the roof structure.
3. Isothermal conditions at 20°C ambient air temperature, discharge louvre zero deflection, v = 0,5 m/s.
4. Sound pressure level in dB(A) in free field conditions, measured at 5 meters from the unit
5. Sound pressure level in dB(A), measured at 5 meters from the unit with A=160m² and Q=2
6. Measured at nominal input rate with G20 at 20°C ambient temperature.
G A S T E C
A T&B Group Company
Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz
0805UESA GBEN
J&M Sabbestraat 130
B-8930 Menen
Belgium
Tel. +32(0) 56 52 95 11
Fax. +32(0) 56 52 95 33
e-mail: [email protected]
website: www.reznor.eu
Company Standards and Services:
All Reznor products are tested and approved to CE standards. Reznor Europe nv is assessed to GASTEC EN ISO 9001:
2000 Quality Assurance. Reznor offers a service to its customers; including budget schemes, on site technical support and a
comprehensive after-sales package. Reznor reserves the right to change specifications without prior notice.

Similar documents

UNIT HEA TERS

UNIT HEA TERS »» Units can be selected to operate at 60 Hz or 50 Hz »» Accurate size selection can be determined by using Reznor selection software program ●●Dependable - The standard totally enclosed motors hav...

More information

Low NO High Efficiency Condensing Unit Heaters

Low NO High Efficiency Condensing Unit Heaters Natural gas G20 Calorific value 10.48kW/m3 GCV, inlet gas pressure maximum 50mbar, minimum 17.5mbar. Propane G31 Calorific value 14.0kW/kg GCV, inlet gas pressure maximum 50mbar, minimum 37mbar.

More information